© 2016 Sensata Technologies
7
Step 5: Connecting the MicroGTs using AC Connectors
The MicroGT 500 inverter’s datasheet states the maximum allowable
number of microinverters on one AC branch circuit is seven.
WARNING:
DO NOT exceed the maximum number of
microinverters in an AC branch circuit — as displayed on the
unit’s label.
Note:
You may need to supply an AC Extension Connector cable
(ME-MGT-AC-EXT) if the microinverters on the same branch circuit
are greater than 6 feet apart.
1. Plug the female AC connector of the
fi
rst MicroGT inverter into
the male connector of the next microinverter (Figure 8), and so
on, to form a continuous AC branch circuit.
2. Install a protective end cap on the open AC connector of the last
microinverter in the AC branch circuit (Figure 9).
Figure 9, AC Connector Protective End Cap
B
A
B
MA
D
E
I
N
U
S
A
Figure 8, Connecting the MicroGTs via AC Connectors
AC Connectors
Note:
Use a screwdriver to
split the main connectors.
Installation