Magnetrol B73 Instruction Manual And Parts List Download Page 3

3

INSTALLATION

CRITICAL ALARM FUNCTION

It is recommended that for critical alarm functions, an addi-
tional level switch be installed as a high-high or low-low
level alarm for maximum protection.

PIPING

Figure 3 shows a typical piping installation of a Magnetrol
level switch to a pressure vessel. Reference mark on float
chamber should be aligned to correspond with liquid level
in vessel at which switch control is desired.

Use pipe of sufficient strength to support the control. If nec-
essary, provide a stand or hanger to help support its
weight. All piping should be straight and free of “low spots”
or “pockets” so that lower liquid line will drain towards the
vessel and upper vapor line will drain toward the control.
Shut-off valves are recommended for installation between
the vessel and the control. If control is to be used with a
lower temperature liquid (one which will “boil” in the float
chamber if outside heat is absorbed), the chamber and pip-
ing should be insulated. Such boiling in the chamber will
cause false level indications. DO NOT INSULATE SWITCH
MECHANISM HOUSING.

On controls equipped with pneumatic switch assemblies,
consult bulletin on mechanism furnished for air (or gas) pip-
ing instructions. Refer to chart on this page for bulletin num-
bers for pneumatic switches.

MOUNTING

Adjust piping as required to bring control to a vertical posi-
tion. Magnetrol controls must be mounted within three (3°)
degrees of vertical. A three degree slant is noticeable by
eye, but installation should be checked with a spirit level on
top and/or sides of float chamber.

Controls should be mounted as close to the vessel as pos-
sible. This will result in a more responsive and accurate
level change in the control. Liquid in a long line may be
cooler and more dense than liquid in the vessel causing
lower level indication in the control than actual level in the
vessel.

cable entry

Pressure
vessel

Switch

actuating

level

reference

marks

Drain

valve

Shutoff

valve

Max 

305 mm

Figure 3

WIRING

Most mechanical control switch housings are designed to
allow 360° positioning of the cable entries by loosening the
set screw(s). See figure 4. On high temperature applica-
tions (above 120° C [250° F]), high temperature wire should
be used between control and first junction box located in a
cooler area.

1. To gain access to switch mechanism(s) remove switch

housing cover. (See CAUTION next page.)

2. Pull in supply wires (conductors), wrap them around

enclosing tube under the baffle plate and connect to
proper terminals. Be certain that excess wire does not
interfere with "tilt" of switch and that adequate clearance
exists for replacement of switch housing cover.

NOTE: See bulletin on switch mechanism furnished with
your control (as listed below) for proper connections.

3. Connect power supply to control and test switch action

by varying liquid level in tank or vessel.

CAUTION: 
In hazardous area, do not power the unit until
the cable gland is sealed and the enclosure
cover is screwed down securely.

NOTE: If switch mechanism fails to function properly, check
vertical alignment of control housing and consult installation
instructions in switch mechanism bulletin.

4. Replace switch housing cover and place control into ser-

vice.

NOTE: If control has been furnished with an explosion proof
(cast) or moisture proof (gasketed) switch housing, check
the following:

– After wiring connections have been completed, housings

must be sealed via the correct cable gland to prevent
entrance of air.

– Check cover to base fit, to be certain gasketed joint is

tight. A positive seal is necessary to prevent infiltration of
moisture laden air or corrosive gases into switch housing.

Switch mechanism

Bulletin

Reference series

Mercury switches

42-783

A

Dry contact switches

42-683

B, C, D, U, W, X

Anti-vibration mercury switches

E

Anti-vibration dry contact switches

42-684

G, H, I

Bleed type pneumatic valve

42-685

J

Non-bleed type pneumatic valve

42-686

K

Summary of Contents for B73

Page 1: ...g in position Swing out position HL LL Enclosing tube non magnetic OPERATING CYCLE As the liquid level rises in the chamber refer to Figure 1 the float moves the magnetic attraction sleeve up within the enclosing tube and into the field of the switch mechanism magnet As a result the magnet is drawn in tightly to the enclosing tube causing the switch to trip making or break ing an electrical circui...

Page 2: ... EX6 ED5 EW5 mercury switch Series F 230 C Snap switch 450 F SPDT FAP F2P F3P FKR FK8 FU8 FK7 FU7 FAQ F2Q F3Q FKY FK6 FU6 FK5 FU5 hermetically DPDT FDP F8P F9P FNR FN8 FX8 FD7 FW7 FDQ F8Q F9Q FNY FN6 FX6 FD5 FW5 sealed Series HS 230 C Snap switch 450 F SPDT HM2 H7A H6A HS3 HB1 HB2 HB3 HB4 hermetically sealed with DPDT HM6 H7C H6C HS7 HB5 HB6 HB7 HB8 terminal block Series U 120 C SPDT UAP U2P U3P U...

Page 3: ...el in the vessel cable entry Pressure vessel Switch actuating level reference marks Drain valve Shutoff valve Max 305 mm Figure 3 WIRING Most mechanical control switch housings are designed to allow 360 positioning of the cable entries by loosening the set screw s See figure 4 On high temperature applica tions above 120 C 250 F high temperature wire should be used between control and first junctio...

Page 4: ... and lever Such wear can cause false switch actuat ing levels Adjust switch mechanism to compensate if possible or replace switch DO NOT operate your control with defective maladjusted switch mechanisms refer to bulletin on switch mechanism furnished for service instructions Magnetrol controls may sometimes be exposed to excessive heat or moisture Under such conditions insulation on electrical wir...

Page 5: ...ould restrict movement preventing sleeve s from reaching field of magnet s 5 Fill chamber with liquid at room pressure Check float s to be certain it is buoyant in the liquid float chamber must have adequate liquid level If float is determined to be filled with liquid or collapsed entire float chamber assembly sensing unit should be replaced CHECK COMPLETE UNIT Reassemble the unit Reconnect the po...

Page 6: ...andard Construction 89 3410 009 Stainless Steel Connection Sleeve Kit 5 Guide Washer 6 Attraction Sleeve 7 Enclosing Tube Models with material code 1 2 Models with material code 3 4 Nema 4X Nema 7 9 Pneumatic Switch Housing 32 6302 031 32 6302 036 Baseefa Cenelec 32 6344 002 32 6344 001 12 1301 002 8 E Tube Gasket 9 Chamber Assembly Chamber assemblies are available as complete sensing units ONLY w...

Page 7: ... 1 2 163 2 6 42 0 08 for material code 4 250 2 9 84 0 08 250 2 9 84 0 08 83 2 3 27 0 08 160 2 6 30 0 08 160 2 6 30 0 08 Housing A B Entry C max D IP 65 NEMA 4x 151 5 93 109 4 29 1 NPT M20 x 1 5 or PG16 2 entries 1 plugged 459 18 07 NEMA 7 9 IP 65 143 5 63 100 3 94 1 NPT 1 entry 453 17 83 CENELEC BASEEFA IP 66 143 5 63 110 4 33 3 4 NPT OR M20 x 1 5 2 entries 507 19 80 NEMA 3R IP 53 Pneumatic K 118 ...

Page 8: ...E So that we may efficiently process any materials that are returned it is essential that a Return Material Authorisation RMA form will be obtained from the factory It is mandatory that this form will be attached to each material returned This form is avail able through Magnetrol s local representative or by contacting the factory Please supply the following information 1 Purchaser Name 2 Descript...

Reviews: