20
6.5
Volume Calculation
P40: - - ba Tank/silo shape
ba
Tank/silo shape
Also to be set
b0
Standing cylindrical tank shape: value of “b” as below bottom
P40(b), P41
01
Standing cylindrical tank/silo with conical bottom
P41, P43, P44
02
Standing rectangular tank/silo (with chute)
P41, P42, (P43, P44, P45)
b3
Lying cylindrical tank shape: value of “b” as bellow bottom
P40(b), P41, P42
04
Spherical tank
P41
FACTORY DEFAULT: 00
P41-45:
Tank/silo dimensions
Standing cylindrical tank/silo
with hemispherical bottom
Standing cylindrical tank/silo
with conical bottom
Standing rectangular tank/silo
with or without chute
b=0
P40
b=1
b=2
b=3
If no chute
P43, P44 and P45=0
Lying cylindrical tank
Spherical tank
b=0
b=1
b=2
b=3
P40
6.6
Volume Flow Measuring
P40: - - ba Appliances, formula, data
ba
Appliances, formula, data
Also to be set:
Type
Calculation formula
Qmin
[l/s]
Qmax
[l/s]
“P”
[cm]
00
GPA-1P1
Q[l/s]= 60.87*h
1.552
0.26
5.38
30
P46
01
GPA-1P2
Q[l/s]= 119.7*h
1.553
0.52
13.3
34
P46
02
GPA-1P3
Q[l/s]= 178.4*h
1.555
0.78
49
39
P46
03
GPA-1P4
Q[l/s]= 353.9*h
1.558
1.52
164
53
P46
04
GPA-1P5
Q[l/s]= 521.4*h
1.558
2.25
360
75
P46
05
GPA-1P6
Q[l/s]= 674.6*h
1.556
2.91
570
120
P46
06
GPA-1P7
Q[l/s]= 1014.9*h
1.556
4.4
890
130
P46
07
GPA-1P8
Q[l/s]= 1368*h
1.5638
5.8
1208
135
P46
08
Magnetrol Parshall
flume
GPA-1P9
Q[l/s]= 2080.5*h
1.5689
8.7
1850
150
P46
09
General PARSHALL flume
P46, P42
10
PALMER-BOWLUS (D/2)
P46, P41
11
PALMER-BOWLUS (D/3)
P46, P41
12
PALMER-BOWLUS (Rectangular)
P46, P41, P42
13
Khafagi Venturi
P46, P42
14
Bottom-step weir
P46, P42
15
Suppressed rectangular or BAZIN weir
P46, P41, P42
16
Trapezoidal weir
P46, P41, P42
17
Special trapezoidal (4:1) weir
P46, P42
18
V-notch weir
P46, P42
19
THOMSON (90°-notch) weir
P46
20
Circular weir
P46, P41
21
General flow formula: Q[l/s]= 1000*P41*h
P42
, h [m]
P46, P41, P42