BE 57-660 Eclipse Model 700 Guided Wave Radar Transmitter
2.4.2.1 To install a rigid single rod probe:
1. Ensure that the process connection is at least 1" NPT or is a
flanged mounting.
2. Carefully place the probe into the vessel. Align the gasket
on flanged installations.
3. Align the probe process connection with the threaded or
flanged mounting on the vessel.
4. For threaded connections, tighten the hex nut of the probe
process connection. For flanged connections, tighten flange
bolts.
5. When mounted directly into vessels, the probe can be stabi-
lized by placing the tip of the probe into a non-metallic cup
or bracket at the bottom of the probe.
A bottom spacer option is offered for mounting into a
metallic cup or bracket or for centering within a pipe/cham-
ber. Refer to Replacement Parts, Section 3.8 for additional
information.
2.4.2.2 To install a flexible single rod probe:
1. Make sure the process connection is at least 1" NPT or a
flanged mounting.
2. Carefully place the probe into the vessel. Align the gasket
on flanged installations.
3. Align the probe process connection with the threaded or
flanged mounting on the vessel.
4. For threaded connections, tighten the hex nut of the probe
process connection. For flanged connections, tighten flange
bolts.
5. Probe can be shortened in field:
a. Raise TFE weight (1) exposing securing device (2).
b. Loosen both #10–32 set screws (3) using 3/32" hex
wrench and remove securing device.
c. Cut and remove needed cable (4) length.
d. Reattach securing device and tighten screws.
e. Enter new probe length (in the appropriate units) into
the transmitter.
6. Probe can be attached to the tank bottom using the 13 mm
(0.50") hole provided in the TFE weight. Cable tension
should not exceed 23 Kgs (50 lbs).