Display
Actions
Application
xx: Select "EU" (European) for metric or "US" for US engineering units by using UP
/ DOWN
keys
Factory Default Value: US and LI
After selecting the desired value push the ENTER
to save the value and proceed to the next parameter.
H: xxxx Range
(maximum measuring distance)
Distance between transducer face and bottom of the tank.
Manual Entry: Set value using UP
/ DOWN
/ NEXT
keys and save it with the ENTER
key.
Automatic Entry: Use the "Get Level" function (UP
+ DOWN
) to obtain the actual measured value
in the tank, or to a fixed target, i.e. wall. Push ENTER
to save value and proceed to the next parameter
Note: The "Get Level" feature only works if the Echo LED is lit.
Factory Default Value: 20 feet (maximum range)
4: xxxx
Level value assigned to 4 mA current output
Manual Entry: Set level value using UP
/ DOWN
/ NEXT
keys and save it with the ENTER
key.
Automatic Entry: Use the "Get Level" function (UP
+ DOWN
) to display the actual measured value
with level in the tank or to a fixed target. Push ENTER
to save value and proceed to the next parameter.
Note: The "Get Level" feature only works if the Echo LED is lit.
Factory Default Value: 0 feet (0% value or, empty tank)
20: xxxx
Level value assigned to 20 mA current output
Manual Entry: Set level value using UP
/ DOWN
/ NEXT
keys and save it with the ENTER
key
Automatic Entry: Use the "Get Level" function (UP
+ DOWN
) to display the actual measured value
with level in the tank or to a fixed target. Push ENTER
to save value and proceed to the next parameter.
Note: The "Get Level" feature only works if the Echo LED is lit.
Factory Default Value: 19.17 feet (100% full tank, this value is range minus the dead zone of 10")
Er
is the fail-safe Error indication value.
Select "Hold", "3.6" mA or "22.0" mA by using the UP
/ DOWN
keys, and push ENTER
to
save the value and proceed to the next parameter.
Factory Default Value: "Hold" last mA current value
dt
is the damping time (in seconds) required for the level application
Select 0, 3, 6, 10, 30, or 60 seconds by using the UP
/ DOWN
keys) and push ENTER
to save
it as above.
Factory Default Value: 60 seconds
51-638 Echotel Model 338 Two-Wire Ultrasonic Transmitter
8
NOTE: If no push buttons are pressed for 30 minutes, the transmitter
will automatically return to the measurement mode, and oper-
ate with the parameters entered during the last completed
programming.
NOTE: The Range, 4 mA, and 20 mA values shown below can be
entered manually, or by automatic entry using the "Get Level"
feature. Because the automatic entry involves moving the
liquid level to the exact 4 mA point, 20 mA point, and Range
values, the manual entry is the preferred configuration mode.
To enter or exit the
QuickSet Configuration
menu press
ENTER
+ DOWN
keys for 3 seconds.
Ap:xx
yy
H:xxxx
4:xxxx
20:xxxx
Er:xxxx
dt:xxxx