58-645 Pulsar® Model R86 Non-Contact Radar Transmitter – PROFIBUS PA Output
2.3.2.1 AI Out Display Screens
The Analog Input Block Out values can be conditionally
displayed as part of the “rotating” home menu screens. A
representative example is shown at left.
The screens will be formatted as shown with:
• Physical Device Tag (Selectable)
• Measured Value Status (Bad, Good, Uncertain)
• Bar Graph
For example, “AI1_Level” would be the most commonly
used AI Out screen.
“AI2---” would be displayed when the channel value is 0
[uninitialized] for AI block 2.
Because the Model R86 transmitter has eight (8) Analog
Input blocks, any or all of which may be used in particular
applications, a Transducer block parameter controls which
AI block Out values will be displayed on the LCD.
Any or all (or none) of the AI block Out values can be
selected for display on the LCD.
NOTE: In the photo at left, status is shown as “Bad out of Service”.
This message could be shown prior to commissioning.
Device Address screen
The address can be changed to any number from 0 to 126,
and changing the address does not require use of the
advanced password. (Note: changing or resetting the address
results in a reset of the transmitter.)
Physical Device Tag screen
The Tag can be set using the keypad and local display, or
from the Profibus interface.
The [AI Block] PV Scale values are automatically converted
to appropriate values if the units for the channel used by an
AI block are changed. For example, if PV Scale Upper Value
is 240 inches and Channel is Level, if Level Units is
changed from inches to feet, PV Scale Upper Value will
automatically change to 20 [feet].
LCD Screen