background image

38

70D0005

TPB Gas Log Set

NOTE REGARDING VENTED PRODUCTS

This  product  must  be  installed  by  a  licensed  plumber  or 
gas  fitter  when  installed  within  the  Commonwealth  of 
Massachusetts.
Any  residence  with  a  direct  vent  product  must  have  a  CO 
detector installed in the residence.
Installation  of  the  fireplace  or  vented  gas  log  in  the  State 
of  Massachusetts  requires  the  damper  to  be  permanently 
removed or welded in the fully open position.
In addition, a naturally vented gas log may not be installed in 
a bedroom or bathroom in the State of Massachusetts.
Flex  line  installation  must  not  exceed  36  inches  and  must 
have a T shutoff valve. 

NOTE REGARDING VENT FREE PRODUCTS

This  product  must  be  installed  by  a  licensed  plumber  or 
gas  fitter  when  installed  within  the  Commonwealth  of 
Massachusetts.
In  addition,  vent  free  products  may  not  be  installed  in  a 
bedroom or bathroom regardless of size or type in the State 
of Massachusetts.
Flex  line  installation  must  not  exceed  36  inches  and  must 
have a T shutoff valve.

CARBON MONOXIDE DETECTOR REQUIREMENTS

(2) Revise  10.8.3  by  adding  the  following  additional 
requirements:
(a)  

For  all  side  wall  horizontally  vented  gas  fueled 

equipment  installed  in  every  dwelling,  building  or  structure 
used  in  whole  or  in  part  for  residential  purposes,  including 
those owned or operated by the Commonwealth and where 
the  side  wall  exhaust  vent  termination  is  less  than  seven 
(7)  feet  above  finished  grade  in  the  area  of  the  venting, 
including but not limited to decks and porches, the following 
requirements shall be satisfied:
1. 

Installation of carbon monoxide detectors. 

At the time 

of  installation  of  the  side  wall  horizontal  vented  gas  fueled 
equipment, the installing plumber or gas fitter shall observe 
that  a  hard  wired  carbon  monoxide  detector  with  an  alarm 
and battery back-up is installed on the floor level where the 
gas  equipment  is  to  be  installed.  In  addition,  the  installing 
plumber  or  gas  fitter  shall  observe  that  a  battery  operated 
or  hard  wired  carbon  monoxide  detector  with  an  alarm  is 
installed on each additional level of the dwelling, building or 
structure served by the side wall horizontal vented gas fueled 
equipment. It shall be the responsibility of the property owner 
to secure the services of qualified licensed professionals for 
the installation of hard wired carbon monoxide detectors
 

a.  In the event that the side wall horizontally vented gas 

fueled equipment is installed in a crawl space or an attic, the 
hard wired carbon monoxide detector with alarm and battery 
back-up may be installed on the next adjacent floor level.
 

b.  In the event that the requirements of this subdivision 

can not be met at the time of completion of installation, the 
owner shall have a period of thirty (30) days to comply with 
the above requirements; provided, however, that during said 
thirty  (30)  day  period,  a  battery  operated  carbon  monoxide 

Massachusetts Residents Only — Please read and follow these special requirements

detector with an alarm shall be installed.
2. 

Approved  Carbon  Monoxide  Detectors.

 

Each  carbon 

monoxide detector as required in accordance with the above 
provisions shall comply with NFPA 720 and be ANSI/UL 2034 
listed and IAS certified.
3. 

Signage.

  A  metal  or  plastic  identification  plate  shall  be 

permanently  mounted  to  the  exterior  of  the  building  at  a 
minimum height of eight (8) feet above grade directly in line 
with  the  exhaust  vent  terminal  for  the  horizontally  vented 
gas  fueled  heating  appliance  or  equipment.  The  sign  shall 
read,  in  print  size  no  less  than  one-half  (1/2)  inch  in  size, 
“GAS  VENT  DIRECTLY  BELOW.  KEEP  CLEAR  OF  ALL 
OBSTRUCTIONS.”
4. 

Inspection.

  The  state  or  local  gas  inspector  of  the  side 

wall  horizontally  vented  gas  fueled  equipment  shall  not 
approve the installation unless, upon inspection, the inspector 
observes  carbon  monoxide  detectors  and  signage  installed 
in  accordance  with  the  provisions  of  248  CMR  5.08(2)(a)1 
through 4.
(b) 

Exemptions:

  The  following  equipment  is  exempt  from 

248 CMR 5.08(2)(a)1 through 4:
1.  The  equipment  listed  in  Chapter  10  entitled  "Equipment 
Not  Required  To  Be  Vented"  in  the  most  current  edition  of 
NFPA 54 as adopted by the Board; and
2. Product Approved side wall horizontally vented gas fueled 
equipment installed in a room or structure separate from the 
dwelling,  building  or  structure  used  in  whole  or  in  part  for 
residential purposes.
(c)  

Manufacturer requirements — Gas Equipment Venting 

System  Provided.

 

When  the  manufacturer  of  Product 

Approved side wall horizontally vented gas equipment provides 
a venting system design or venting system components with 
the equipment, the instructions provided by the manufacturer 
for installation of the equipment and the venting system shall 
include:
1.  Detailed  instructions  for  the  installation  of  the  venting 
system design or the venting system components; and
2.  A  complete  parts  list  for  the  venting  system  design  or 
venting system.
(d) 

Manufacturer  requirements  —  Gas  Equipment 

Venting System Not Provided. 

When the manufacturer of 

a Product Approved side wall horizontally vented gas fueled 
equipment  does  not  provide  the  parts  for  venting  the  flue 
gases, but identifies “special venting systems,” the following 
requirements shall be satisfied by the manufacturer:
1. The referenced "special venting system" instructions shall 
be  included  with  the  appliance  or  equipment  installation 
instructions; and
2. The “special venting systems” shall be Product Approved 
by the Board, and the instructions for that system shall include 
a parts list and detailed installation instructions.
(e)  

A copy of all installation instructions for all Product 

Approved side wall horizontally vented gas fueled equipment, 
all venting instructions, all parts lists for venting instructions, 
and/or all venting design

Summary of Contents for 18TPB

Page 1: ...as supplier s instructions If you cannot reach your gas supplier call the fire department Installation and service must be performed by a qualified installer service agency or the gas supplier 70D0005...

Page 2: ...ing System Operation 20 Thank you and congratulations on your purchase of a Gas Log Set PLEASE READ THE INSTALLATION AND OPERATION INSTRUCTIONS BEFORE USING THE APPLIANCE IMPORTANT Read all instructio...

Page 3: ...draperies 2 Children and adults should be alerted to the hazard of high surface temperature and should stay away to avoid burns or clothing ignition 3 Young children should be carefully supervised wh...

Page 4: ...pply piping system by closing its equipment shutoff valve during any pressure testing of the gas supply piping system at test pressures equal to or less than 1 2 psig 3 5 kPa 23 Do not use this room h...

Page 5: ...mended when handling ceramic fiber logs to prevent skin irritation from loose fibers Logs are fragile handle with care Gas Specifications Gas Rate Max Input Min Input Model Fuel Control BTU h BTU h 18...

Page 6: ...per pa sec m2 or less with openings gasketed or sealed b weather striping has been added on openable windows and doors and c caulking or sealants are applied to areas such as joints around window and...

Page 7: ...91 2001 typically referred to as a Universal Firebox as long as firebox hearth dimen sions meet the minimum hearth dimensions shown below Figure 2 Hearth Minimum Dimension Model A B C D 18TPB 26 13 18...

Page 8: ...Set in an Enclosure NOTE Non combustible material such as refractory brick may be used to line the floor of the fireplace in order to raise the height of the gas log set in relation to a restrictive...

Page 9: ...he dimensions shown in Figures 4 through 12 and defined in the fireplace manufacturer s instructions are minimum clearances to maintain when installing this heater Left and right clearances are determ...

Page 10: ...ter with chimney flue damper open Refer to Installing Vented Applications found on page 18 TABLE A Heat Resistant Material Requirements with no Mantel or Combustible Projection CLEARANCES and HEIGHT R...

Page 11: ...o less than 12 Install hood and observe pro files shown in Figure 8 page 15 OR extend heat resistant material to at least 12 and observe profiles shown in Figure 7 page 14 Install hood and observe pro...

Page 12: ...requirements Figure 8 Minimum Mantel Clearance with Hood All Models Example A mantel may project from the wall a maximum of 21 2 at a minimum of 14 above the opening and a maximum of 6 at a minimum of...

Page 13: ...mantel may project from the wall a maximum of 10 at a minimum of 28 above the opening CLEARANCES and HEIGHT requirements Figure 10 is an example of an unsafe mantel instal lation This mantel projects...

Page 14: ...is closer than 14 to the base of the fireplace The minimum distance must be maintained from the top surface of carpeting tile etc See Figure 11 OR The gas log heater may be installed nearer to the fl...

Page 15: ...ot outage or sooting Use a heat resistant seal ant Install and operate the appliance as directed in this manual Damper stop installation A damper stop must be provided with the unit Contact your deale...

Page 16: ...he grate is essential to prevent any movement of the gas logs and controls during operation Figure 14 Securing Heater to Floor of Fireplace Firebox Screw Anchor Hole Screw WARNING You must secure the...

Page 17: ...ons that the Pressure Tapping Point May Be Installed CAUTION Use new black iron or steel pipe Internally tinned copper or copper tubing can be used per National Fuel Code section 2 6 3 providing gas m...

Page 18: ...rn captured screw counter clockwise two or three turns and then place tubing to pressure gauge over test point Use test point OUT closest to control knob After taking pressure reading be sure and turn...

Page 19: ...ne wire to TH or connect the wall switch thermostat to the two male 0 25 terminals on the left side of the unit The color of the wires does not matter Figure 17 Wiring Diagram Note Log switch wires ar...

Page 20: ...Reading Thermostat contacts OPEN Main burner OFF 1 Check gas pressure to the unit If gas pressure is within minimum and maximum on data plate then check pilot voltage 500 milli volts minimum If the m...

Page 21: ...te See Figure 19 2 Place rear log 2 on two pins on back of grate allowing the right end of the rear log to rest on top of the right top log See Figure 20 Pins Rear Log 2 Right Base Log 1 WARNING The p...

Page 22: ...3 Left Base Log 3 Pins Figure 22 Installing Right Top Log 4 Right top log 4 Pins 4 Place right top log 4 on two pins located to the left of right base log See Figure 22 3 Place left base log 3 on two...

Page 23: ...PLACEMENT Figure 23 Installing Left Top Log 5 Left Top Log 5 5 Place right end of left top log 5 on bottom center grate pin Rest the left end of left top log 5 on the left base log See Figure 23 Bott...

Page 24: ...ime size pieces evenly across the burner surface in between the logs Do not add additional Rock Wool See Figure 26 Wash hands after placing Rock Wool Itching may occur Figure 26 Placing Rock Wool Dime...

Page 25: ...ing Burner on Riser Figure 28 Burner Installed on Riser Important When installing riser kit the minimum recommended height for the fire box opening will be increased by 2 the riser height Steel bar Gr...

Page 26: ...ure 32 a b Installing Andirons andiron INSTALLATION Optional andirons are available Slide the two tabs in back of each andiron under the cast iron grate The andirons may be used with or without the ri...

Page 27: ...mocouple then the main burner cannot function reli ably See Figure 34 for incorrect shape of pilot flame Milli volt Control and Thermostat control Figure 33 Correct Appearance of Pilot Flame Figure 34...

Page 28: ...burning will result During manufacturing fabricating and shipping various components of this appliance are treated with cer tain oils films or bonding agents These chemicals are not harmful but may pr...

Page 29: ...upplier s instructions If you cannot reach your gas supplier call the fire department C Use only your hand to push in or turn the gas control knob Never use tools If the knob will not push in or turn...

Page 30: ...or longer to allow air to bleed out of the gas piping 7 With the control knob pushed in push in and release the piezo ignitor button to light the pilot 8 Continue pushing the control knob in for a fur...

Page 31: ...p air intake holes clean will result in sooting and poor combustion Inspect and clean all burner ports Inspect ODS pilot for operation and accumulation of lint at air intake holes Verify flame pattern...

Page 32: ...re 2 Contact local gas company 3 ODS pilot is partially clogged 3 Clean ODS pilot 4 Defective Thermopile 4 Check wire connections Check output should be 500 milli volts across TH TP and TP Terminals w...

Page 33: ...l gas company 2 Burner orifice is clogged 2 Clean burner or replace burner orifice Slight smoke or odor during initial operation 1 Burner orifice is clogged or damaged 1 Clean burner or replace burner...

Page 34: ...Log Set replacement parts Failure to position the parts in accordance with these diagrams or failure to use only parts specifically approved with this appliance may result in property damage or perso...

Page 35: ...0468 5 Injector 1 58D0051 58D0052 70D0064 57D0680 70D0064 57D0680 6 ODS Pilot Assy 1 14D0473 14D0477 14D0473 14D0477 14D0473 14D0477 7 On Off Switch 1 32D0232 32D0232 32D0232 32D0232 32D0232 32D0232 8...

Page 36: ...specifically approved with this appliance may result in property damage or personal injury WARNING Blazing Oak Logs Item Description Qty BOCL18 BOCL24 BOCL30 1 Right Base Log 1 70D0131 70D0041 70D023...

Page 37: ...37 70D0005 TPB Gas Log Set...

Page 38: ...ith the above requirements provided however that during said thirty 30 day period a battery operated carbon monoxide Massachusetts Residents Only Please read and follow these special requirements dete...

Page 39: ...he Limited Lifetime Warranty will also be void if the appliance is not operated and maintained according to the operating instructions supplied with the appliance and does not extend to 1 firebox burn...

Page 40: ...MHSC 149 Cleveland Drive Paris Kentucky 40361 www mhsc com...

Reviews: