3.2

 

Examples of installation 

 

 

Fig. 2: Avoid accumulation of air 

 

 

 

Fig. 3: Mount a valve or a regulator after the flow meter 

 

Note:

 During installation it must be ensured that no water 

can enter the calculator. 

3.3

 

Installation for cooling metering 

 

Note: 

It  is  recommended  that  the  flow  meter  is  installed 

on the hot side.  

When installing as a cold meter it is essential that the black cover 
on the measuring tube is pointed to the side or downwards in order 
to avoid problems with condensation forming.  
Fit  the  calculator  separate  to  the  volume  measurement  tube,  e.g. 
on  the  wall.  Make  a  loop  downwards  in  order  to  prevent 
condensation running along the connected lines into the calculator.  

 

 

 

Transducer cover 

Fig. 4: Recommended installation position for cooling metering 

4

 

Calculator 

The ambient temperature of the calculator must not exceed 55 °C. 
Avoid  direct  sunlight.  For  water  temperatures  between  10 °C  and 
90 °C you can fit the calculator on the volume measurement unit or 
on the wall. 

4.1

 

Aligning the calculator 

Proceed as follows to align the calculator: 
1.

 

Pull the calculator off the volume measurement unit. 

2.

 

Turn the calculator to the left or right through 90° or 180° as 
required. 

3.

 

Push the calculator onto the adapter plate in this position until 
it engages. 

 

Fig. 5: Calculator installation position 

4.2

 

Wall fitting (split fitting) 

Fit  the  calculator  to  the  wall  at  water  temperatures  below  10 °C 
and above 90 °C.  
For wall mounting proceed as follows: 

 

Pull the calculator off the adapter plate. 

 

Unscrew the adapter plate from the volume measurement unit. 

 

Fit the adapter plate to the wall. 

 

Push the calculator onto the adapter plate. 

 

 

Fig. 6: Adapter plate and wall fitting 

5

 

Power supply 

The flow meter is equipped with a long life battery for ten years of 
operation. You can take the operating time from the dial plate. 

 

Warning:

 Do not open the batteries. Do not bring battery into 

contact  with  water  or  expose  to  temperatures  above  80 °C. 
Dispose of used batteries at suitable collection points. 

 

Note:

  Only  batteries  approved  by  the  manufacturer  may  be 

installed. 

6

 

Interfaces 

The flow meter is equipped with an optical interface in accordance 
with EN 62056-21 as standard.  
In addition, the flow meter is equipped with a pulse output and is 
delivered  with  a  2m  two  wire  cable.  The  connecting  cable  can  be 
lengthened  with  a  cable  2 x 0.75  mm

2

.  A  distributing  box  is 

recommended. 

7

 

Activation of the calculator 

For activation proceed as follows: 

 

Open the slide valves slowly. 

 

Check the system for leak-tightness and bleed air out carefully. 

After more than 100 sec. the flow meter begins to work.  
If the operating limit is exceeded and the flow rate is positive, 
volume pulses are generated according to the pulse parameter 
settings. 

 

Check the measured value flow or the volume of progress on 
the connected calculator for plausibility. 

 

Vent the system until the flow rate value on the calculator is 
stable. Check the output. 

8

 

Functional details 

The  operating  hours  are  counted  from  the  first  connection  of  the 
power supply.  
Missing hours are summated if there is an error and the flow meter 
is thus unable to take a measurement. 
Volume  readings,  maximum  flow  rates  and  missing  hours  are 
stored monthly for 36 months. 
The device number and the firmware version number are issued by 
the manufacturer. 
 
 
 
 

 