INSTALLATION

The  solenoid  valve  is  in  conformity  with 

the  Directive  94/9/CE  (said  Directive  ATEX 

100 a) as device of group II, category 3G 

and  as  device  of  group  II,  category  3D; 

for this reason it is suitable to be installed 

in  the  zones  2  and  22  as  classifi ed  in  the 

attachment I to the Directive 99/92/EC. The 

solenoid  valve  is  not  suitable  to  be  used 

in zones 1 and 21 and, all the more so, in 

zones 0 and 20 as classifi ed in the already 

said Directive 99/92/EC. 

To  determine  the  qualifi cation  and  the 

extension of the dangerous zones, see the 

norm EN 60079-10.

The  device,  if  installed  and  serviced 

respecting  all  the  conditions  and  the 

technical  instructions  of  this  document,  is 

not source of specifi c dangers: in particular, 

during the normal working, is not forecast, 

by  the  solenoid  valve,  the  emission  in  the 

atmosphere  of  infl ammable  substance  in 

way to cause an explosive atmosphere.

WARNING:  all  installation/wiring/ 

maintenance work must be carried out 

by skilled staff.

•  The  gas  supply  must  be  shut  off  before 

installation.

•  Check that the line pressure DOES NOT 

EXCEED the maximum pressure stated 

on the product label.

It  is  always  important  to  read 

carefully  the  instruction  sheet  of 

each product.

 Overall dimensions in mm 

  Flanged 

connections F

P. max 

(mbar) 

A

B

EVP... 

EVPC...

70 

137 

05 

185

200 / 360 

70 

137 

150 

205 

185

360 mbar 

90 

157 

172 

225 

205

EVPC DN 25 

200 / 360 

142 

170 

195 

250 

230

EVP DN 25 

360 mbar 

162 

190 

205 

262 

242

200 mbar 

160 

185 

200 

262 

240

360 mbar 

160 

210 

210 

275 

253

200 mbar 

160 

210 

225 

290 

267

360 mbar 

160 

210 

225 

290 

267

EVPC DN 32 - DN 40 - DN 50 

200 / 360 

230 

237 

252 

295 

269

EVP DN 50 

360 mbar 

160 

235 

235 

300 

278

EVP DN 32 - DN 40 - DN 50 

360 mbar 

230 

261 

261 

326 

304

EVP DN 65 

360 mbar 

290 

321 

321 

480 

432

EVP DN 80 

360 mbar 

310 

328 

328 

486 

439

EVP DN 100 

360 mbar 

350 

389 

389 

547 

500

EVP DN 125 

360 mbar 

480 

570 

570 

728 

681

EVP DN 150 

360 mbar 

480 

570 

570 

728 

681

EVP DN 200 

360 mbar 

600 

680 

680 

-

Summary of Contents for EVP/NC

Page 1: ...ch thermostat etc They can be equipped with a flow regulator and adjustable slow opening kit EC certified according to EN 161 In conformity with the 2009 142 EC Directive Gas Directive In conformity w...

Page 2: ...Environment temperature 15 60 C Max superficial temperature 85 C Protection degree IP65 Class DN 15 DN 150 A DN 200 B Group 2 Closing time 1 s Opening time 1 s Coils poliammidic resin encapsulated wi...

Page 3: ...32 003 110 V 50 Hz EVP05 002 EVP32 002 230 V 50 60 Hz EVP05 008 EVP32 008 EVP NC DN 40 12 Vdc EVP06 001 EVP40 001 24 Vdc EVP06 005 EVP40 005 24 V 50 Hz EVP06 003 EVP40 003 110 V 50 Hz EVP06 002 EVP40...

Page 4: ...spring 4 Body valve 5 Obturator 6 Seal washer 7 G 1 4 cap 8 Filter 9 Fixing screws 10 Cover or bottom 11 Electrical coil 12 Coil fixing nut or screw 13 Flow calibration screw EVPF version 14 Bottom o...

Page 5: ...Capacity diagram EVP NC P max 360 mbar 1 metano 2 aria 3 gas di citt 4 gpl 1 methane 2 air 3 town gas 4 lpg e e ne o...

Page 6: ...cause an explosive atmosphere WARNING all installation wiring maintenance work must be carried out by skilled staff The gas supply must be shut off before installation Check that the line pressure DO...

Page 7: ...on the screw 16 This screw has not limit the opening speed increases gradually screwing clockwise the screw 16 To regulate the rapide stroke operate on the screw 15 Screwing counterclockwise till the...

Page 8: ...ntrol rete pipe r seau red utenza user utilisateur punto de consumo rete pipe r seau red EXAMPLE OF INSTALLATION 2 1 Gas filter type FM 2 Over pressure slam shut off valve type MVB1 MAX 3 Gas pressure...

Page 9: ...seefig 3 4 5 6 unscrew the nut 12 or the slow opening kit 17 and remove the coil 11 Unscrew the fixing screws 9 and with care take the cover 10 off the body 4 of the valve then control the obturator...

Page 10: ...12V RAC ES CN 2110 RADDRIZZATORE Energy Saving RECTIFIER Energy Saving 24 Vdc BO 0417 BO 0417 24V RAC ES CN 2100 NORMALE Energy Saving NORMAL Energy Saving 24 V 50 Hz BO 0417 BO 0417 24V RAC ES CN 21...

Page 11: ...rgy Saving DN 65 DN 80 P max 360 mbar 24 Vdc BO 1110 24 Vdc DN 65 80 CN 2000 NORMALE NORMAL 24 V 50 Hz BO 1115 24 Vac DN 65 80 CN 2010 RADDRIZZATORE Energy Saving RECTIFIER Energy Saving 110 V 50 60 H...

Reviews: