VENTILATOREN
FR
MDR .. EC
FIG
UK
DE
Fan does not switch on/does not run.
Cause 1:
No mains voltage, earth fault.
Measure:
Check whether the power supply is
guaranteed (mains fuse, service switch, motor
connection).
Cause 2:
Wiring not carried out correctly.
Measure:
Check wiring
connection wiring
diagram.
Cause 3:
Thermal motor protection has trig
-
gered (motor is overheated).
Measure:
Ensure that the air ways are free, re
-
move foreign objects if necessary. Check room
temperature. Check voltage. If necessary, install
air filter in duct system.
Cause 4:
The impeller is blocked or dirty.
Measure:
Remove foreign objects or dirt.
Fan runs too slowly / volumetric flow too low
Cause 1:
Impeller is rubbing
Measure:
Remove foreign objects or dirt.
Cause 2:
Deposits on the impeller and in the
housing caused by dust in the air.
Measure:
Install air filter in duct system. Ensure