51-638 Echotel Model 338 Two-Wire Ultrasonic Transmitter
30
1.6.11 Additional Software Parameters
P97 Software Code
P97 stores the software revision number.
P99 Password Protection
Factory default value for P99 is: 0000
P99 allows the entry of a password to protect all of the
software configuration data. This provides protection
against accidental (or intentional) re-programming of any
parameters.
The password can be any numeric value other than
0000
.
After setting a password, the password protection will
automatically be activated when the unit is returned to
the Measurement Mode. If password protection is activat-
ed, the software parameters can only be viewed; this is
indicated by a flashing colon ":" between the parameter
address and the parameter value.
In order to program a unit that has password protection,
first enter the password in
P99
. The password protection
is re-activated each time the unit is returned to the
Measurement Mode. To delete the password protection
feature, enter the password in
P99
. After confirming it
with
, re-enter parameter
P99
as
0000
as shown below:
[
enter password
]
➛
➛
➛
[0000]
➛
password
protection is turned off.