57-657 SIL Certified Safety Manual for ECLIPSE Model 706

Safe Failure Fraction (SFF) for each subsystem in a safety
system (Type B–complex components as per IEC 61508
Part 2) of which the level transmitter is just one component.

3. All products chosen for use in the SIF must meet the

requirements of IEC 61508 for the given SIL Capability
level or be justified based on proven in use data collected for
each job.

The exSILentia tool from exida is recommended for design
verification. This automatically checks all three limits and
displays the results for any given design. The ECLIPSE
Model 706 is in the exSILentia database. This tool contains
all needed failure rate, failure mode, SIL Capability and
common cause data as well as suggested proof test methods.

2.0

Applicable Models

This manual is only applicable to the HART versions of
the ECLIPSE Model 706 transmitter shown in Table 1.

NOTE: Ensure that the Model 706 transmitter and probe are installed

as  a  set  matched  by  the  Serial  Number  shown  on  the  name
plates.

3.0

Level Measuring System

The diagram at left shows the structure of a typical measuring
system incorporating the ECLIPSE Model 706 transmitter.
This SIL 2/3 Certified device is only available with an ana-
log signal (4–20 mA) with HART communications; and,
the measurement signal used by the logic solver can be the
analog 4–20 mA signal proportional to the Level, Interface
Level or Upper Layer Thickness.

• For fault monitoring, the logic unit must recognize both

high alarms (

 21.5 mA) and low alarms (

 3.6 mA).

• If the logic solver loop uses intrinsic safety barriers, caution

must be taken to ensure the loop continues to operate
properly under the low alarm condition.

• The only unsafe mode is when the unit is reading an

incorrect level within the 4–20 mA range (> ±2% deviation).

• MAGNETROL defines the faulted mode as one in which

the 4–20 mA current is driven out of range (i.e., less than
3.8 mA or greater than 21.5 mA).

• Volume and flow are not included in the safety function

for the ECLIPSE Model 706.

• The 4–20 mA output signal can be configured for over-

range per NAMUR NE43.

Actuator

PACTware

™ 

with

Eclipse

®

 DTM

HART Modem

Eclipse

®

 Model 706

Logic

Unit

Summary of Contents for Eclipse 706-512

Page 1: ...n the output will be driven to the customer specified out of range signal i e 3 6 mA or 21 mA The Enhanced Model 706 is certified for use in low demand level measurement applications Application The H...

Page 2: ...ronmental 6 6 1 2 1 Operating 6 6 1 2 2 Storage 6 6 2 Installation 6 6 3 Skill Level of Personnel 6 6 4 Necessary Tools 7 6 5 Configuration Information 7 6 5 1 General 7 6 5 2 Configuration 7 6 5 3 Wr...

Page 3: ...the liquid level The amplitude of the reflection depends on the dielectric con stant of the product The higher the dielectric constant the larger the reflection 1 3 Determining Safety Integrity Level...

Page 4: ...Serial Number shown on the name plates 3 0 Level Measuring System The diagram at left shows the structure of a typical measuring system incorporating the ECLIPSE Model 706 transmitter This SIL 2 3 Ce...

Page 5: ...an Time To Repair MTTR SIL determinations are based on a number of factors including the Mean Time To Repair MTTR The analysis for the ECLIPSE Model 706 is based on a MTTR of 24 hours 5 0 Supplementar...

Page 6: ...Manual 57 606 for Environmental limitations 6 1 2 1 Operating The operating temperature range is 40 to 175 F 40 to 80 C 6 1 2 2 Storage The device should be stored in its original shipping box and not...

Page 7: ...nfiguration Ensure the Model 706 transmitter has been properly config ured for the application and probe Special consideration should be given to the following configuration parameters Dielectric Rang...

Page 8: ...nse Times Continuous internal diagnostics are present within the Enhanced ECLIPSE Model 706 transmitter In the event a Fault is detected a message will appear on the LCD and the output current will be...

Page 9: ...indicate OK b Choose the menu DIAGNOSTICS EVENT HISTORY Event Log i Any FAULT or WARNING messages must be investigated and understood ii Corrective actions should be taken for FAULT messages continued...

Page 10: ...curves a Select DIAGNOSTICS ECHO CURVE View Echo Curve i Observe the present Echo Curve identify the characteristic portions of the waveform related to the FIDUCIAL Process level End of Probe and othe...

Page 11: ...figuration parameters avail able via the Local User Interface during normal operation The end user will enable the User Password to lock out any end user modifiable configuration parameters avail able...

Page 12: ...will respond to a change from the user s process within the safety function response time The Eclipse Model 706 shall transition to the Faulted Mode from the Normal Mode within the Diagnostic Test Int...

Page 13: ...13 57 657 SIL Certified Safety Manual for ECLIPSE Model 706 9 0 Appendices 9 1 SIL Certificate...

Page 14: ...14 57 657 SIL Certified Safety Manual for ECLIPSE Model 706 9 2 FMEDA Report exida Management Summary...

Page 15: ...itself and its operating conditions The assumption of a constant failure rate is based on the bathtub curve Therefore it is obvious that the PFDavg calculation is only valid for components that have...

Page 16: ...Mod Guideline on the Implementation of ANSI ISA 84 00 01 2004 Service Policy Owners of MAGNETROL controls may request the return of a control or any part of a control for complete rebuilding or replac...

Reviews: