background image

15

BFC36 Balanced Flue Heat-Circulating Fireplace

7412647

Side Wall Protection

Adjacent combustible side walls that are within mini-
mum dimensions shown in Figure 24 of the fireplace 
opening  must be protected with MHSC Wall Shield 
Model SP40 or a specifically built wall shield described 
in Figure 18.
The special wall shield design described in Figure 18 is 
an alternate method of adding protection to side walls 
and can be used in place of the SP40 with the same 
wall clearances specified for the SP40. Rt must =1.85 
minimum.

Examples of wall shield insulation:

1.  Manville - CERAFORM 126, K=.27, 
  1/2 inches thick
2.  EH2416, K = .458, 
  1 inch thick required.

Hearth Installation

A hearth extension is required to protect a combustible 
floor in front of the fireplace. Refer to Figure 21 for mini-
mum dimensions and mounting detail.

Note:  Hearth Extension must not cover the air inlet 
opening of a fireplace.

The hearth extension described in Figure 21 must be 
a durable non-combustible material with a minimum 
(total) Rt value of 1.09; refer to Figure 22 for examples. 
The overall height (above a combustible floor), depth 
and width must be as indicated, with the extension cen-
tered to the fireplace opening.
The top of insulation must be covered with a non-com-
bustible decorative covering 

or

 a piece of .018” mini-

mum sheet metal, to protect hearth extension material.  
(Fig. 21)
Secure the hearth extension to the floor to prevent 
shifting, using trim molding or other similar means at 
three (3) outer edges.  Seal crack between the fireplace 
hearth and hearth extension with a non-combustible 
material.  (Figs. 21 and 23)

Minimum Wall Clearances

WITH

Noncombustible

Surround Facing

WITHOUT

Noncombustible

Surround Facing

Minimum Hearth Extension Dimensions

(for On-Site Construction)

G

H

G

J

Seal cracks

between the 

fireplace

and hearth

extension with

noncombustible

material

Safety strips 

must overlap 

���

" minimum

May install 

noncombustible 

decorative 

covering

OR

 .018" min. 

sheet metal

Fireplace

Hearth

Combustible

Floor

Minimum

Insulation

Value "R"

4" MIN.

FP594b
BFC combustible min.
8/21/00   djt

Firebox

Opening

A -

 Min. clearance 

to combustible

perpendicular wall

B -

 Min. clearance 

to combustible

perpendicular wall when

using noncombustible wall shield*

Side

Wall

Side 

Wall

F

**

C

**

E

E

D

4" Brick

(Example material)

Combustible material permitted within shaded area.  

 * Noncombustible wall shield requires 1" EH2416 

    insulation (minimum R Value = 1.85) between decorative 

    noncombustible rigid covering and combustible wall.  

    Minimum height and width is 40" x 40".
** Dimension/degree of angle will vary depending on thickness 

    of noncombustible surround facing.

Shaded area 

starts 1/2" from 

away from edge 

of unit 4"

FP594b

Fig. 21 

 Combustible side wall protection and hearth extension dimensions.

   

J

  BFC36 

26” 

12” 

17° 

25° 

12” 

8” 

8” 

18” 

47

¹⁄₄

   

660 mm  305 mm 

 

 

305 mm  203 mm  203 mm 457 mm 1200 mm

Summary of Contents for BFC36

Page 1: ...Closed Combustion Heat Circulating Fireplace Model BFC36 For use in the U S Canada Underwriter s Laboratories Report No MH6018 DO NOT DISCARD THIS MANUAL Retain for future use 7412647 8 08 Rev 15 Hom...

Page 2: ...n combination or assembly with a MHSC re place system notwithstanding any indepen dent testing laboratory or other third party approval of such component parts or acces sory Any such action may possib...

Page 3: ...ge 647 BFC36 specs 8 18 00 djt 13 Dia 343mm Rough Opening Width 43 Rough Opening Height Rough Opening Depth Gas Line Access 51 1297mm 51 1297mm 1 8 3 4 m m 197mm 23 584mm 610mm 624mm 39 997mm 246mm 35...

Page 4: ...ftstop Standoff Surround Trim Ledge Standoff Glass Door Romex Pigtail Gas Line Access Knock out Each Side Air Inlet Basket Grate Bottom Grille Metal Safety Strip s Shown not inplace 1 2 or 3 pieces Na...

Page 5: ...et of angled run of chimney Chimney supports are required for every 30 feet and 60 feet of vertical chimney height above the hearth Determine the offset distance of your chimney arrangement from the c...

Page 6: ...r 2 total 45 elbows in Canada per replace may be used 6 A guy wire stabilizer is required for chimneys extend ing more than 6 1 8m above a roof line The Ten Foot Rule Major U S building codes specify...

Page 7: ...ow the chimney system should be run contact your Ver mont Castings Majestic Products dealer for assistance Installation Insulating Fireplace Enclosure for Cold Climates If you live in a cold climate i...

Page 8: ...ire nuts must be tight NOTE Check local building codes to determine if junction box is required at the romex pigtail house wire connection Also check junction box and speed control SCVS installation i...

Page 9: ...ut Check to see where existing ceiling joists and other possible obstructions are located i e wiring plumbing etc If necessary re position chimney and or replace to avoid obstructions Cutting the Hole...

Page 10: ...in front of the replace This Z shaped safety strip is not provided but must be fabricated of metal with each horizontal leg at least 1 38mm wide and equal in length to the metals strips provided with...

Page 11: ...ness up to 8 203mm When combined thickness of ceiling material ceiling joists and ooring material exceeds 8 203mm adjustments must be made in framing to assure that minimum air spaces to chimney are m...

Page 12: ...ombustible surfaces Combustible surfaces include burnable materials such as ceiling members joists ooring combustible insulation and roof structures WARNING Do not pack required air spaces with insula...

Page 13: ...e not a substitute for local building codes You must check your local building codes to determine speci c requirements for your city or state NOTE Other building materials may be required in addition...

Page 14: ...mantel clearances 12 from top of grille opening 6 from top of grille opening Face Plate FP531b mantel clearances 9 03 djt 12 305mm Max 12 305mm Min 1 38mm 6 159mm Min Fig 19 Mantel clearance Combustib...

Page 15: ...ct hearth extension material Fig 21 Secure the hearth extension to the oor to prevent shifting using trim molding or other similar means at three 3 outer edges Seal crack between the replace hearth an...

Page 16: ...nits of K BTU SQ FT HR F IN Thickness of Listed Material FP533ADD Addendum 6 1 99 djt 8 4 99 changed 2 to 1 one inch to 1 2 inch djt FP533ADD Fig 22 Hearth extension material factors Example of Determ...

Page 17: ...pipe should not come in contact with any wood structures until it has reached a point at least 1 25 mm away from replace side BTU input of a gas appliance installed in replace should be rated less th...

Page 18: ...cription BFC36 1 Top Grille Painted 3126160 2 Bottom Grille Painted 3126160 3 Grate Assembly 7579218 4 Left Door Assembly Complete 30004361 5 Right Door Assembly Complete 30004362 6 Rear Firebrick 235...

Page 19: ...c Glass Panel two per replace 30004352 21 Flat Gasket 3 4 Wide two per replace 20013997 22 Knob two per replace 1600657 23 Bushing four per replace 1201895 24 Pan Hd PH 1 4 20 x 1 Black two per replac...

Page 20: ...uch must be operat ed only with MHSC approved components If you use an unapproved component to make any modi cations you may create a possible re hazard and will void the MHSC warranty In addition suc...

Page 21: ...ing is not included TT200C Adapter Kit TT8CB is required Chase Top Housing Used with chase terminations to prevent rain entry FL88 8 ue Contemporary Flashing 8 6 12 with 8 ue Required for Contemporary...

Page 22: ...22 BFC36 Balanced Flue Heat Circulating Fireplace 7412647...

Page 23: ...ressure dif ferentials produced by wind Broken glass components Cracks in ceramic and castable parts that do not affect safe operation We do not warrant this replace to be in compliance with your loca...

Page 24: ...MHSC 149 Cleveland Drive Paris Kentucky 40361 www mhsc com...

Reviews: