background image

12

BFC36 Balanced Flue Heat-Circulating Fireplace

7412647

Firestop spacers are not available for, nor are they 
required on vertical walls.

DO NOT 

put any sealant around the area where the 

outer pipe slides through the firestop spacer.  If you 
seal this area,

 it may cause a fire hazard.

Canadian Requirements 

for Insulation Shield

In Canada, an attic insulation shield is required to 
prevent attic insulation from contacting the chimney 
section. 

NOTE:

 If the attic insulation shield is used, the 

firestop is not required in the attic installation. Fram-
ing dimensions for the chimney hole should measure 
17

¹⁄₂

” x 17

¹⁄₂

” (445 x 445mm). An attic shield MUST be 

installed on top of attic joists (above the floor level). 
(Fig. 17)

A chimney support is 2

¹⁄₂

" (64mm) long when installed. 

Consider this dimension when determining how many 
straight chimney sections are needed.

NOTE:

  Chimney supports are generally used in long 

runs in a chase installation.

Additional Ceilings

If you encounter additional ceilings, repeat same steps 
required for first ceiling installation.  See firestop illus-
tration in Page 11, Figure 16. 

Penetrating the Roof

Run pipe to roofline.  Since chimney system must be 
vented to the out-of-doors, you 

must

 use an approved 

MHSC termination.
If a chase is used, refer to the installation manual pro-
vided with the termination cap.

Locate Chimney Centerpoint On Roof

Use same procedure detailed in locating center point of 
the flue system.
Drive a nail up through roof at the center point.  This will 
determine center point on outside of the roof.

Cut and Frame Roof Hole

Size of roof hole varies with the type of chimney 
termination installed. Refer to installation instructions 
provided with MHSC chimney termination to find correct 
size of roof hole.
There must be a 1

¹⁄₂

” (38mm) air space between out-

ermost portion of chimney sections and any adjacent 
combustible surfaces. (Combustible surfaces include 
burnable materials such as:  ceiling members, joists, 
flooring, combustible insulation and roof structures.)

WARNING:  Do not pack required air spaces with 
insulation or other materials.

Mark an outline of the roof hole around the center of the 
point nail.  

NOTE:

 Hole dimensions given in the chim-

ney top installation instructions are 

horizontal 

dimen-

sions; therefore, the hole size must be marked on the 
roof accordingly.
Cover the opening of the installed chimney so debris 
cannot get into the system.
Cut and frame the hole.  It is good practice to use fram-
ing lumber that is the same size as the rafters.  Install 
the frame securely because the chimney top and flash-
ing anchored to the frame must be able to withstand 
heavy winds.

Install Remainder of Chimney Sections

Since you have already preplanned the height of your 
termination according to the 

Ten Foot Rule

, continue to 

install pipe to the predetermined height.

NOTE:

 In the U.S., it is a good idea, although not al-

ways required, to install an attic insulation shield where 
blown-in insulation is planned to be used in the attic.
Install the attic insulation shield with the flanges on its 
base extending down into the framing hole. Nail each 
corner of attic insulation shield to the framing members 
of the ceiling hole using 8d nails.  Attic shields are not 
required at the roof.

Continue Installing Pipe to Complete Run

Continue attaching pipe sections to complete system 
to next level always being careful that the pipe is firmly 
snap-locked in place before proceeding to next pipe 
section.

Chimney Supports

If chimney supports are required, they are installed the 
same as elbows.  Nail chimney support straps to ad-
jacent structural framing, as shown on Page 8, Figure 
9. Bend straps as necessary and make sure they are 
secure so they will support the weight of the chimney. 

IGF263

MBUF

5/9/96

Attic Insula-

tion Shield

Nails 

(4 required)

Attic Joist

Ceiling

Base Flanges

FP263

Fig. 17

  Attic shield installation (Canadian requirement).

Summary of Contents for BFC36

Page 1: ...Closed Combustion Heat Circulating Fireplace Model BFC36 For use in the U S Canada Underwriter s Laboratories Report No MH6018 DO NOT DISCARD THIS MANUAL Retain for future use 7412647 8 08 Rev 15 Hom...

Page 2: ...n combination or assembly with a MHSC re place system notwithstanding any indepen dent testing laboratory or other third party approval of such component parts or acces sory Any such action may possib...

Page 3: ...ge 647 BFC36 specs 8 18 00 djt 13 Dia 343mm Rough Opening Width 43 Rough Opening Height Rough Opening Depth Gas Line Access 51 1297mm 51 1297mm 1 8 3 4 m m 197mm 23 584mm 610mm 624mm 39 997mm 246mm 35...

Page 4: ...ftstop Standoff Surround Trim Ledge Standoff Glass Door Romex Pigtail Gas Line Access Knock out Each Side Air Inlet Basket Grate Bottom Grille Metal Safety Strip s Shown not inplace 1 2 or 3 pieces Na...

Page 5: ...et of angled run of chimney Chimney supports are required for every 30 feet and 60 feet of vertical chimney height above the hearth Determine the offset distance of your chimney arrangement from the c...

Page 6: ...r 2 total 45 elbows in Canada per replace may be used 6 A guy wire stabilizer is required for chimneys extend ing more than 6 1 8m above a roof line The Ten Foot Rule Major U S building codes specify...

Page 7: ...ow the chimney system should be run contact your Ver mont Castings Majestic Products dealer for assistance Installation Insulating Fireplace Enclosure for Cold Climates If you live in a cold climate i...

Page 8: ...ire nuts must be tight NOTE Check local building codes to determine if junction box is required at the romex pigtail house wire connection Also check junction box and speed control SCVS installation i...

Page 9: ...ut Check to see where existing ceiling joists and other possible obstructions are located i e wiring plumbing etc If necessary re position chimney and or replace to avoid obstructions Cutting the Hole...

Page 10: ...in front of the replace This Z shaped safety strip is not provided but must be fabricated of metal with each horizontal leg at least 1 38mm wide and equal in length to the metals strips provided with...

Page 11: ...ness up to 8 203mm When combined thickness of ceiling material ceiling joists and ooring material exceeds 8 203mm adjustments must be made in framing to assure that minimum air spaces to chimney are m...

Page 12: ...ombustible surfaces Combustible surfaces include burnable materials such as ceiling members joists ooring combustible insulation and roof structures WARNING Do not pack required air spaces with insula...

Page 13: ...e not a substitute for local building codes You must check your local building codes to determine speci c requirements for your city or state NOTE Other building materials may be required in addition...

Page 14: ...mantel clearances 12 from top of grille opening 6 from top of grille opening Face Plate FP531b mantel clearances 9 03 djt 12 305mm Max 12 305mm Min 1 38mm 6 159mm Min Fig 19 Mantel clearance Combustib...

Page 15: ...ct hearth extension material Fig 21 Secure the hearth extension to the oor to prevent shifting using trim molding or other similar means at three 3 outer edges Seal crack between the replace hearth an...

Page 16: ...nits of K BTU SQ FT HR F IN Thickness of Listed Material FP533ADD Addendum 6 1 99 djt 8 4 99 changed 2 to 1 one inch to 1 2 inch djt FP533ADD Fig 22 Hearth extension material factors Example of Determ...

Page 17: ...pipe should not come in contact with any wood structures until it has reached a point at least 1 25 mm away from replace side BTU input of a gas appliance installed in replace should be rated less th...

Page 18: ...cription BFC36 1 Top Grille Painted 3126160 2 Bottom Grille Painted 3126160 3 Grate Assembly 7579218 4 Left Door Assembly Complete 30004361 5 Right Door Assembly Complete 30004362 6 Rear Firebrick 235...

Page 19: ...c Glass Panel two per replace 30004352 21 Flat Gasket 3 4 Wide two per replace 20013997 22 Knob two per replace 1600657 23 Bushing four per replace 1201895 24 Pan Hd PH 1 4 20 x 1 Black two per replac...

Page 20: ...uch must be operat ed only with MHSC approved components If you use an unapproved component to make any modi cations you may create a possible re hazard and will void the MHSC warranty In addition suc...

Page 21: ...ing is not included TT200C Adapter Kit TT8CB is required Chase Top Housing Used with chase terminations to prevent rain entry FL88 8 ue Contemporary Flashing 8 6 12 with 8 ue Required for Contemporary...

Page 22: ...22 BFC36 Balanced Flue Heat Circulating Fireplace 7412647...

Page 23: ...ressure dif ferentials produced by wind Broken glass components Cracks in ceramic and castable parts that do not affect safe operation We do not warrant this replace to be in compliance with your loca...

Page 24: ...MHSC 149 Cleveland Drive Paris Kentucky 40361 www mhsc com...

Reviews: