27
© 2016 Sensata Technologies
Operation
4.3.1 Operational
Notes
• To manually stop the generator during the run time cycle, simply
press the remote switch to the
OFF
position.
• If a fault condition occurs, press the AGS remote switch to
OFF
and then back to the
ENABLE
or
TEST
position. If the problem
persists, refer to the Troubleshooting section in this manual.
• When the AGS remote switch is placed in the
OFF
position,
all AGS generator start functions are disabled. The
STATUS
indicator is also off when the switch is in this position.
• Once the generator has completed the
RUN TIME HOURS
, the
AGS immediately begins to monitor the
START TEMP °F
and
START VOLTS DC
settings for the next autostart cycle.
• It is recommended that the AGS remote switch be set to the
OFF
position if the connected generator is placed into storage or left
unattended for extended lengths of time.
• If using the temperature start feature in an RV coach, set
the air conditioner thermostat to match the
START TEMP °F
setting. If using two air conditioners, it is suggested that the
second air conditioner thermostat be set 2°-5° higher than the
fi
rst air conditioner. This staggered setting allows the
fi
rst air
conditioner to start and run in an effort to keep the coach cool.
If the temperature continues to rise inside the coach, the second
air conditioner turns on to further cool the coach.
• When the generator starts successfully, the
STATUS
indicator
turns solid green. The generator runs until the
RUN TIME HOURS
setting is reached, at which time a stop signal is sent to the
generator.
• If the generator is running when either switch is placed in
the
TEST
position, the generator stops and then starts again.
The generator then runs for approximately 30 seconds before
shutting off.
• There is a two minute delay before the AGS attempts to start
the generator if the voltage to the AGS controller falls to the
START VOLTS DC
setting. There is no delay if the AGS attempts
to start the generator when the temperature around the remote
switch rises to the
START TEMP °F
setting.