   Safety Regulations 

ROU250 

1.

 

Safety Regulations 

1.1

 

Warnings 

 

To  avoid  serious  injury  or  death

,  read  this  manual 

carefully  before  operating  this  unit.  Contact  the 
manufacturer  using  contact  information  on  the  back 
cover of this manual if you have any questions. 

 

Always  think  before  acting

,  familiarity  breeds 

carelessness,  and  carelessness  can  result  in  serious 
injury or death. 

 

Only  a  qualified  technician  should  operate  the 
recovery machine.

 

 

Read  all  safety  information  regarding  the  safe 
handling  of  refrigerant  and  refrigerant  oil

.  Including 

the  Material  Safety  Data  Sheet.  MSDS  sheets  can  be 
obtained from your refrigerant supplier. 

 

Always  wear  safety  goggles  and  protective  gloves 
when  working  with  refrigerants

.  Refrigerants  can 

damage skin and eyes.  Avoid touching caustic liquids 
or gas. 

 

Make sure the work area is properly ventilated

.  

 

Use ONLY authorized refillable refrigerant tanks

. The 

recovery unit requires the use of recovery tanks with a 
minimum of 27.3 bar (396psi) working pressure. 

 

Do not overfill the storage tank

. The tank is full at 80% 

of  volume.  There  should  be  enough  space  for  liquid 
expansion---overfilling  of  the  tank  may  cause  a  violent 
explosion.    A  scale  or  a  80%  O.F.P.  switch  must  be 
used to avoid overfilling the storage tank. 

 

Do not exceed the working pressure of the recovery 
tank cylinder. 

 

 

Before  recovering  refrigerant  the  tank  should  reach 
a  vacuum  level  of  1000mbar  (29.53InHg)

.  This  is for 

purging  non-condensable  gases.  Each  tank  was  full  of 
nitrogen  when  produced,  thus  the  nitrogen  should  be 
evacuated before recovery. 

 

When not in use ensure all valves are closed.

 This will 

maximize  the  lifecycle  of  the  machine,  as  excess 
moisture from atmosphere will shorten operating life. 

 

When using an extension cord, it should  be 14AWG 
minimum  and  no  longer  than  7.62  meters  (25  feet)

Failure to do so may cause excessive voltage drop and 
could damage the compressor. 

 

A  dry  filter  must  always  be  used  and  should  be 
replaced frequently

. We recommend replacing the dry 

filter  (P/N  026  80774  00)  every  3  months  when  the 
machine  is  in  regular  use.    If  the  machine  is  used  to 
recovery pure known refrigerant use a different filter for 
each type of refrigerant.  

 

Special care should be taken when recovering from 
a “burned-out” system.

 Use two filters in series when 

recovering from these systems.  Flush out the recovery 
machine with a  small  amount of  clean refrigerant  once 
recovery  is  complete  to  purge  off  any  foreign 
substances left in the machine. 

 

The  system  has  a  high  &  low  pressure  shut  down 
switch. 

If  the  pressure  inside  the  system  goes  above 

38bar,  the  system  will  automatically  shut  off.    The 
shutoff will need to be manually reset.  The low pressure 
shutdown occurs at approximately 10 In/Hg (339mbar).  
The  machine  will  automatically  start  again  when  the 
pressure rises to approximately 5 psi (35bar). 

 

If  the  tank  pressure  exceeds  300psi  (20.7bar),  use 
the  TANK  COOLING  PROCEDURE  to  reduce  the 
tank pressure

.  

 

When  recovering  large  amounts  of  liquid,  use  the 
LIQUID PUSH/PULL PROCEDURE.

  

 

After recovering, make sure there is no refrigerant 
left  in  the  machine.    Read  the  SELF-PURGING 
PROCEDURE  carefully.

  Liquid  refrigerant  left  in  the 

machine may expand and destroy components. 

 

If the recovery machine is to be stored or not used 
for  any  substantial  length  of  time  we  recommend 
purging with nitrogen.

  

 

Care should be taken when moving the machine. 

 

 

 

 

Summary of Contents for ROU250

Page 1: ...MAHLE ROU250 EN Operation Manual Recovery Only Unit...

Page 2: ...Y PERSON WHO OPERATES THIS EQUIPMENT NEEDS TO KNOW AND UNDERSTAND ALL OF THE INFORMATION IN THIS MANUAL FAILURE TO DO SO COULD RESULT IN SERIOUS INJURY OR DEATH READ THIS MANUAL CAREFULLY AND RETAIN F...

Page 3: ...edure 7 6 2 Purging Procedure 8 6 3 Liquid push pull procedure 8 6 4 Tank Cooling Procedure 9 7 Troubleshooting 10 8 ROU250 System Kits 11 8 1 ROU250 Kit With R134a Manifold Tank 11 8 2 ROU250 Kit wit...

Page 4: ...all valves are closed This will maximize the lifecycle of the machine as excess moisture from atmosphere will shorten operating life When using an extension cord it should be 14AWG minimum and no long...

Page 5: ...the recovery unit itself is approved for multiple refrigerants For a complete list of applicable refrigerants please see the specification section of this manual 3 Symbols Use 3 1 Warning notices Warn...

Page 6: ...quipment and its proper use when servicing motor vehicles and their components Safety information provided with this equipment should be emphasized by the employer and understood by each employee The...

Page 7: ...f the recovery machine If the recovery machine If the recovery machine fails to start rotate the fails to start rotate the fails to start rotate the fails to start rotate the INPUT valve and the MODE...

Page 8: ...filling the storage tank once the be used to avoid over filling the storage tank once the be used to avoid over filling the storage tank once the siphon siphon siphon siphon is started it can continu...

Page 9: ...e hoses as shown 2 Turn the MODE valve to the Recover position 3 Open the Vapor and Liquid valve of the storage tank 4 Power on and start the compressor 5 Open the INPUT valve and OUTPUT valve of the...

Page 10: ...ressor does not start Machine is in high pressure shutdown Reduce pressure and press High Pressure Switch Output pressure is too high Rotate INPUT valve and MODE valve to PURGE then rotate INPUT valve...

Page 11: ...ROU250 en 11 System Kits 8 ROU250 System Kits 8 1 ROU250 Kit With R134a Manifold Tank P N 460 80423 00 8 2 ROU250 Kit with R1234yf Manifold Tank P N 460 80424 00...

Page 12: ...Notes ROU250 ROU250 en 12 System Kits 8 3 R134a Manifold Gauge Set Kit P N 360 83173 00 8 4 R1234yf Manifold Gauge Set Kit P N 360 83174 00...

Page 13: ...ROU250 en 13 System Kits 8 5 ROU250 Complete Kit R1234yf R134a With Tank P N 460 80425 00...

Page 14: ...Notes ROU250 ROU250 en 14 System Kits 8 6 Rou250 Unit Only P N 460 80422 00 8 7 Dot Cylinder With Float Switch P N 360 80310 00...

Page 15: ...ROU250 en 15 Schematics 9 Schematics 9 1 Electrical Schematic...

Page 16: ...Notes ROU250 ROU250 en 16 Schematics 9 2 Flow Schematic...

Page 17: ...17 Tube 2 Control Arm 10 Dryer Filter 18 Base 3 Front Panel 11 Hose 19 Rubber Foot 4 Input Gauge 12 Tube 20 Condenser 5 Output 13 Tube 21 Fan 6 Knob 14 Compressor 22 Back Panel 7 Circuit Breaker 15 M...

Page 18: ...Notes ROU250 en 18 Notes ROU250 en 18 Notes...

Page 19: ...ROU250 en 19 Parts Diagram...

Page 20: ...Notes ROU250 035 82540 MAHLE Aftermarket Inc 10 Innovation Drive York PA 17402 U S A Phone 800 468 2321 Fax 717 755 8304 E mail tech mss us mahle com www servicesolutions mahle com...

Reviews: