Fig. 4: Rear view (detail)
1
Power cord connector and Power switch
2
HP&LP vehicle connector/couplers and hoses
ATTENTION: Leave the quick coupling taps closed
when the unit is not in use and at the end of vehicle
service operations.
7.2
Software update
It is possible to check for software updates via Wi-Fi and
download them inside the
•
Main Menu
o
Setup
Updates Check
7.3
Initial verification
Execute the following actions in sequence by following the
display guided procedure and the illustrations on the
of the equipment:
•
Gas weight verification
•
Oil weight verification
•
First vessel filling
It is possible to interrupt the initial verification, the station
will propose at next powering to continue.
The equipment cannot operate until all the steps of
initial verification have been completed.
CAREFULLY ABIDE BY THE
FOLLOWING INSTRUCTIONS TO
AVOID DANGER TO PERSONS, THE
DISCHARGE OF REFRIGERANT IN
THE ATMOSPHERE
2
1
| ACX380/4850
Leave the quick coupling taps closed
when the unit is not in use and at the end of vehicle
Fi and
Execute the following actions in sequence by following the
e illustrations on the screen
It is possible to interrupt the initial verification, the station
The equipment cannot operate until all the steps of the
Let us consider as first filling the one carried out during the initial
check with internal tank of the equipment free of refrigerant and
containing air.
Set the quantity of refrigerant to fill (at least 3 kg) and follow the
guided procedure shown on the display.
Check that the equipment hoses are not connected and positioned
in the hose winder. Start the procedure that initially implies the
creation of vacuum in the internal tank. This phase will take 15
minutes and will act on the whole equipment.
Only when the message appears asking to connect the charge tank,
connect the LP quick coupler (colour blue
refrigerant tank using the supplied adaptor.
When the message occurs open the coupler by turning the knob
clockwise. Open the valve on the external tank.
Just right before reaching the planned quantity of refrigerant, the
unit will stop and ask the user to close the external refrigerant tank.
Then, the device will continue the recovery from the hoses and ends
when these are empty. Hence, it is necessary to
coupler and disconnect it from the external tank.
Thanks to the E³ CONNECT function, the refrigerant
between the cylinder fitting and the hose quick
of the process - will not be released in the enviro
There may be two types of source tanks: with plunger and without
plunger.
Tanks with plunger shall remain upright to be able to transfer liquid
refrigerant; for this type of tanks connect to the L (liquid) coupler.
Tanks without plunger have only one valve, so they must be turned
upside down to transfer the liquid refrigerant.
The LP gauge indicates the pressure inside the external tank.
After some minutes the unit will automatically end the function.
At the end the weight of the charged refrigerant will be displayed.
7.4
New PAG and POE oil bottles filling
To fill the new oil bottles (Fig.1 Pos. 9) they have to be extracted
from their housing by means of the quick coupler on the top of the
bottle; slightly press downward the coupler ring n
Fill the bottle by paying special attention to the “Active Oil
Protection” system.
•
During the oil suction phase, before entering the bottle air is
made dry as it passes through a path of special “desiccant”
material.
•
The air inside the bottle is therefore completely “dry”
ACX380/4850 | 12 en
Let us consider as first filling the one carried out during the initial
check with internal tank of the equipment free of refrigerant and
Set the quantity of refrigerant to fill (at least 3 kg) and follow the
Check that the equipment hoses are not connected and positioned
in the hose winder. Start the procedure that initially implies the
creation of vacuum in the internal tank. This phase will take 15
minutes and will act on the whole equipment.
Only when the message appears asking to connect the charge tank,
blue) of the unit to an external
refrigerant tank using the supplied adaptor.
When the message occurs open the coupler by turning the knob
clockwise. Open the valve on the external tank.
Just right before reaching the planned quantity of refrigerant, the
unit will stop and ask the user to close the external refrigerant tank.
Then, the device will continue the recovery from the hoses and ends
when these are empty. Hence, it is necessary to open the LP quick-
from the external tank.
Thanks to the E³ CONNECT function, the refrigerant - usually kept
between the cylinder fitting and the hose quick-coupler until the end
will not be released in the environment.
There may be two types of source tanks: with plunger and without
shall remain upright to be able to transfer liquid
refrigerant; for this type of tanks connect to the L (liquid) coupler.
e valve, so they must be turned
upside down to transfer the liquid refrigerant.
gauge indicates the pressure inside the external tank.
After some minutes the unit will automatically end the function.
refrigerant will be displayed.
New PAG and POE oil bottles filling
To fill the new oil bottles (Fig.1 Pos. 9) they have to be extracted
from their housing by means of the quick coupler on the top of the
bottle; slightly press downward the coupler ring nut to extract it.
Fill the bottle by paying special attention to the “Active Oil
During the oil suction phase, before entering the bottle air is
sses through a path of special “desiccant”
air inside the bottle is therefore completely “dry”
Summary of Contents for ACX380
Page 1: ...MAHLE ACX380 480 EN Service Manual A C Service Equipment...
Page 31: ...en 31 ACX380 480 APPENDIX 1 REFRIGERANT FLUID CIRCUIT ACX380 480 H...
Page 33: ...en 33 ACX380 480 Recovery cycle H...
Page 34: ...ACX380 480 34 en Vacuum H...
Page 35: ...en 35 ACX380 480 Recharge H...
Page 45: ...MAHLE Aftermarket Italy S p A Via Quasimodo 4 a 43126 Par ma ITALY 2019 10 28...