Magic-pac HWC8 V Series Installation Instructions Manual Download Page 16

Page 16 of 19

507388-03

Issue 2127

Burner Orifices

Orifices  are  threaded  into  the  gas  manifold.  To  remove 

them:

1.  Remove the burner & manifold assembly as described 

previously.

2.  Remove the four screws securing the gas manifold to 

the burner assembly.

3. 

Remove the orifices by unscrewing them. Do not use 

any pipe thread sealant during reassembly.

4.  For reassembly, follow the above steps in reverse 

order.

Combustion Inducer

The combustion inducer can be removed for inspection, 

replacement,  or  to  access  the  heat  exchanger  and  flue 

tube extension for cleaning. To remove the combustion 

inducer:

1.  Remove the control board mounting bracket as 

described previously.

2.  Disconnect the black inducer motor leads.
3.  Disconnect the inducer prover switch tubing at the 

switch.

4.  Remove the two screws on the combustion inducer 

plate.

5.  Pull the combustion inducer and plate toward you until 

it is free of the dilution air box that supports it. Lower 

the inducer and plate and rotate to pull the assembly 

out of the compartment.

6. 

The flue tube extension can be cleaned if necessary. 

Leave it in place; do not remove it from the unit.

7.  For reassembly, follow the above steps in reverse 

order.

Heat Exchanger

The heat exchanger should be inspected periodically and 

cleaned if necessary. When cleaning use a stiff brush with 

a wire handle to remove scale and soot. To access the 

heat exchanger tubes for cleaning:

1.  Remove the burner & manifold assembly as described 

previously.

2.  Remove the combustion inducer as described 

previously.

3.  Remove the four screws securing the dilution air box 

to the flue collector box.

4.  Remove the nine or twelve screws (depending on 

model) securing the flue collector box to the vest panel.

5.  Using the wire brush, brush out the inside of each heat 

exchanger tube from the burner assembly end and 

from the flue collector box end.

6. 

Brush out the inside of the flue collector box.

7. 

Brush out the inside of the flue tube extension.

8.  If soot buildup is excessive, clean the combustion 

inducer wheel and housing.

9.  When brushing is complete, blow all brushed areas 

with air. Vacuum as needed.

10.  For reassembly, follow the above steps in reverse 

order.

Cooling Chassis

The refrigeration system contained in the cooling chassis 

normally requires no maintenance since it is a closed, 

self-contained system. System is charged with R410A 

refrigerant. Periodic maintenance is limited to:

• 

Cleaning the air filter. Follow directions noted on the 

filter and label attached to the access panel.

•  Cleaning the condenser coil if covered with any foreign 

material, lint, leaves, or other obstructions.

If servicing or major repairs are required, the complete 

chassis can be removed from the unit. To remove the 

chassis:

1. 

Shut off the main power supply.

2. 

Remove filter access panel and panel covering cooling 

controls.

3.  Remove drain hose from the drain pan.
4.  Disconnect the plug-in electrical connections. 
5.  Disconnect two power leads at contactor (leads come 

from grommet in unit partition).

6.  Remove screws from panel directly in front of blower 

and remove panel. Also remove additional screws 

located near top edge of control panel.

7.  Drape power wires and wire harnesses out of cabinet 

and tape to upper panel.

8.  Slide out the chassis, being careful not to damage any 

seals or parts. Particular care should be taken to insure 

wiring is not damaged during removal/reinstallation 

process. 

NOTE: 

Tubing is not to be used as a handle.

To reinstall the chassis, reverse the procedure outlined 

above. Be sure that the chassis is inserted as far back as 

it will go before replacing the screws. Side flanges on the 

chassis must be engaged with sealing strips on the unit 

sides to prevent water and air leakage. Reconnect the 

wire harness, reconnect the power leads, and replace both 

access panels before turning on the main electrical power. 

Summary of Contents for HWC8 V Series

Page 1: ...ombustible materials near the furnace or warm air ducts The material may ignite by spontaneous combustion creating a fire hazard WARNING These units are not approved for mobile home applications Such...

Page 2: ...03 Issue 2127 22 27 7 8 29 7 16 13 3 8 43 3 16 16 1 6 1 8 1 Supply Return Low Voltage Supply Line Voltage Box 1 3 4 8 2 3 4 1 1 2 2 7 8 18 1 4 2 2 1 2 Gas Inlet Condensate Drain HWC9 Only Return Supp...

Page 3: ...ile or other combustible material other than wood flooring The grille side of the unit may be flush with or extend beyond the face of the exterior wall but should not be recessed more than 2 from the...

Page 4: ...When properly nested the angle on top of the unit should line up with the top flange of the sleeve and should almost touch Fasten the unit to the sleeve with five screws furnished with the sleeve The...

Page 5: ...could cause an unsafe condition 3 Insofar as is practical close all building doors and windows between the space in which the appliances remaining connected to the common venting system are located an...

Page 6: ...losing the individual manual shutoff valve during any pressure testing of gas supply piping system at test pressures equal to or less than 1 2 psig or 14 W C If the piping system is to be tested at pr...

Page 7: ...the unit Refer to the rating plate located on the unit for proper fuse or breaker size Make sure the unit is electrically grounded in accordance with local codes or in the absence of local codes with...

Page 8: ...in the return duct work or elsewhere the permanent filter can be used or replaced with a disposable filter If a disposable filter is used refer to the information provided in Table 1 when sizing the...

Page 9: ...e checked to see that none of the wiring is loose or missing Cooling chassis is charged with R410A refrigerant Blower The unit contains a direct drive multispeed blower The proper speeds have been pre...

Page 10: ...6012P18A 45 75 60 TAP 1 HEAT 208 or 230 630 71 600 N A 570 N A 550 N A TAP 2 HEAT 208 or 230 770 58 740 60 715 62 690 64 TAP 3 HEAT 208 or 230 885 50 855 52 830 54 810 55 TAP 4 COOL 208 or 230 560 540...

Page 11: ...ustment Screw Under Cap Gas Manifold Pressure Test Tap Model Rise Range F Mid Rise F Indoor Blower Speed Unit Voltage V 0 1 w c 0 2 w c 0 3 w c 0 4 w c SCFM Temp Rise F SCFM Temp Rise F SCFM Temp Rise...

Page 12: ...ee times Should the burners fail to ignite within the three trials for ignition the ignition control will lock out for 1 hour before beginning another ignition cycle To reset the control turn the ther...

Page 13: ...osen these screws to remove control board mounting bracket Ignition Control Board Remove these screws to remove Burner Assembly Igniter Combustion Inducer Gas Valve Primary Limit Mounted to Vest panel...

Page 14: ...Verify proper operation after servicing WARNING Refer to Figure 8 for heating compartment component layout It is recommended that the furnace be inspected annually by a qualified service person Burner...

Page 15: ...ew and pull the igniter out of the burner assembly 4 For reassembly follow the above steps in reverse order Rollout Switch If for any reason the heat exchanger becomes blocked the temperature sensitiv...

Page 16: ...from the flue collector box end 6 Brush out the inside of the flue collector box 7 Brush out the inside of the flue tube extension 8 If soot buildup is excessive clean the combustion inducer wheel an...

Page 17: ...507388 03 Issue 2127 Page 17 of 19 Figure 10 Wiring Diagram HWC 12 18 Wiring Diagrams...

Page 18: ...Page 18 of 19 507388 03 Issue 2127 Figure 11 Wiring Diagram HWC 24...

Page 19: ...507388 03 Issue 2127 Page 19 of 19 Figure 12 Wiring Diagram HWC 30...

Reviews: