Intelli-Protect User Manual
April 2023
4.4 Zone Setup
To configure the location of a No-Fly Zone, first disable the zone by clearing the ‘Enable’ checkbox. On
initial setup, all zones are disabled by default. Each zone is numbered from 1 to 31. Use the Previous and
Next buttons at the top of the menu to scroll between all 31 zone configurations.
Each zone displays a user-customizable ID descriptor or name for added clarity.
Position the hoist at one corner of the desired zone and press the
Teach Initial Corner
button to store the
initial corner position of the zone.
Position the hoist at the diagonal corner of the desired zone and press the
Teach Diagonal Corner
button
to store the corner position and finalize the zone.
If needed the data can be entered manually by pressing on the measurement. The value entered can be
beyond the configured travel limits.
1.
Zone Configuration
a.
Press the previous or next buttons until
the desired zone number appears
b.
Press the Enable button to remove the
check box if enabled
c.
Move hoist to one corner
d.
Press
Teach Initial Corner
button
e.
Move hoist to opposite diagonal corner
f.
Press
Teach Diagonal Corner
button
g.
Move the hoist away
h.
Press the Enable button to enable zone
protection
i.
Press the ID field to enter a name
Figure 4-6: Configuring and Enabling a Zone
Summary of Contents for Intelli-Protect NFZ-CONFIG-5050
Page 1: ...Intelli Protect User Manual Part Number 113 11850 Rev 02 April 2023 Copyright 2023 Magnetek...
Page 35: ...Intelli Protect User Manual April 2023 Page 35 of 65 Figure 4 2 Zone Configuration...
Page 38: ...Intelli Protect User Manual April 2023 Page 38 of 65 Figure 4 4 Zone Configuration...
Page 46: ...Intelli Protect User Manual April 2023 Page 46 of 65 Figure 4 12 Zone Overview Setup...
Page 64: ......
Page 65: ...Intelli Protect User Manual Part Number 113 11850 Rev 02 April 2023...