2.0 - TECHNICAL DATA
• Use
: non-aggressive gases of the three families (dry gases)
• Ambient temperature (TS)
: -20 ÷ +60 °C
• Supply voltages (see table 2)
: 12 Vdc - 12 V/50 Hz - 24 Vdc - 24 V/50 Hz - 110 V/50-60 Hz - 230 V/50-60 Hz*
• Power supply tolerance
: -15% ... +10%
• Electric wiring
: cable gland M20x1.5
• No. cycles/hour
: see table 2a - 2b - 2c
• Absorbed power
: see table 2a - 2b - 2c
• Maximum operating pressure
: 200 mbar or 360 mbar (see product label)
• Opening time
: <1 s
• Closing time
: < 1 s
• Protection rating
: IP65
• Class
: A
• Mechanical resistance
: Group 2
• Rp Threaded connections
: (DN 15 - DN 20 - DN 25 - DN 32 - DN 40 - DN 50) according to EN 10226
• Flanged connections to be coupled with PN 16 flanges : (DN 32 - DN 40 - DN 50) ISO 7005 / EN 1092-1
• NPT threaded or ANSI 150 flanged connections : on request
• Filter element
: 1 mm wire mesh
• In compliance with
: Regulation (EU) 2016/426 (Appliances burning gaseous fuels)
Directive EMC 2014/30/EU - Directive LVD 2014/35/EU
Directive RoHS II 2011/65/EU