2.0 - TECHNICAL DATA
• Use
: non-aggressive gases of the three families (dry gases)
• Ambient temperature (TS)
: -20 ÷ +60 °C
• Supply voltages (see table 2)
: 24 Vdc - 24 V/50 Hz - 110 V/50-60 Hz - 230 V/50-60 Hz*
• Supply voltage tolerance
: -15% ... +10%
• Electric wiring
: electric cable l=3 metres with wire terminals
• No. cycles/hour**
:
~
90 (ON time 10s - OFF time 30s)
• Absorbed power
: see table 2
• Maximum operating pressure
DN 32 - DN 40 - DN 50
: 3 bar or 6 bar (see product label)
DN 65 - DN 80 - DN 100 - DN 125 - DN 150
: 500 mbar,1 bar, 3 bar or 6 bar (see product label)
• Opening time
: <1 s
• Closing time
: <1 s
• Protection rating
: IP65
• Coil protection mode
: II 3G Ex nC IIC T4 Gc X - II 3D Ex tc IIIC T135°C Dc X
• Class
: A
• Mechanical resistance
: Group 2
• Rp Threaded connections
: (DN 32 - DN 40 - DN 50) according to EN 10226
• Flanged connections to be coupled with PN 16 flanges : (DN 32 - DN 40 - DN 50 - DN 65 - DN 80 - DN 100 - DN 125 - DN 150)
ISO 7005 / EN 1092-1
• NPT threaded or ANSI 150 flanged connections : on request
• In compliance with (see also table on page 21) : Regulation (EU) 2016/426 (Appliances burning gaseous fuels)
EN 60079-0-7-14-15-31 - ATEX Directive 2014/34/EU
PED Directive 2014/68/EU (versions with P.max = 1-3-6 bar)
EMCDirective 2014/30/EU - LVD Directive 2014/35/EU
RoHS II Directive 2011/65/EU
* Only single-phase, the device does not work if powered with three-phase voltage.
** For cycles/hours with ON/OFF times different from those indicated, contact our technical office
2.1 - MODEL IDENTIFICATION
XV-1 :
Fast opening P. max 0.5 or 1 bar (see product label)
ATEX 3G - 3D
XV-3 :
Fast opening P. max 3 bar
ATEX 3G - 3D
XV-6 :
Fast opening P. max 6 bar
ATEX 3G - 3D
XVF-1 :
Fast o flow adjustment P. max 0.5 or 1 bar (see product label) ATEX 3G - 3D
XVF-3 :
Fast o flow adjustment P. max 3 bar
ATEX 3G - 3D
XVF-6 :
Fast o flow adjustment P. max 6 bar
ATEX 3G - 3D
2.2 - SIL LEVEL
For models in compliance with Regulation (EU) 2016/426 (see table in 9.0),
the SIL level of the stand-alone solenoid valve
is SIL 2; when two solenoids are installed in series and the relative leak test (Valve Proving System), certified according to
EN 1643, the achieved level is SIL 3, as set forth in EN 676:2008. The solenoid valve has PL d level. For further data refer
to the SIL LEVEL table (table 2).
3.0 - COMMISSIONING THE DEVICE
3.1 - OPERATIONS PRIOR TO INSTALLATION
All installation operations must be carried out in the absence of an explosive atmosphere.
• It is necessary to close the gas upstream of the valve prior to installation;
• Make sure that the line pressure
DOES NOT EXCEED
the maximum pressure declared on the product label;
• Any protective caps (if any) must be removed prior to installation;