12
5.2.6 Full Parameter Access
To access all features provided by the Echotel.
Description of all parameters can be found under the chapter “Parameter” (Chapter 6.).
Keys
Function
ENTER
E
+ NEXT
(press for 3 seconds)
Enter or exit Full Parameter Access programming mode.
In this programming mode, the display will indicate:
yy is the Parameter Address
xxxx is the Parameter Value
Note: Measuring is going on during programming in accordance with the old parameter set. New parameter set will be valid
after returning to measurement from programming mode.
Steps and indications of the Full Parameter Access programming mode
pressing
Keys
while
Parameter Address is blinking
while
Parameter Value is blinking
ENTER
E
Go to the Parameter Value
Save the modification of the Parameter Value and return to the
Parameter Address
NEXT
+ UP
Cancel all modifications of the actual
programming phase. Pressing for 3 secs is
required while CANCEL will be displayed
for warning
Neglect the modification of the Parameter Value.
and return to the Parameter Address without saving the
modifications
NEXT
+ DOWN
Reset entire device to Factory Default.
Since this action will reset all parameters,
“LOAD” will appear on the display:
- to confirm, press ENTER
- to escape, press any other key
- Exception: clearing TOT 1 (See at P77)
Display default of the Parameter Values
(it can be saved by pressing ENTER
E
)
NEXT
Move blinking of the digit to the left
UP
/ DOWN
Modify the blinking digit (increase, decrease) or scroll up/down
6.
PARAMETERS – DESCRIPTIONS AND PROGRAMMING
6.1
Measurement Configuration
P00: - cba
Application/Engineering Units
Programming of this parameter will result in loading the factory default with the
corresponding engineering units.
a
Operating (measurement) mode
Display indication
0
Liquid level measurement
“Li”
1
Free flowing solids level measurement
“So”
b
Engineering units (according to “c”)
Metric
ft
0
m
inch
1
cm
inch
Attention: mind the sequence!
Coming to this parameter the right
value “a” will be blinking first.
c
Calculation system
0
Metric
1
US
FACTORY DEFAULT: 000
yy:xxxx