background image

Appendix 

– PM Alignment Procedure 

13 

 

c.  Drive asserts SPD_REG_RLS and 

CLOSE_CONTACT (all other outputs 
will operate as programmed and have 
no special status or benefit during the 
Alignment Procedure) 

d.  Motor Contactor closes 
e.  Drive asserts BRAKE_PICKED, if used 
f. 

Brake is lifted 

g.  Drive starts the Open Loop Alignment 

running at approximately 1/8

th

 of the 

rated motor speed (A5) 

h.  When the Alignment is finished, the 

drive will go to zero speed and simulate 
removal of the run command (i.e. SPD 
REG RLS = 0 (false); CLOSE 
CONTACT = 0 (false)) even if Run 
Command is still being asserted 

i. 

Run Command is removed 

During the test, the motor should rotate for 
about four seconds and the RUN light will be lit 
for the duration of the procedure. 

 

Erratic movement of the motor may occur 
during acceleration and deceleration 
segments of the alignment, but constant 
speed operation will be smooth. If the 
motor is jerking as it is rotating, increase 
the OL ALIGN SCALE (A5) by 0.5. 

 

If the alarm 

SPD DEV ALM

 is displayed, 

increase the value of SPD DEV ALARM 
LVL (A1) then retry procedure to see what 
fault the drive may actually be getting. The 
SPD DEV ALM will not allow the alignment 
procedure to finish and must be moved out 
of the way to proceed. 

 

If the fault 

SPD DEV FLT

 is displayed, 

first, verify the shield of the encoder cable 
is properly grounded. Then retry the 
alignment procedure. If the fault still exists, 
increase SPD DEV FLT LVL (A1), and 
then retry alignment procedure. 

 

If the fault 

OVERCURR FLT

 is displayed; 

decrease ALIGN VLT FACTOR (A4) 
and/or the OL ALIGN SCALE (A5) retry 
alignment procedure 

 

If 

ENCODER FAULT

 or

 TACH LOSS

 is 

displayed, verify that the encoder is 
working or that the brakes on the motor 
are being picked. 

6)  View the value of ENCODER ANG 

OFST(A5).  If the value is 30000, the 
alignment procedure did not work and 
must be redone. If the, ENCODER ANG 
OFST (A5) is 00000, the alignment 
procedure passed. 

7) 

Enter the value in ‘Measured PPR’ (D1) 
into ‘Encoder Pulses’ (A1) 

8)  Run motor at 20% contract speed and 

verify alignment is correct. 

 

If ropes are not attached, set INERTIA 
(A1) to 0.25 seconds 

 

If the SPD DEV FLT occurs, check if 
TORQ CURR (D2) is greater than 5% 
(>5%).  If this is the case, repeat the 
alignment procedure. 

9)  Run the motor at 100% contract speed. 

While the motor is running at contract 
speed, make note of number in the 
‘Measured PPR’ (D1). 

10) 

Enter the ‘Measured PPR’ from above at 
contract speed in

to ‘Encoder Pulses’ (A1) 

Auto Alignment Procedure 

Auto Alignment is a function that will calculate 
the alignment angle without the need to spin 
the motor. This procedure has to be done with 
the brake set.  This is especially useful for 
replacing encoders. Auto Alignment may be 
enabled two separate ways, one way is to 
enable the function through the operator and 
the other is to enable Auto Align by giving the 
drive a run command. In order for the function 
to properly work, all faults must be cleared 
(FAULT LED is off), the brake must be set, and 
the motor contactor must pull in. 
 

NOTE: If HF Inject can be performed, it is 
recommended that the HF Inject be performed 
instead of the Auto Alignment because HF 
Inject is more reliable. 

1)  In order to accurately measure the 

alignment, the brake must be set and the 
motor contactor must be closed. 
Depending on the method used for 
enabling Auto Alignment, drive signals 
may be used in conjunction with the 
contactor. 

2)  Run the Auto Alignment (U10) to 

determine the position of the motor poles.  

 

Press Enter, then the UP Arrow to display: 

                            10:00                         May 4 

  U0   UTILITY 
  U10  ALIGNMENT 

READY 

RUN 

USER 

TORQUE 

LIMIT 

FAULT 

SUBMENU 

DATA ENTRY 

Summary of Contents for CPA HPV 900 Axial Flux PM Series

Page 1: ...xial Flux PM Technical Manual NOTE This is a supplementary manual for the PM Axial Flux If any detail about the HPV900 Series 2 is needed please refer to the technical manual TM7333 TM7354 Rev 20 2017...

Page 2: ...responsibility or accept invoices for unauthorized repairs to its components even though defective The life of the products the Company depends to a large extent upon type of usage thereof and THE COM...

Page 3: ...The drive has a common ground bus terminal connection All grounds need to land at this common point including building motor transformer and filter grounds This will limit the impedance between the g...

Page 4: ...ng Instructions 6 Encoder Electrical Connection 8 Proximity Sensor Electrical Connection 8 PM Drive Setup Procedure 9 PM Alignment Procedure 11 HF Inject preferred method 11 Open Loop Alignment 12 Aut...

Page 5: ...cludes all parameters in the A1 A5 submenu and C1 C4 submenus 3 Proceed to PM Drive Setup Procedure on page 9 to continue with setting of motor data Encoder Pulses rotor alignment and auto tune 4 Refe...

Page 6: ...5 5 5 250 10 16 19 40 2 HPV900 4016 2E1 02 200 8 20 21 15 10 11 7 5 250 10 21 24 53 3 HPV900 4021 2E1 02 200 8 26 28 4 20 15 15 11 250 10 27 31 68 3 HPV900 4027 2E1 02 6 200 8 34 36 0 25 20 19 15 250...

Page 7: ...8ft of cable between the drive and motor 46S04444 0100i 100m cable for encoder 100m cable for proximity sensor encoder 37 3mm rider wheel proximity sensor sensor bracket target and other misc hardware...

Page 8: ...the encoder at low running speeds PPR D1 Elevator Data Name Description Units Recommendation Measured PPR This is a setup fine tuning parameter This parameter will show how many pulses the drive coun...

Page 9: ...nput 2 shield analog output 1 2 3 4 5 6 Speed Cmd 10VDC PreTorque Cmd 10VDC 1 7 analog output 2 analog common 27 28 29 30 31 32 relay 1 relay 2 HPV 900 Axial Flux input power R S T 17 18 1 2 3 4 19 20...

Page 10: ...icture of Proximity Sensor PN 05P00217 0097 1 The rider wheel should be tightly fitted on the incremental encoder s shaft as shown in Figure 4 with 2mm allen key or a Philips head screw driver dependi...

Page 11: ...6 Picture of encoder proximity sensor and sensor bracket PN 43T02814 0030 4 Ascertain the correct location on the rotor where the target is to be fitted and prepare the surface by cleaning using the a...

Page 12: ...ale proximity sensor end connector into the female cable end connector Finally rotate the coupling ring on the female connector in the opposite direction until it latches into its closed position Figu...

Page 13: ...is mounted on a rider wheel that sits on the rotor 1 revolution of the rider wheel doesn t equate to 1 revolution of the motor a Ropes off PPR preferred i with ropes removed from off sheave perform an...

Page 14: ...r poles needs to be performed The 3 methods to find the motor pole are High Frequency HF Injection Open Loop Align and Auto Align beginning on page 11 in PM Alignment Procedure NOTE HF injection is re...

Page 15: ...the ALIGNMENT from DISABLE to ENABLE then press Enter as shown below 5 Press the DOWN arrow to see BEGIN ALIGNMENT Note If the operator displays the screen below verify ALIGNMENT U10 is set to enable...

Page 16: ...GNMENT from DISABLE to ENABLE Press ENTER Press the DOWN arrow to start the alignment procedure The operator will display Note If the operator displays the following screen verify ALIGMENT U10 is set...

Page 17: ...akes on the motor are being picked 6 View the value of ENCODER ANG OFST A5 If the value is 30000 the alignment procedure did not work and must be redone If the ENCODER ANG OFST A5 is 00000 the alignme...

Page 18: ...dure Note If the operator displays the following screen verify ALIGNMENT U10 is set to enable there are no active faults FAULT LED is off and the drive is not in a RUN mode RUN LED is off During Align...

Page 19: ...nt to the motor and calculate the motor characteristics 5 If the selection ON RUN is made the drive expects the following sequence to occur prior to the drive applying current to motor Command run ins...

Page 20: ...motor phasing Incorrect Encoder Phasing Verify that the encoder phasing is correct Swap encoder A and A channel on TB1 1 and TB1 2 Perform an Open Loop Alignment Encoder Power Supply Check that the e...

Page 21: ...up with the proximity sensor using the Z Edge Count D1 Verify that there is no noise on the proximity sensor channel by verifying that the Z Edge Count D1 isn t incrementing decrementing more than on...

Page 22: ...Parameter Setting Verify that the Encoder Pulses A1 matches the number for Measured PPR D1 while the motor is rotating at high speed If they don t match enter measured PPR in Encoder Pulses A1 RTR NOT...

Page 23: ...ent Procedure on page 11 Usually drive s HIT TORQUE LIMIT alarm message is displayed depending on setting of TRQ LIM MSG DLY A1 parameter Verify drive and or motor sizing May need a larger capacity HP...

Page 24: ...mity sensor every time the target is lined up with the proximity sensor using the Z Edge Count D1 Verify that there is no noise on the proximity sensor channel by verifying that the Z Edge Count D1 is...

Page 25: ...motor The drive takes approximately 0 30s to perform the HF Inject before running NOTE the brakes should NOT be opened while the drive is performing this initial magnet search after power up or an en...

Page 26: ...e Proximity Sensor LA46S04416 0100 FRU 100 meter cable for Proximity Sensor Includes 100 meters 328 ft of cable for the Proximity Sensor LA05P00057 0112 FRU Motor Encoder Kit Includes Incremental Enco...

Page 27: ...cy Injection High Frequency Injection 11 21 HIT TORQUE LIMIT 17 M Measured PPR 4 9 Mechanically mount 1 6 Model Number 2 Motor data 9 O Once Per Revolution Bump 18 Open Loop Alignment 12 P Parts See S...

Page 28: ......

Page 29: ......

Page 30: ...Magnetek Elevator Products N50 W13775 Overview Dr Menomonee Falls Wisconsin 53051 800 236 1705 262 252 6999 FAX 262 790 4142 http www elevatordrives com Magnetek Elevator Products Europe Unit 3 Bedfor...

Reviews: