background image

13

360DVS Series Direct Vent Fireplaces

10006326

Electronic Gas Control Valve

This appliance may be fitted with a Honeywell ignition 
module. 

Installation of the remote ON/OFF starter switch on 
electronic ignition units

 (Fig. 12): 

1.  Thread the wiring through the holes on the side 

panels of the appliance. Take care not to cut the wire 
or insulation on metal edges. Route the wire to a 
conveniently located receptacle box.

2.  Attach the wire to the ON/OFF switch and install the 

switch into the receptacle box.

3.  Connect the white wire from the wall switch to the 

black wire from the transformer, using an approved 
wire nut. Connect the black wire from the wall switch 
to the black wire running from the #6 position of the 
ignition module, also using an approved wire nut.

PILOT

HONEYWELL IGNITION MODULE

ORANGE

BLUE

BLACK

WHITE

NOVA SIT 822 VALVE

HI

LO

POWER CORD

W/FEMALE SPADE

120 VAC RTN

WHITE

GREEN

BLACK

120 VAC HOT

BLACK

YELLOW

24 VAC RET

40VA TRANSFORMER

24 VAC HOT

BLACK

WHITE

WALL SWITCH

WHITE

OFF

1    2    3          5    6    8     9

 MV      MV/VP   PV                    GRD      24V     SENSE   SPARK

24V

ORANGE

RED

GREEN

BLACK

FP1225

Fig. 12

  Honeywell ignition module.

Your fireplace is approved to be vented either through 
the side wall, or vertically through the roof.

• 

Only CFM Corporation venting components, specifi-
cally approved and labeled for this fireplace, may be 
used.

• 

Venting terminals shall not be recessed into a wall or 
siding.

• 

Horizontal venting must be installed on a level plane 
without an inclining or declining slope.

There must not be any obstruction

 such as bushes, 

General Venting

garden shed, fencing, deck or utility building within 24” 
(610mm) from the front of the termination hood.
Do not locate the termination hood where excessive 
snow or ice buildup may occur. Be sure to check the 
vent termination area after snow falls; clear it to prevent 
accidental blockage of the venting system. When using 
a snow blower, make sure snow is not directed toward 
the vent termination area. 

Location of Vent Termination

It is imperative the vent termination be located observ-
ing minimum clearances as shown on the following 
page.

Summary of Contents for 360DVS2 RN

Page 1: ...soline or other flammable vapors and liquids in the vicinity of this or any other appliance If you smell gas 1 Open windows 2 Do not touch electrical switches 3 Do not try to light any appliance 4 Extinguish any open flame 5 Do not use any telephone in your building 6 Immediately call your gas supplier from a neighbor s phone 7 Follow your gas supplier s instructions 8 If you cannot reach your gas s...

Page 2: ...nstallation 17 Below Grade Installation 20 Vertical Through the Roof Application Installation 21 Twist Lock Venting Components 23 Operating Instructions Glass Information 24 Louvre Removal 24 Window Frame Assembly Removal 24 Glass Cleaning 25 Ceramic Refractory Installation 25 Log Installation 25 Lava Rock Ember Material Placement 26 Flame Temperature Adjustment 26 Flame Characteristics 27 Lightin...

Page 3: ...cess Pleaseensurethatyourroomiswellventilated open all windows Itisrecommendedthatyouburnyour fireplaceforatleast ten 10 hours the first time you use it If the optional fan kit has been installed place the fan switch in the OFF position during this time 11 When the fireplace is installed directly on carpeting vinyl tile or any combustible material other than wood it must be installed on a metal or wo...

Page 4: ...the horizontally vented gas fueled heating appliance or equipment The sign shall read in print size no less than one half 1 2 inch in size GAS VENT DIRECTLY BELOW KEEP CLEAR OF ALL OBSTRUCTIONS Inspection The state or local gas inspector of the side wall horizontally vented gas fueled equipment shall not approve the installation unless upon inspection the inspector observes carbon monoxide detecto...

Page 5: ...as Line Access Electrical Access Gas Line Access J J K J J Fireplace Dimensions 360DVS2 Rear Vent Configuration Top Vent Configuration Fig 1a Fireplace specifications 360DVS2 Ref Rear Vent Configuration Top Vent Configuration A 38 968 mm 38 968 mm B 43 1099 mm 43 1099 mm C 24 610 mm 24 610 mm D 24 610 mm 24 610 mm E 37 949 mm 37 949 mm F 35 911 mm 35 911 mm G 30 775 mm 7 178 mm H 12 305 mm 12 305 mm I ...

Page 6: ...G Fireplace Dimensions 360DVS3 306DVSL 360DVSR Rear Vent Configuration Top Vent Configuration Ref Rear Vent Configuration Top Vent Configuration A 38 968 mm 38 968 mm B 40 1032 mm 40 1032 mm C 24 610 mm 24 610 mm D 24 610 mm 24 610 mm E 37 949 mm 37 949 mm F 35 911 mm 35 911 mm G 30 775 mm 7 178 mm H 12 305 mm 12 305 mm I 3 80 mm 3 80 mm J 2 70 mm 2 70 mm K 1 33 mm 1 33 mm Appliance Dimensions Fig 1b ...

Page 7: ...t Configuration CFM121 CFM122 Framing Dimensions Ref Rear Vent Configuration Top Vent Configuration ROD 24 610 mm minus two times finishing material thickness to be even with face of unit ROH 38 981 mm Not to be framed until unit is set in place due to 3 79 mm allowance for flue collar ROW Not to be framed until unit is set in place 43 1111 mm due to 3 79 mm allowance for flue collar Fig 2a Fireplace fr...

Page 8: ...CFM123 CFM124 Framing Dimensions Ref Rear Vent Configuration Top Vent Configuration Model 360DVS3 360DVSL R 360DVS3 360DVSL R ROD See Note 1 See Note 2 See Note 1 See Note 2 ROH 38 981 mm Not to be framed until unit is set in place due to 3 79 mm allowance for flue collar ROW 40 1032 mm minus one time 1x finishing material thickness to be even with face of unit Fig 2b Fireplace framing dimensions 360D...

Page 9: ...ibles A B C D E V W X Y Z CFM146 DV Mantel Chart 7 5 01 sta Louvre Assembly Top Fireplace Top of Combustion Chamber Bottom of Door Trim Mantel Shelf Mantel from Top Ref or Breast Plate Ref of Comb Chamber V 10 254 mm A 19 483 mm W 8 203 mm B 17 432 mm X 6 152 mm C 15 381 mm Y 4 102 mm D 13 330 mm Z 2 51 mm E 11 297 mm Mantel Chart CFM146 Fig 4a Combustible mantel minimum installation CFM170 DV Bui...

Page 10: ... 24V Hi Lo 38 000 26 600 360DVS2EP Prop 24V Hi Lo 38 000 28 500 360DVS3RN Nat Millivolt 38 000 26 600 360DVS3RP Prop Millivolt 38 000 28 500 360DVS3EN Nat 24V Hi Lo 38 000 26 600 360DVS3EP Prop 24V Hi Lo 38 000 28 500 360DVSLRN Nat Millivolt 38 000 26 600 360DVSLRP Prop Millivolt 38 000 28 500 360DVSRRN Nat Millivolt 38 000 26 600 360DVSRRP Prop Millivolt 38 000 28 500 Gas Specifications Gas Inlet ...

Page 11: ... socket assembly from the EB 1 box 3 Feed the supply line in from the out through the elec trical knockout 4 Connect the ground wire of the supply line to the green screw of the socket assembly 5 Connect the white wire of the power line to the chrome screw of the socket assembly 6 Connect the black wire of the power supply line to the brass screw polarized of the socket assembly FP1428 EB 1 locati...

Page 12: ... purpose NOTE When converting appliance to top vent ensure the insulation material referred to in step 3 is completely removed 4 Remove the 4 screws securing the flue cover plate to the top of the intake box and remove the cover and gasket Fig 11 5 Remove 4 screws securing the flue pipe to back of the intake box and remove pipe and gasket Fig 11 6 Secure the plate and gasket removed in step 4 over t...

Page 13: ... 40VA TRANSFORMER 24 VAC HOT BLACK WHITE WALL SWITCH WHITE OFF 1 2 3 5 6 8 9 MV MV VP PV GRD 24V SENSE SPARK 24V ORANGE RED GREEN BLACK FP1225 Fig 12 Honeywell ignition module Your fireplace is approved to be vented either through the side wall or vertically through the roof Only CFM Corporation venting components specifi cally approved and labeled for this fireplace may be used Venting terminals sha...

Page 14: ... 5m above the meter regulator assy I Clearance to service regulator vent outlet 3 91cm 3 91cm J Clearance to nonmechanical air supply inlet 6 15cm for appliances 10 000 6 15cm for appliances to building or the combustion air inlet to any Btuh 3kW 12 30cm for 10 000 Btuh 3kW 9 other appliances appliances 10 000 Btuh 3kW and 23cm for appliances 10 000 100 000 Btuh 30kW 36 91cm Btuh 3kW and 50 000 Bt...

Page 15: ... Vaseline or similar substance on male end of twist lock pipe prior to assembly Male End Female End Screw Holes TWL100 Fig 15 Twist lock pipe joints Outside Corner Inside Corner Termination Clearances Termination clearances for buildings with combustible and noncombustible exteriors G Combustible 6 152 mm Noncombustible 2 51 mm F Combustible 6 152 mm Noncombustible 2 51 mm G Balcony with no side w...

Page 16: ...dewall vent graph showing the relationship between vertical and horizontal dimensions for a Direct Vent flue system Fig 16 Sidewall vent graph Rear Wall Application When installed as a rear vent unit this appliance may be vented directly to a termination located on the rear wall behind the appliance Specific rear vent starter kits must be used in these applications see venting components The appli a...

Page 17: ...with the termination Vertical Sidewall Application It is very important the venting system maintain its bal ance between the combustion air intake and the flue gas exhaust certain limitations concerning vent con figurations must be strictly adhered to The vent graph Fig 16 showing relationship be tween vertical and horizontal side wall venting will help determine allowable dimensions Minimum clearan...

Page 18: ...45 elbows permitted per side wall installation is two 2 These elbows can be installed in either the vertical or horizontal run For each 45 elbow installed in the horizontal run the length of the horizontal run MUST be reduced by 18 45 cm This does not apply if 45 elbows are installed on the vertical part of the vent system The maximum number of elbow degrees in a system is 270 Example shown in Fig...

Page 19: ... i e from the elbow to the outside wall face plus 2 51 mm or the distance required if installing a second 90 elbow Fig 27 Always install horizontal venting on a level plane X X FP1441 Fig 27 Horizontal length requirement STEP 6 Use appropriate length of pipe section telescopic or fixed and install The 20 508 mm section of pipe which goes through the wall is packaged with the 7DVSK starter kit and c...

Page 20: ...l exceeds 24 610 mm 1 Establish vent hole through the wall Fig 24 2 Remove soil to depth of about 16 406 mm below base of snorkel Install window well not supplied Refill hole with 12 305 mm of coarse gravel leav ing a clearance of about 4 102 mm below snorkel Fig 28 3 Install vent system 4 Ensure a watertight seal is made around the vent pipe coming through the wall 5 Apply high temperature sealant...

Page 21: ...vel the maximum horizontal length must be reduced by 18 457 mm Example Maximum horizontal length Zero elbows 10 3 m 1 x 45 elbows 8 2 6 m 2 x 45 elbows 7 2 1 m A minimum of an 8 ft 2 43 m vertical rise Two 2 sets of 45 elbow offsets may be used within the vertical sections From zero to max 8 ft 2 43 m vent pipe can be used between elbows Fig 30 7DVCS supports offsets Fig 33 This application will r...

Page 22: ...m collar and seal around the pipe 10 Add additional vent lengths for proper height Fig 32 11 Apply high temperature sealant to 4 and 7 collars of vertical vent termination and install CFM110 Typical ceiling roof support 10 90 Typical Roof Sup port Application Typical Ceiling Sup port Application CFM110 Fig 33 Chimney support TWL101a Twist Lock Pipe 2 8 99 djt Sheet Metal Screws 5 3 per joint Seala...

Page 23: ...SK Sidewall Starter Kit Model 7TDVSKV Vertical Venting for 7TDVSKV A order 1 12 to 6 12 roof pitch for 7TDVSKV B order 7 12 to 12 12 roof pitch for 7TDVSKV F order flat roof Starter Kit Model 7TDVSKS Snorkel Kit Snorkel Termination 7TDVSNORK for Below Grade Installation 45 Elbow 7TDVT45 for Rear Vent to Vertical Vent or Vertical Horizontal Offsets 90 Transition Elbow 7TDVRT90 for Rear Vent to Verti...

Page 24: ...ft window frame assembly up and away from the fireplace 7 To reinstall the window frame assembly reverse this procedure Front Window Frame Assembly 1 Remove the top and bottom louvre assembly 2 Remove the lower window trim held in place with magnets 3 Remove both lower retaining screws Access to these screws is gained through the holes along the lower edge of the frame behind the trim Fig 38 4 Tilt...

Page 25: ...ogs by the number cast into the underside For correct operation of the fireplace the logs must be correctly placed in the sequence described below 1 Unpack the logs from the shipping carton The logs are fragile handle them carefully Handle and dispose of plastic bags in which logs were shipped in a safe manner As with all plastics they are not toys and should be kept away from infants 2 Remove both...

Page 26: ...g and separate it into small pieces then scatter it over burner tiles in a random fashion Do not pack down ember material leave it in a fluffy state Lava Rock Pt 10001454 Remove lav rock material from packaging and spread it over ceramic floor panels outside log stack Do not place this lava rock material on burner tiles Flame Temperature Adjustment RN RP Models For units equipped with HI LO valves t...

Page 27: ...tment knob for SIT valve Flame Characteristics It is important to periodically perform a visual check of the pilot and burner flames Compare them to the pictorials illustrated below Figs 45 46 If the flame patterns appear abnormal contact a qualified service provider for service and adjustment 3 8 1 2 10 13mm F584 703 Fig 45 Correct pilot flame appearance LG323 Fig 46 Correct log flame appearance LG322...

Page 28: ...e to smell next to the floor because some gas is heavier than air and will settle on the floor WHAT TO DO IF YOU SMELL GAS Do not try to light any fireplace Do not touch any electric switch Do not use any phone in your building Immediately call your gas supplier from a neighbor s phone Follow the gas supplier s instructions 10 Push the control knob all the way in and hold Immediately light the pilot ...

Page 29: ...r it call a qualified service technician Force or attempting repair may result in a fire or explosion D Do not use this appliance if any part has been under water Immediately call a qualified service technician to inspect the appliance and replace any part of the control system and any gas control that has been under water 1 Turn the remote switch to the OFF position 2 Turn OFF all electrical power t...

Page 30: ...ck not supplied must be used to conduct this test 3 Pilot burning no gas to A Wall switch or wires defective Check wall switch and wires for proper connections main burner Jumper wires across terminals at wall switch if burner comes on repalce defective wall switch If okay jumper wires across wall switch wires at valve if burner comes on wires are faulty or connections are bad B Thermopile may not...

Page 31: ...URES ARE GOOD AND PILOT BURNER ORIFICE IS NOT BLOCKED CHECK ELECTRICAL CONNECTIONS BETWEEN MODULE AND PILOT OPERATOR ON GAS CONTROL CHECK FOR 24VAC ACROSS PV MVPV TERMINALS ON MODULE IF VOLTAGE IS OKAY REPLACE GAS CONTROL IF NOT REPLACE MODULE NOTE IF S8600B GOES INTO LOCKOUT RESET SYSTEM CHECK CONTINUITY OF IGNITION CABLE AND GROUND WIRE CLEAN FLAME ROD CHECK ELECTRICAL CONNECTIONS BETWEEN FLAME ...

Page 32: ...ace Piezo Ignitor Supply Line Hooked Up Shutoff Valve Open PILOT STAYS LIT For Air In The Lines Thermopile Needs A Min 325mv Adjust Pilot Flame Height All Wiring Connections Replace Thermopile Thermocouple Needs A Min Of 14mv PILOT LIGHTS MAIN BURNER Valve Is Turned On Wall Switch Is Not Turned On Watch For Grounded Wires Thermopile Needs A Min 325mv Plugged Burner Orifice Defective Valve Turn To P...

Page 33: ...447 360DVS air shutter Air Shutter Retain ing Screws Air Shutters FP1447 Fig 47 Air shutter adjustment 8 SIT Top Convertible Pilot Gently lift off pilot hood from the pilot NOTE Do not remove the spring clip holding the hood in place Us ing a correctly sized Allen key unscrew the exposed orifice Insert the new orifice supplied in the kit do not overtighten the orifice Replace the pilot hood ensuring ...

Page 34: ...as used The only variations are in orifice sizes and component part num bers Your authorized service provider will ensure correct parts are used L O H I HV120 Honeywell valve conversion 9 24 02 djt Regulator Cap Conversion Screw Pressure Regu lator Housing HV120 Fig 50 Honeywell conversion screw replacement Honeywell Gas Control Valve Fig 50 The Honeywell valve fitted to this unit is suitable for us...

Page 35: ...y it should be performed by a qualified technician 1 Turn off pilot light at gas valve side 2 Let fireplace cool if it has been running 3 Remove window frame assembly Refer to Window Frame Assembly Removal section 4 Remove logs 5 Vacuum burner compartment especially around orifice primary air openings 6 Visually inspect pilot Brush or blow away any dust or lint accumulation 7 Reinstall logs 8 Ignite ...

Page 36: ... 14 3a b 15a b 16a b 6326 360DVS parts 31a b 32 35 33 HI LO 34a b 25 36 37 30 1 1a 1b 1c 1d 1e 1f 1g CFM Corporation reserves the right to make changes in design materials specifications prices and discontinue colors and products at any time without notice 360DVS Series Units H63H00 H63I00 H63A00 GFSM2L0 H63B00 H93H00 H93A00 H93B00 H83A00 H83B00 H73A00 H73B00 ...

Page 37: ...10002266 8 Pilot Hood SIT Top Convertible 10002385 10002385 10002385 10002385 Orifice Pilot PSE Nat 10001822 10001822 10001822 10001822 Orifice Pilot PSE Prop 10001823 10001823 10001823 10001823 Orifice Pilot SIT Top convertible Nat 10002268 10002268 10002268 10002268 Orifice Pilot SIT Top conv Prop 10002269 10002269 10002269 10002269 Pilot tube fittings Top convertible 10001296 10001296 10001296 10001...

Page 38: ...6257 Air Inlet Cover Plate Assembly 10006174 10006174 10006174 10006174 Air Inlet Cover Plate Gasket 10006171 10006171 10006174 10006171 Flue Pipe Plate Assembly 10002554 10002554 10002554 10002554 FluePipe Plate Gasket 10002237 10002237 10002237 1000223 Flue Cover Plate 10002298 10002298 10002298 10002298 Flue Cover Plate Gasket 10002233 10002233 10002233 10002233 Relief Plate with gasket 1000242...

Page 39: ...he power supply may be connected in two ways Method A Route the 6 lead fitted to the unit to a conveniently located wall socket Method B The EB I receptacle box Pt ZA1200 may be hard wired into the house supply The fan lead is then plugged into the EB I box FK12 This auxiliary fan system increases the efficiency of the circulation of the heating air The FK12 Fan Assembly is a fixed speed fan system a...

Page 40: ... Wall mounted thermostat control Decorative Trim Frame Kit The DV360TKMP Medium Trim Kit in polished brass is available for the 360DVS2 model only Each kit contains 4 polished brass trim pieces and the necessary attaching screws to frame one side window of the unit Installation Refer to Fig 53 1 Remove the top louvre assembly 2 Lower the bottom louvre assembly to expose the lou vre hinges Unscrew ...

Page 41: ...41 360DVS Series Direct Vent Fireplaces 10006326 ...

Page 42: ...42 360 DVS Series Direct Vent Fireplaces 10006326 ...

Page 43: ...hop Ifuponinspection thedamageisfoundtobethefaultofthemanufacturer repairs will be authorized at no charge to the customer parts and or labor Any part and or component replaced under the provisions of this warranty is covered for six months or the remainder of the original warranty whichever is longest This warranty is limited to the repair of or replacement of part s found to be defective in mate...

Page 44: ...4 65 360DVS3RN 62 4 83 84 65 360DVS3RP 62 4 83 84 65 360DVS3EN 62 4 83 84 65 360DVS3EP 62 4 83 84 65 360DVSLRN 62 4 83 84 65 306DVSLRP 62 4 83 84 65 360DVSLEN 62 4 83 84 65 360DVSLEP 62 4 83 84 65 360DVSRRN 62 4 83 84 65 360DVSRRP 62 4 83 84 65 360DVSREN 62 4 83 84 65 360DVSREP 62 4 83 84 65 2695 Meadowvale Blvd Mississauga Ontario Canada L5N 8A3 800 668 5323 www cfmcorp com CFM Corporation ...

Reviews: