TPB Gas Log Set
PLACING THE DECORATIVE ROCk
FLAME APPEARANCE
Flames from the pilot and burner should be visually checked as soon as the heater is installed.
In addition, periodically check the flames visually during operation.
CHECkING THE PILOT FLAME
The pilot flame must always be present when the heater is in operation.
It should just
touch the top of the thermocouple tip for natural.
see Figure 33
for correct pilot flame.
If the pilot flame does not touch the thermocouple, then the main burner cannot function reli-
ably.
see Figure 34
for incorrect shape of pilot flame.
MILLI-VOLT CONTROL AND THERMOSTAT CONTROL
Figure 33 -
Correct Appearance of Pilot Flame
Figure 34 -
Incorrect Appearance of Pilot Flame
Thermocouple
for Natural
Thermocouple
for LP
Thermocouple
for LP
Thermocouple
for Natural
CAUTION
DO NOT sprinkle volcanic rock on the logs, around the pilot, or on or near burners.
This may cause sooting. Place volcanic rock only on the floor of the fireplace.
During initial operation of the new heater, burning logs will give off a paper burning
smell and orange flames will be present. Simply open the windows for a few hours
to vent the odor.