Magic-Pak MCE4 Series Installation And Maintenance Instructions Manual Download Page 2

Page 2 of 14

507860-01

Issue 1927

Minimum and maximum operation conditions must be 

observed to assure maximum system performance 

with minimum service required. Refer to Table 1 for the 

application limitations of the unit.

Table 1. Application Limitations

Outdoor Ambient Air Temperature °F

Minimum DB

Maximum DB

Cool 

Cool 

Heat

65

115

75

Indoor Ambient Air Temperature °F

Minimum 

Maximum

DB/WB

DB

DB/WB

DB

Cool

Heat 

Cool

Heat

62/57

50

90/72

80

DB = Dry Bulb
WB = Wet Bulb

Location

The unit must be installed with approved wall sleeve 

and grille accessories for safe operation. Improper 

installations could result in property damage, personal 

injury, or death.

 WARNING

For information on wall sleeves and grille accessories, see 

the 

Accessories

 section. 

The  design  is  certified  for  thru-the-wall  or  up-to-the  wall 

(inside wall) installation only. The interior portions of 

the unit may be surrounded by a closet with clearances 

to combustible material held to 0” at the sides, top, and 

front of the plenum. All servicing and cleaning of the unit 

can be performed from the front. If installed in a closet 

or utility room, provide 25” clearance in front for service 

if the door to the room is not in line with the front of the 

unit (see Figure 1). 

Accessibility clearances must take 

precedence over fire protection clearances.

Units that comply with the maximum cabinet leakage 2% of 

rated airflow requirements of ANSI/ASHRAE 193 (complies 

with IECC 2015) are identified on the rating plate.

Installation and servicing of air conditioning equipment 

can be hazardous due to internal refrigerant pressure 

and live electrical components. Only trained and 

qualified  service  personnel  should  install  or  service 

this equipment. Installation and service performed by 

unqualified  persons  can  result  in  property  damage, 

personal injury, or death.

 WARNING

For your safety, do not store or use gasoline or other 

flammable vapors and liquids in the vicinity of this or any 

other appliance. Such actions could result in property 

damage, personal injury, or death.

 WARNING

The unit must be installed with approved wall sleeve 

and grille accessories for safe operation. Improper 

installations could result in property damage, personal 

injury, or death.

 WARNING

Inspection

Upon receipt of equipment, carefully inspect it for possible 

shipping damage. If damage is found, it should be noted 

on the carrier’s freight bill. Take special care to examine 

the unit inside the carton if the carton is damaged. File a 

claim with the transportation company. 

If any damages 

are discovered and reported to the carrier do not 

install the unit, as claim may be denied.

Check the unit rating plate to confirm specifications 

are as ordered.

Limitations

The unit should be installed in accordance with all national 

and local safety codes.

Limitations of the unit and appropriate accessories must 

also be observed.

The outdoor fan is designed to operate against no more 

than .10” w.c. static pressure.

Summary of Contents for MCE4 Series

Page 1: ...nd any state or provincial laws or local ordinances Local authorities having jurisdiction should be consulted before installation is made Such applicable regulations or requirements take precedence ov...

Page 2: ...ated airflow requirements ofANSI ASHRAE 193 complies with IECC 2015 are identified on the rating plate Installation and servicing of air conditioning equipment can be hazardous due to internal refrige...

Page 3: ...g a door or access panel opposite the front of the unit is the preferred method of providing access The door or access panel must be at least 30 wide centered on the unit and as tall as the unit IMPOR...

Page 4: ...ille Installation Refer to installation instructions included with the wall sleeve kit and the louver grille kit along with Figure 2 for guidance in assembling and installing the wall sleeve and louve...

Page 5: ...on to top and bottom corners of unit to sleeve seal Caulk if needed Ductwork Ductwork should be designed and sized according to the methods in Manual Q of the Air Conditioning Contractors of America A...

Page 6: ...0 08 475 68 0 09 440 73 0 10 400 77 0 10 5 kW TAP 4 HEAT 525 59 0 08 505 65 0 09 480 69 0 09 N A N A N A N A N A N A TAP 5 HEAT 615 81 0 11 590 88 0 12 560 94 0 13 530 99 0 13 500 103 0 14 MCE4 11 181...

Page 7: ...HEAT 740 65 0 09 705 74 0 10 640 83 0 11 N A N A N A N A N A N A TAP 5 HEAT 820 81 0 11 790 91 0 12 740 100 0 13 675 109 0 15 600 117 0 16 7 kW TAP 4 HEAT 860 91 0 12 835 100 0 13 795 108 0 14 N A N A...

Page 8: ...er Model Number Filter Area in2 MCE4 11 09 MCE4 11 12 250 0MCE4 11 18 3MCE4 11 18 5MCE4 11 18 310 7MCE4 11 18 10MCE4 11 18 380 MCE4 11 24 420 MCE4 11 30 480 MCE4 11 36 575 Table 5 Minimum Required Sur...

Page 9: ...xtures or appliances Follow manufacturer s instructions enclosed with the thermostat for general installation procedures Color coded insulated wires 18 AWG should be used to connect the thermostat to...

Page 10: ...wer up to unit there is a 3 minute time delay to the compressor contactor R to Y Any 24V interrupt R C to the defrost control will initiate the 3 minute delay to the contactor Cooling When the thermos...

Page 11: ...1P Extruded Aluminum Louver Kit 33 Height ALVRAL 2 Extruded Aluminum Louver Kit Custom Color 33 Height ALVRAL 2P Extruded Aluminum Louver Kit 45 Height ALVRAL 3 Extruded Aluminum Louver Kit Custom Co...

Page 12: ...Louver ASLEEVE8 2 8 32 3 4 16 16 5 8 32 7 8 for 45 Louver ASLEEVE8 5 8 45 16 16 5 8 45 1 8 10 Wall Sleeve Kit for 29 Louver ASLEEVE10 1 10 29 16 16 5 8 29 1 8 for 33 Louver ASLEEVE10 2 10 32 3 4 16 16...

Page 13: ...507860 01 Issue 1927 Page 13 of 14 Figure 9 Connection Diagram MCE Without Electric Heater 538012 01 Wiring Diagrams...

Page 14: ...Page 14 of 14 507860 01 Issue 1927 Figure 10 Connection Diagram MCE With Factory Installed Electric Heater 538013 01...

Reviews: