5.2.6 Full Parameter Access

To access all features provided by the Echotel.

Description of all parameters can be found under the chapter “Parameter” (Chapter 6.).

Keys

Function

ENTER 

E

 + NEXT 

(press for 3 seconds)

Enter or exit Full Parameter Access programming mode.

In this programming mode, the display will indicate:

yy is the Parameter Address
xxxx is the Parameter Value

Note: Measuring is going on during programming in accordance with the old parameter set. New parameter set will be valid
after returning to measurement from programming mode.

Steps and indications of the Full Parameter Access programming mode

 

pressing 

Keys

while

 Parameter Address is blinking

 

while 

Parameter Value is blinking

ENTER 

E

Go to the Parameter Value

Save the modification of the Parameter Value and return to the
Parameter Address

NEXT 

 + UP 

Cancel all modifications of the actual
programming phase. Pressing for 3 secs is
required while CANCEL will be displayed
for warning

Neglect the modification of the Parameter Value.
and return to the Parameter Address without saving the
modifications

NEXT 

 + DOWN 

Reset entire device to Factory Default.
Since this action will reset all parameters,
“LOAD” will appear on the display:
- to confirm, press ENTER
- to escape, press any other key
- Exception: clearing TOT 1 (See at P77)

Display default of the Parameter Values

(it can be saved by pressing ENTER 

E

)

NEXT 

Move blinking of the digit to the left

UP 

 / DOWN 

Modify the blinking digit (increase, decrease) or scroll up/down

6.

 

PARAMETERS – DESCRIPTIONS AND PROGRAMMING

6.1

 

Measurement Configuration

P00: - cba

Application/Engineering Units

Programming of this parameter will result in loading the factory default with the

corresponding engineering units.

a

Operating (measurement) mode

Display indication

0

Liquid level measurement

“Li”

1

Free flowing solids level measurement

“So”

b

Engineering units (according to “c”)

Metric

ft

0

m

inch

1

cm

inch

Attention: mind the sequence!

Coming to this parameter the right

value “a” will be blinking first.

c

Calculation system

0

Metric

1

US

FACTORY DEFAULT: 000

yy:xxxx

Summary of Contents for Echotel 335

Page 1: ...Echotel Series 335 338 Compact Ultrasonic Transmitter INSTALLATION and PROGRAMMING MANUAL...

Page 2: ...he 046 8108 001 Programming Module 9 5 2 3 Indications of the 046 8108 001 Programming Module and the LEDs 9 5 2 4 Current Output Scaling 10 5 2 5 QUICKSET 11 5 2 6 Full Parameter Access 12 6 PARAMETE...

Page 3: ...nic level metering technology is based on the principle of measuring the time required for the ultrasound pulses to make a round trip from the sensor to the level to be measured and back The sensor em...

Page 4: ...50 V AC 3 A HART optional Outputs Display 375 0SAP 100 6 digits icons and bargraph Custom LCD Electrical connections 2 x Pg16 and 2 x _ NPT Wire cross section 0 5 2 5 mm2 Electrical protection Class I...

Page 5: ...hotel FOAM Foaming of the liquid surface may render ultrasonic level measuring impossible If possible a location should be found where foaming is the smallest the device should be located as far as po...

Page 6: ...ic isolation is not provided The unit may be damaged by electrostatic discharge EDS via terminal thus apply the precautions commonly used to avoid electrostatic discharge 5 PROGRAMMING The Echotel wil...

Page 7: ...g completed all other magnetic influences will be avoided Minimum level 0 empty tank assignment to 4 mA Place the Echotel at a distance to the target corresponding to the required maximum distance min...

Page 8: ...22 mA 3 Place magnet to the symbol A Programming completed Damping Check valid echo as above Action LED indication 1 Place magnet to the symbol B Transmitter in programming mode 2 Place magnet to the...

Page 9: ...ent of level to de energising of the relay Full Parameter Access 5 2 6 All features of the Echotel can be accessed by parameter addresses Example Measurement configuration Outputs Measurement optimali...

Page 10: ...a ll modifica ti ons returnto pa r ameter addr ess P a r ame t e r va lu e A c tu a l Notes If the parameter value is not accessible i e the parameter address keeps blinking after pressing ENTER E th...

Page 11: ...level value measured by the Echotel ENTER E Save actual value on the screen and move to the next screen NEXT UP Quit Current Output Scaling without saving the modifications NEXT DOWN Display Factory D...

Page 12: ...value with level in tank or a fix target i e wall GET LEVEL functions only if ECHO LED is lit and save it as above DEFAULT maximum measuring distance m see Technical Data Table 4 mA xxxx level value...

Page 13: ...ill be displayed for warning Neglect the modification of the Parameter Value and return to the Parameter Address without saving the modifications NEXT DOWN Reset entire device to Factory Default Since...

Page 14: ...in mind that the instrument is measuring distance as basic quantity Measured distance Resolution Xmin 2m 1mm 2m 5m 2mm 5m 10m 5mm over 10m 10mm The resolution depending on the distance can be consider...

Page 15: ...of P04 see table below can also be displayed by double key pressing NEXT DOWN Echotel Maximum measuring distance Level transmitters for liquids PP or PVDF m ft Echotel 338 6 20 Echoptel 335 8 26 Keep...

Page 16: ...end of the measuring range for example tanks with heaters or other interfering objects sludge cone of silo etc may cause faulty readings If the level of the medium sinks below the blocked out range S...

Page 17: ...e Echotel will provide one of the current outputs below For errors and their indications see Chapter 7 a Error indication according to NAMUR 0 Hold last value 1 3 6 mA 2 22 mA FACTORY DEFAULT 0 6 3 Re...

Page 18: ...s parameter provides information for the QUEST software for optimising the echo search pattern a Estimated angle of repose 0 No angle of repose default 1 Below 15 2 Over 15 The optimal setting of this...

Page 19: ...Liquids P00 Li P27 2000 P28 a Echo loss handling a Echo loss error indication Remark 0 Delayed During echo loss display and analogue output will hold last value If the echo loss prevails for 10 sec p...

Page 20: ...eter if the Echotel unambiguously selects a wrong echo for example the echo reflected from the surface is much weaker than the interfering one s see figure beside and on next page Enter the distance o...

Page 21: ...ormula data Also to be set Type Calculation formula Qmin l s Qmax l s P cm 00 GPA 1P1 Q l s 60 87 h1 552 0 26 5 38 30 P46 01 GPA 1P2 Q l s 119 7 h1 553 0 52 13 3 34 P46 02 GPA 1P3 Q l s 178 4 h1 555 0...

Page 22: ...Parshall flume Sensor P 46 Sensor P40 09 General Parshall flume 0 305 P42 width 2 44 0 026 Q m3 s 0 372 P42 h 0 305 1 569 s 2 5 P42 Q m3 s K P42 h1 6 P 2 3 A A h P46 Sensor Sensor P42 P P40 10 Palmer...

Page 23: ...oidal weir 0 0032 Q m3 s 82 20 P41 100 0 5 P42 m 15 0 1 h m 2 Q m3 s 1 772 P42 h1 5 1 320 tg P41 2 h2 47 Accuracy 5 P04 P46 h P42 P41 P40 17 Special Trapezoidal 4 1 weir 0 0018 Q m3 s 50 0 3 P42 m 10...

Page 24: ...s in the table Address Serial number of the data pair Measurement value to be transmitter and displayed Conditions of correct programming of the data pairs Left column L Right column r L 1 0 r 1 L i r...

Page 25: ...he actual close end blocking distance is displayed Provides useful information if automatic blocking was selected in P05 6 9 Additional Open Channel Flow Metering Features P76 LEV Head of flow The Hea...

Page 26: ...order to program the device locked by a secret code first enter the Secret Code in P99 The Secret Code is re activated each time the Echotel is returned to Measurement Mode To delete the Secret Code...

Page 27: ...4 14 Maximum measuring distance P29 18 Blocking out of object 1 P05 15 Minimum measuring dist Close end blocking P30 18 Blocking out of object 2 P06 15 Far end blocking P31 19 Sound velocity at 20_C P...

Page 28: ...N A P71 24 Distance of the of Measuring Window read out parameter P96 N A P72 24 Amplitude of the Echo in the Measuring read out parameter P97 24 Software code P73 24 Echo Position time read out para...

Reviews: