5.6.3 Write Enabling / Unlocking
Refer to section 2.6 of the PULSAR Model R86 Installation
and Operating Manual Bulletin 58-603 for information on
password protection.
When the alterations to the system are complete, ensure the
menu has been locked with the password to prevent inad-
vertent changes to the device.
5.7
Site Acceptance Testing
To ensure proper operation after installation and configura-
tion a site acceptance test should be completed. This proce-
dure is identical to the Proof Test Procedure described in
Section 6.1.4.
5.8
Recording Results
Results of Site Acceptance Testing must be recorded for
future reference.
5.9
Maintenance
5.9.1 Diagnostics
Internal diagnostic testing does a complete cycle approxi-
mately four times per minute. A message will appear and
the Output current will be driven to 3.6 or 22 mA (cus-
tomer selectable) upon detection of a Diagnostic Failure.
Worst-case internal fault detection time is one minute.
5.9.2 Troubleshooting
Report all failures to MAGNETROL.
Refer to Section 3.4 of the PULSAR Model R86
Installation and Operating Manual Bulletin 58-603 for
troubleshooting device errors.
• As there are no moving parts in this device, the only main-
tenance required is the proof test.
• Firmware can only be upgraded by factory personnel.
8
58-651 Pulsar
®
Model R86 SIL Functional Safety Manual