Electrical equipment should be checked
regularly. Loose connections should be
re-secured, damaged lines or cables should
be replaced immediately.
●
Risk of electric shock if fan is not completely
installed/damaged.
Only operate the fan
when it is completely installed. Do not put
a damaged unit into operation and do not
allow it to be operated until repaired.
●
A device for mains separation with at least
3 mm contact opening per pole and a fixed
electrical installation (connection according
to wiring diagram) and sufficiently dimen
-
sioned cables is required. Operation is only
permissible using the voltage and frequency
shown on the rating plate.
●
Unit may also be energized even when at a
standstill and may be switched on automat
-
ically by sensors or by the thermal switch in
the motor winding.
●
Ensure EMC-compliant installation of the
control cables, avoid interference (ensure suf
-
ficient distance to mains and motor cables).
With shielded cables, connect the shield at
one end of the signal input of the evaluation