Air Filter

All indoor return air must be filtered. A washable filter is 

furnished with the unit, located in the return air compartment. 

If the optional front return opening is used and a duct is 

installed, provisions must be made to accommodate filter 

servicing. If a filter is installed at a separate central return 

location, then the factory furnished filter must be removed 

from the unit.

The  filter  should  be  cleaned  at  least  three  times  during 

each of the heating and cooling seasons, or more 

frequently if unusual conditions are encountered. To clean 

the washable filter, shake filter to remove excess dirt and/

or use a vacuum cleaner. Wash filter in soap or detergent 

water and replace after filter is dry. It is not necessary to oil 

the filter after washing.

The  washable  filter  may  be  replaced  with  a  disposable 

filter. Table 4 lists filter sizes that fit the unit.

Model Number

Filter Size 

(in.)

*MCE4-11-09* 

*MCE4-11-12* 

*MCE4-11-18*

18 x 20 x 1

*MCE4-11-24*

20 x 22 x 1

*MCE4-11-30*

22 x 24 x 1

*MCE4-11-36*

22 x 28 x 1

Table 4. Filter Sizes

If an installation is made in which it is more desirable to 

mount the filter exterior to the unit, in the return duct work 

or elsewhere, the washable filter can be used or replaced 

with a disposable filter. If a disposable filter is used, use the 

information provided in Table 5 when sizing the disposable 

filter.

Model Number

Filter Area 

(in

2

)

*MCE4-11-09* 

*MCE4-11-12*

250

0MCE4-11-18* 

3MCE4-11-18* 

5MCE4-11-18*

310

7MCE4-11-18* 

10MCE4-11-18*

380

*MCE4-11-24*

420

*MCE4-11-30*

480

*MCE4-11-36*

575

Table 5. Minimum Required Surface Area for 

Disposable Filters

Condensate Drain

Provisions must be made to properly drain the indoor and 

outdoor drain pans of this appliance.

Indoor drain and outdoor drain connection: 3/4” NPT to 

3/4” PVC fitting (schedule 40 minimum). Both drains must 

be trapped as shown in Figure 6. The drain line should 

pitch gradually downward at least 1” per 10’ of horizontal 

run to an open drain.

If local codes require the use of metal condensate lines, 

do not thread metal fittings into the unit drain pans. Thread 

a PVC fitting into the unit drain pans and make the field 

connection to the PVC fitting. 

NOTE: 

MCE units are designed with a redundant drain 

system  to  handle  condensate  without  the  need  for  a 

secondary  or  emergency  drain  pan.  Should  the  indoor 

coil  condensate  drain  system  fail,  all  water  is  contained 

within the unit and the flow is directed into the unit base 

pan.  From  there  it  will  drain  into  the  condensate  riser. 

If  for  some  reason  the  water  cannot  drain  into  the  main 

condensate riser, all water is contained in the unit, and the 

design will allow drainage out through the wall sleeve and 

louver assembly to the outside of the building.

Use  thread  sealant  on  the  threaded  fittings.  Install 

threaded fittings by hand only. 

Do not over torque the 

fittings.

Do  not  thread  metal  condensate  fittings  to  unit  drain 

pans.

 CAUTION

Figure 6. Condensate Drain Installation

Summary of Contents for MCE4 Series

Page 1: ...nd any state or provincial laws or local ordinances Local authorities having jurisdiction should be consulted before installation is made Such applicable regulations or requirements take precedence ov...

Page 2: ...ated airflow requirements ofANSI ASHRAE 193 complies with IECC 2015 are identified on the rating plate Installation and servicing of air conditioning equipment can be hazardous due to internal refrige...

Page 3: ...g a door or access panel opposite the front of the unit is the preferred method of providing access The door or access panel must be at least 30 wide centered on the unit and as tall as the unit IMPOR...

Page 4: ...ille Installation Refer to installation instructions included with the wall sleeve kit and the louver grille kit along with Figure 2 for guidance in assembling and installing the wall sleeve and louve...

Page 5: ...on to top and bottom corners of unit to sleeve seal Caulk if needed Ductwork Ductwork should be designed and sized according to the methods in Manual Q of the Air Conditioning Contractors of America A...

Page 6: ...0 08 475 68 0 09 440 73 0 10 400 77 0 10 5 kW TAP 4 HEAT 525 59 0 08 505 65 0 09 480 69 0 09 N A N A N A N A N A N A TAP 5 HEAT 615 81 0 11 590 88 0 12 560 94 0 13 530 99 0 13 500 103 0 14 MCE4 11 181...

Page 7: ...HEAT 740 65 0 09 705 74 0 10 640 83 0 11 N A N A N A N A N A N A TAP 5 HEAT 820 81 0 11 790 91 0 12 740 100 0 13 675 109 0 15 600 117 0 16 7 kW TAP 4 HEAT 860 91 0 12 835 100 0 13 795 108 0 14 N A N A...

Page 8: ...er Model Number Filter Area in2 MCE4 11 09 MCE4 11 12 250 0MCE4 11 18 3MCE4 11 18 5MCE4 11 18 310 7MCE4 11 18 10MCE4 11 18 380 MCE4 11 24 420 MCE4 11 30 480 MCE4 11 36 575 Table 5 Minimum Required Sur...

Page 9: ...xtures or appliances Follow manufacturer s instructions enclosed with the thermostat for general installation procedures Color coded insulated wires 18 AWG should be used to connect the thermostat to...

Page 10: ...wer up to unit there is a 3 minute time delay to the compressor contactor R to Y Any 24V interrupt R C to the defrost control will initiate the 3 minute delay to the contactor Cooling When the thermos...

Page 11: ...1P Extruded Aluminum Louver Kit 33 Height ALVRAL 2 Extruded Aluminum Louver Kit Custom Color 33 Height ALVRAL 2P Extruded Aluminum Louver Kit 45 Height ALVRAL 3 Extruded Aluminum Louver Kit Custom Co...

Page 12: ...Louver ASLEEVE8 2 8 32 3 4 16 16 5 8 32 7 8 for 45 Louver ASLEEVE8 5 8 45 16 16 5 8 45 1 8 10 Wall Sleeve Kit for 29 Louver ASLEEVE10 1 10 29 16 16 5 8 29 1 8 for 33 Louver ASLEEVE10 2 10 32 3 4 16 16...

Page 13: ...507860 01 Issue 1927 Page 13 of 14 Figure 9 Connection Diagram MCE Without Electric Heater 538012 01 Wiring Diagrams...

Page 14: ...Page 14 of 14 507860 01 Issue 1927 Figure 10 Connection Diagram MCE With Factory Installed Electric Heater 538013 01...

Reviews: