Madas Technical Manual

 - 9|9.3 - REV. 0 of 1

th

 May 2018

  4.0  ELECTRICAL CONNECTIONS (see diagrams fig. 3 and 4)

They must be carried out with the system stopped and 

NOT

 electrically powered. 

• Prior to carrying out any electrical wiring operations, make sure that the mains voltage matches the supply voltage indicated 

on the product label.

•  

NOTE:

 The wiring operations must be carried out ensuring the product's IP65 protection rating;

• Undo the fixing screws (

8

) and remove the cover (

9

).

• Connect the power supply to the power terminals and the earth cable to the 

  terminal using the appropriate cable 

terminals. The 12 V and 24 V versions can be powered both with direct current and with alternating current. The connection 
terminals are not polarised.

•  For the electrical connection, use the cable indicated in the valve instruction sheet: 

•  Relay for alarm/failure output max 0.5A resistive: 

 

N.O.

  : Normally open contact

 

C

  : Common contact

N.C.

 : Normally closed contact

•  Normally closed contact - 

EXT IN

 

      

 

 

 

 

 

 

Contact to be used for connection with gas leak detector or for emergency closure button. The contact is dry and must not 
be powered.

•  After making the connection put the cover (

9

) back in its original position and fasten it using the relevant screws (

8

) making 

sure that the gasket (

10

) is inside the groove.

  

5.0  DIP SWITCH (6)

MADAS

®

 seismic sensors are suitable for use with normally open (N.O.) or normally closed (N.C.) valves.

The type of solenoid valve is selected via the internal DIP switch

DIP switch no. 1: (solenoid valve type selection):

ON   =  N.C. solenoid valves
OFF  =  N.O. solenoid valves

DIP switch no. 2 (sensitivity selection):

A2  

=  normal

A1  

=  increased sensitivity

EXAMPLES

•  Configuration for N.C. solenoid valve (DIP Switch 1 -> ON)  

 

 

 

 

 

and normal sensitivity (DIP Switch 2 -> A2)

•  Configuration for N.O. solenoid valve (DIP Switch 1 -> OFF)  

 

 

 

 

 

and normal sensitivity (DIP Switch 2 -> A2)

ON

N.C.

A2

N.O.

A1

1

2

ON

N.C.

A2

N.O.

A1

1

2