Magic-pac HWC8 V Series Installation Instructions Manual Download Page 9

507388-03

Issue 2127

Page 9 of 19

Adjustments – Heating Section

Temperature Rise

At time of installation, the temperature rise must be 

adjusted to be within the range specified on the unit rating 

plate. See Table 2. Select a lower blower speed to increase 

rise. Select a higher blower speed to reduce rise.

Pressure Regulator

The gas input must not exceed the figures shown on the 

rating plate. The unit is equipped for rated inputs with 

manifold pressures of: 3.5” W.C. for natural gas and 10.5” 

W.C. for propane.

The manifold pressure can be measured by removing the 

pipe plug in the automatic gas valve. Connect a water 

manometer and measure the pressure. See Figure 9.

Only small variations in gas input may be made by adjusting 

the regulator. 

In  no  case  should  the  final  manifold 

pressure vary more than 0.3” W.C. for natural gas or 

0.7” W.C. for propane.

To adjust the regulator, turn the adjusting screw on the 

regulator clockwise to increase pressure and input or 

counterclockwise to decrease pressure and input. See 

Figure 9.

For natural gas installations, check the burner rate by 

observing the gas meter (making sure that all other gas 

appliances  are  turned  off).  The  test  hand  on  the  meter 

should be timed for at least one revolution. Note the 

number of seconds for one revolution.

BTU/HR 

Input

=

Cubic Feet per 

Revolution

x 3600 x Heating 

Value

# Seconds per 

Revolution

Adjustments – Cooling Section (HWC models)

No adjustments are required or should be attempted 

regarding any of the components of the cooling chassis. 

The chassis should be checked to see that none of the 

wiring is loose or missing.

Cooling chassis is charged with R410A refrigerant.

Blower

The unit contains a direct-drive, multispeed blower. The 

proper speeds have been preset at the factory for heating 

and cooling. Refer to the wiring diagram or Table 2 for 

recommended heating/cooling speeds for specific models. 

Direct-drive blower motors are permanently lubricated and 

do not require oiling.

Limit Control

A fixed temperature limit control is provided which will shut 

off the gas to the main burners if the unit is overheated for 

any reason. The control must not be adjusted or relocated.

High Altitude Adjustments (U.S. Installations)

Ratings shown on the rating plate are for elevations up to 

2000 feet. For elevations above 2000 feet, ratings should 

be reduced at a rate of 4% for each 1000’ above sea level. 

Refer to the National Fuel Gas Code Z223.1 (latest edition) 

for further explanation.

Installation and Operation in Extremely Cold 

Weather Areas

In areas where extremely cold (below – 20°F) outdoor 

temperatures can be expected, some additional installation 

and operating precautions should be taken. The following 

precautions are taken to prevent possible vent system 

ice blockage that could result in safety shutdown of the 

burners:

1.  Adjust to the highest achievable temperature rise 

within  the  rise  and  static  pressure  ranges  specified 

on  the  rating  plate.  Depending  on  specific  model,  it 

may be possible to change to a lower heating blower 

speed tap to get a higher temperature rise. This also 

increases comfort.

2.  Make sure there are no leaks of outside air into the 

return air system.

3.  Keep the outside louver grille as free as possible of 

any ice that may form and obstruct the flue outlet.

Summary of Contents for HWC8 V Series

Page 1: ...ombustible materials near the furnace or warm air ducts The material may ignite by spontaneous combustion creating a fire hazard WARNING These units are not approved for mobile home applications Such...

Page 2: ...03 Issue 2127 22 27 7 8 29 7 16 13 3 8 43 3 16 16 1 6 1 8 1 Supply Return Low Voltage Supply Line Voltage Box 1 3 4 8 2 3 4 1 1 2 2 7 8 18 1 4 2 2 1 2 Gas Inlet Condensate Drain HWC9 Only Return Supp...

Page 3: ...ile or other combustible material other than wood flooring The grille side of the unit may be flush with or extend beyond the face of the exterior wall but should not be recessed more than 2 from the...

Page 4: ...When properly nested the angle on top of the unit should line up with the top flange of the sleeve and should almost touch Fasten the unit to the sleeve with five screws furnished with the sleeve The...

Page 5: ...could cause an unsafe condition 3 Insofar as is practical close all building doors and windows between the space in which the appliances remaining connected to the common venting system are located an...

Page 6: ...losing the individual manual shutoff valve during any pressure testing of gas supply piping system at test pressures equal to or less than 1 2 psig or 14 W C If the piping system is to be tested at pr...

Page 7: ...the unit Refer to the rating plate located on the unit for proper fuse or breaker size Make sure the unit is electrically grounded in accordance with local codes or in the absence of local codes with...

Page 8: ...in the return duct work or elsewhere the permanent filter can be used or replaced with a disposable filter If a disposable filter is used refer to the information provided in Table 1 when sizing the...

Page 9: ...e checked to see that none of the wiring is loose or missing Cooling chassis is charged with R410A refrigerant Blower The unit contains a direct drive multispeed blower The proper speeds have been pre...

Page 10: ...6012P18A 45 75 60 TAP 1 HEAT 208 or 230 630 71 600 N A 570 N A 550 N A TAP 2 HEAT 208 or 230 770 58 740 60 715 62 690 64 TAP 3 HEAT 208 or 230 885 50 855 52 830 54 810 55 TAP 4 COOL 208 or 230 560 540...

Page 11: ...ustment Screw Under Cap Gas Manifold Pressure Test Tap Model Rise Range F Mid Rise F Indoor Blower Speed Unit Voltage V 0 1 w c 0 2 w c 0 3 w c 0 4 w c SCFM Temp Rise F SCFM Temp Rise F SCFM Temp Rise...

Page 12: ...ee times Should the burners fail to ignite within the three trials for ignition the ignition control will lock out for 1 hour before beginning another ignition cycle To reset the control turn the ther...

Page 13: ...osen these screws to remove control board mounting bracket Ignition Control Board Remove these screws to remove Burner Assembly Igniter Combustion Inducer Gas Valve Primary Limit Mounted to Vest panel...

Page 14: ...Verify proper operation after servicing WARNING Refer to Figure 8 for heating compartment component layout It is recommended that the furnace be inspected annually by a qualified service person Burner...

Page 15: ...ew and pull the igniter out of the burner assembly 4 For reassembly follow the above steps in reverse order Rollout Switch If for any reason the heat exchanger becomes blocked the temperature sensitiv...

Page 16: ...from the flue collector box end 6 Brush out the inside of the flue collector box 7 Brush out the inside of the flue tube extension 8 If soot buildup is excessive clean the combustion inducer wheel an...

Page 17: ...507388 03 Issue 2127 Page 17 of 19 Figure 10 Wiring Diagram HWC 12 18 Wiring Diagrams...

Page 18: ...Page 18 of 19 507388 03 Issue 2127 Figure 11 Wiring Diagram HWC 24...

Page 19: ...507388 03 Issue 2127 Page 19 of 19 Figure 12 Wiring Diagram HWC 30...

Reviews: