12
ES
FR
EN
IT
M90W
Madas Technical Manual
- 9|9.3 - REV. 1 of 6
th
Apr 2023
9.0 - WARRANTY
The warranty conditions agreed with the manufacturer at the time of the supply apply.
Damage caused by:
• Improper use of the device;
• Failure to observe the requirements described in this document;
• Failure to observe the regulations pertaining to installation;
• Tampering, modification and use of non-original spare parts;
is not covered by the rights of the warranty or compensation for damage.
The warranty also excludes maintenance work, the assembly of devices of other manufacturers, making changes to the device
and natural wear.
10.0 - RATING PLATE DATA
The rating plate data (see example provided here) includes the following:
• Manufacturer’s name/logo and address (possible distributor name/logo)
• Mod.:
= device name/model
• Wall installation = Installation position
• IP....
= Protection rating
• 230V....
= Power supply voltage, frequency (if Vac), followed by the electrical absorption
• TS
= Temperature range within which product operation is guaranteed
• year
= Year of manufacture
• Lot
= Product serial number (see explanation below)
• U2312
= Lot issued in year 2023 in the 12th week
• 7634
= progressive job order number for the indicated year
• 00001
= progressive number referring to the quantity of the lot
•
= Disposal in accordance with WEEE directive 2012/19/EU
Mod.: M90W
Wall installation
IP65 - 230 V/50-60 Hz - 3VA TS: -20+60 °C
year: 2023 Lot:U2312 7634/00001
LED
Status
Description
Action
GREEN
Fixed
Power supply ON - Operation
--
Slow flashing (0.5 Hz)
Warm-up (about 15s)
--
Fast flashing (2.Hz)
Maintenance Required
Contact Customer Support
BLUE
Flashing
Eprom Fail: setting data storage
problem
Press the reset button and restart the
device. If the fault persists, the device
must be replaced.
Flashing
Sensor Fault: Accelerometer
damaged
Press the reset button and restart the
device. If the fault persists, the device
must be replaced.
Flashing
Tilt Detected: The device is
positioned at an angle between 5°
and 10° with respect to the vertical
Check the installation position of the
device (Para. ..) Press the reset button and
restart the device. If the fault persists, the
device must be replaced.
RED
Fixed
The system has gone into alarm
Check the conditions of the system and the
status of the connected devices. Restore
normal safety conditions, press the reset
button and restart the device.
11.0 - LED INDICATOR