Gas Line Installation

When purging gas line the front glass must 
be removed.

The gas pipeline can be brought in through the right 
side of the appliance. Knockouts are provided at conve-
nient locations to allow for the gas pipe installation and 
testing of any gas connection.  
The gas line connection can be made with properly 
tinned 3/8” copper tubing, 1/2” rigid pipe or an approved 
flex connector. Since some municipalities have  addi-
tional local codes, it is always best to consult your local 
authority and the 

CSA-B149.1

 installation codes.

For USA installations consult the current National Fuel 
Gas Code, 

ANSI Z223.1/NFPA 54

.

Always check for gas leaks with a mild 
soap and water solution applied with a 
brush no larger than 1” (25 mm). Never 
apply soap and water solution with a spray 

bottle. Do not use an open flame for leak 
testing.

Framing and Finishing

Check appliance to make sure it is levelled 
and properly positioned.

1.  Choose unit location.
2.  Nailing flanges are supplied with the fireplace (found 

on the fireplace hearth). To level the box and secure 
it firmly in place, remove the nailing flanges from 
the hearth and install at the sides of the firebox as 
shown in Figure 3.

3.  Screw through the slotted holes in the drywall strip 

and into pre-drilled holes in fireplace side. Measure 
from face of fireplace to the face of the drywall strip 
to confirm the final depth.

Finishing

Noncombustible materials such as brick and tile can 
be extended over the face of the unit (Do not cover the 
glass door or grille). If a trim kit is to be installed, brick 
and tile will have to be installed flush with the side of 
this appliance.

Gas Specifications

 

 

 

 

Max. 

Min.

 

Model 

Fuel 

Gas Control 

Input 

Input

  NV360RN  Natural 

Millivolt Hi/Lo 

33,500  23,500

  NV360RP  Propane 

Millivolt Hi/Lo 

33,500  23,700

  NV580RN  Natural 

Millivolt Hi/Lo 

45,000  31,500

  NV580RP  Propane 

Millivolt Hi/Lo 

45,000  31,900

NV360 / NV580

Certified to

ANSI Z21.50b-2002 / CSA 2.22b-2002 

Vented Gas Fireplace

High Elevations

Input ratings are shown in BTU per hour and are 
certified without deration for elevations up to 
4,500 feet (1,370m) above sea level.
For elevations above 4,500 feet (1,370m) in USA, 
installations must be in accordance with the 
current ANSI Z223.1/NFPA 54 and/or local codes 
having jurisdiction.
In Canada, please consult provincial and/or local 
authorities having jurisdiction for installations at 
elevations above 4,500 feet (1,370m).

  Minimum Inlet Pressure 

5.5" w.c. 

11" w.c.

  Maximum Inlet Pressure  14.0" w.c.  14.0" w.c.
  Manifold Pressure 

3.5" w.c. 

11" w.c.

Natural

LP

Gas Inlet & Manifold Pressures

Units: H31A00, H31B00, I31A00, I31B00

FP1023

side nailing flange

1/27/00  djt

C

A

B

Adjustable Drywall Strip 

(Nailing Flanges)

 

Screw 

Drywall

  Position 

Depths

 

1/2" / 13 mm

 

5/8" / 16 mm

 

3/4" / 19 mm

Adjustable

1/2", 5/8" & 3/4" 

Spacing

FP1023

Fig. 3

  Nailing flanges.

Air Shutter Setting

 

Model 

Front 

Rear 

 

NV360RN 

closed 

closed

  NV360RP 

open 

open

  NV580RN 

closed 

closed

  NV580RP 

open 

open

Summary of Contents for NV360 Series

Page 1: ...e must be per formed by a quali ed installer service agency or the gas supplier What to do if you smell gas Do not try to light any appliance Do not touch any electric switch do not use any phone in y...

Page 2: ...as Speci cations 6 Gas Inlet Manifold Pressures 6 High Elevations 6 Gas Line Installation 6 Remote Switch Installation 7 Alternate Switch Location 7 EB 1 Electrical Box 7 Install the Venting System Fl...

Page 3: ...d not be used as a drying rack for clothing nor should Christmas stock ings or decorations be hung in the area of it 9 Under no circumstances should any solid fuels wood coal paper or cardboard etc be...

Page 4: ...mm 47 1194 mm B 37 953 mm 41 1048 mm C 36 914 mm 42 1067 mm D 24 622 mm 28 724 mm E 7 179 mm 7 179 mm F 6 152 mm 6 152 mm G 1 32 mm 1 32 mm H 19 489 mm 23 591 mm I 5 140 mm 5 140 mm J 25 641 mm 31 79...

Page 5: ...G 12 305 mm L 12 305 mm H 10 254 mm M 10 254 mm I 8 203 mm N 8 203 mm J 1 38 mm O 1 38 mm Fig 2b Combustible mantel leg minimum installation CFM170 DV Builder Front View O N M L K J F G H I Mantel Le...

Page 6: ...con rm the nal depth Finishing Noncombustible materials such as brick and tile can be extended over the face of the unit Do not cover the glass door or grille If a trim kit is to be installed brick an...

Page 7: ...4 9 WIRING DIAGRAM 1 8 99 djt 11 9 99 added thermopile Thermopile W584 9 Fig 5 Remote switch wiring diagram for R models FP1024 alternate remote switch location 1 27 00 djt FP1024 Fig 6 Alternate swit...

Page 8: ...er frame NOTE A restop is not required at the roof Fig 8 Firestop draftstop positions FP384 FIRESTOP 11 21 96 adapted from IGF53 FP384 Attic Installation Firestop position when area above ceiling is a...

Page 9: ...in height Up to an 8 ft horizontal vent run can be installed within the vent system using a maximum of two 2 90 degree elbows or four 4 45 degree elbows B Vertical installations up to 40 feet 12m in...

Page 10: ...monia household cleaner and warm water gas replace glass cleaner is recommended After initial use the glass should be cleaned two or three times during each heating season depending on the circumstanc...

Page 11: ...logs by placing a small piece of wool on your ngertip and pushing it onto the log Do not place ember material in the inside corners of the front logs Lava Rock The lava rock provided with this replace...

Page 12: ...n and bathroom 2 Light unit and operate for 5 minutes 3 Hold an ignited match cigarette or smoke match in front of the unit Refer to Figure 17 for location of the draft hood opening 4 Check to make su...

Page 13: ...down the main burner assembly The sensor is located above the rebox behind the top louvre assembly It is accessible by removing the top louvre assembly CAUTION The rebox Vent Safety Switch sensor and...

Page 14: ...HITE WHITE WHITE WHITE WHITE WHITE BLACK FP670 NOVA SIT 822 VALVE WIRING DGRM w Honeywell S8600 B Ignition Module 4 30 98 PILOT H I L O H I LO E A P I L O T 1 5 3 4 GREEN MV MVPV PV GND BURNER 24V GND...

Page 15: ...all around the heater area for gas Be sure to smell next to the oor because some gas is heavier than air and will settle on the oor WHAT TO DO IF YOU SMELL GAS Do not try to light any replace Do not t...

Page 16: ...height All Wiring connections Replace thermopile Thermocouple needs a minimum 14mV Defective valve Turn to pilot meter should read greater than 100mV If not replace Pilot Lights with Piezo Ignitor YE...

Page 17: ...le oper ates the main valve operation ON and OFF Clean and or adjust maximum ame impingement on thermopile and thermocouple Turn valve knob to PILOT Maintain ow to pilot millivolt meter should read gr...

Page 18: ...crews A pressure regulator tower B and the spring and diaphragm assembly C Fig 22 FC107 SIT820 valve conversion 10 03 A B C OFF P I L O T O N FC107 Fig 22 Remove mounting screws pressure regulator tow...

Page 19: ...Burner Pan NV580 CO110 Front View Top View Front View Fig 27 Install conversion air shutters NOTE It is not necessary to remove the pilot tube for conversion 7 Remove pilot hood by lifting up Fig 28 8...

Page 20: ...alve Most of these components may require only an oc casional checkup and cleaning and some may require adjustment If repair is necessary it should be per formed by a quali ed technician Logs May Be H...

Page 21: ...e Log Top Right B29 E7 1f Log Top Center Left E5 1g Log Top Center Right E6 2 Volcanic Rock 20000376 20000376 3 Ember Package 51915 51915 4 Lava Rock Burner 57897 57897 5a Burner Housing Assembly Natu...

Page 22: ...000616 21d Ori ce Rear Burner Natural 20002498 20003611 22 Switch ON OFF 51842 51842 23a Valve Honeywell VS8421 Natural 10001782 10001782 23b Valve Honeywell VS8421 LP 10001759 10001759 24a Valve SIT...

Page 23: ...ell Valve not shown 20000062 20000062 45 Vent Safety Switch 10002013 10002013 46a Regulator Head Natural 10001006 10001006 46b Regulator Head LP 10001007 10001007 Fuel Conversion Kits Conversion Kit N...

Page 24: ...eed control can be installed in an electrical box at normal wall switch height for conve nient access 4 The power supply may be connected in 2 ways Method A Route the 6 1 8m lead tted to the unit to a...

Page 25: ...H102 rear ceramic support 2 23 99 djt Rear Ceramic Panel Back of Firebox Burner Rear Log Support H102 Fig 37 Rear ceramic panel placement Decorative Frame Trims A selection of decorative frame trim ki...

Page 26: ...26 NV360 580 Series 20003565...

Page 27: ...tion the damage is found to be the fault of the manufacturer repairs will be authorized at no charge to the customer parts and or labor Any part and or component replaced under the provisions of this...

Page 28: ...2695 Meadowvale Blvd Mississauga Ontario Canada L5N 8A3 800 668 5323 www cfmcorp com CFM Corporation...

Reviews: