23
To adjust the output voltage, check the output voltage on the generator display screen. Look at the “L1N” voltage or
the “L12” voltage on the display. The generator nominal output voltage should be within 10% of the voltage rating
on the voltage selector switch.
To adjust the output voltage, use a flat head screwdriver to turn the screw in the desired direction until the required
voltage shown on the LCD window matches the stated voltage on the voltage selector switch.
For Example:
With the voltage selector switch set to “208/120V” 3 phase position, the voltage shown on the generator
display screen must be within ± 10% of the 208/120V position (188-228V line to line / 108-132V line to neutral).
Note:
Each time the voltage selector switch is changed from one setting to another, an adjustment will need to be
made to the fine voltage using this adjustment screw.
FRONT HOOD OPERATION
WARNING
Stay clear of hood and lift structure when opening and closing generator hoods.
Personal injury may result.
TO OPEN THE FRONT HOOD:
1. With your right hand, grip the handle located on the upper right side of the front panel.
2. With your left hand, pull the hood latch located on the upper corner of the left hood side. Refer to Figure A. Tilt
the hood open until it contacts the bulkhead panel.
CAUTION
Generator hoods are heavy. Use caution when opening or closing.
Figure A