Macurco RD-24 Installation & Operation Manual Download Page 14

 
Macurco

TM

 Macurco RD-24 Manual 

 

 

REV 

 1.0.0 

[34-8708-4770-1] 

14 

|

 

P a g e

 

 

Figure 4-6 

 Zone 4-20mA Output Mode Menu 

4.3.1.3

 

Configure 4-20mA Input or Analog Input 

Analog Inputs read gas sensors connected to RD-24 and will work the same as digital sensors readings, which 
are  the  sensors  with  MRS-485  connected  to  DVP-1200  through  the  RS-485  network  using  the  Modbus 
protocol. 

 

Sensors connected to RD-24 should be displayed to the 

user as “RD

-

24 #address.#analog_input”.

 

#analog_input has a range from 1 to 16, as each RD-24 can have up to 4 expansion boards connected, and 
each analog input expansion board has 4 analog inputs. 
 
DVP-1200 has the capability to connect to up to 192 sensors. By default, DVP-1200 is configured to connect 
to 192 digital sensors. 
 
Each RD-24 that is discovered by DVP-1200 and has analog inputs will cause the controller to internally map 
the RD-24 analog inputs to one of the 192 sensors and automatically adjust the limit of digital sensors that 
can be connected to the controller. 
 
The sensor mapping will be done from top to bottom. It grows from sensor #192 all the way to 128.  
 
By  default,  DVP-1200  allocates  space  to  connect  to  192  digital  sensors.  If  an  RD-24  with  analog  inputs  is 
connected to the controller, DVP-1200 will automatically allocate sensor addresses from the list of 192 in the 
following order: 

-

 

The first RD-24 connected to DVP-1200 will occupy sensor addresses 177 thru 192 in order and as needed. 
For example: Slot 1, input 1 will occupy address 177 and Slot 4, input 4 will occupy address 192. 

-

 

The second RD-24 connected to DVP-1200 will occupy sensor addresses 161 thru 176 in order and as 
needed. 

-

 

The third RD-24 connected to DVP-1200 will occupy sensor addresses 145 thru 160 in order and as needed 

-

 

The fourth RD-24 connected to DVP-1200 will occupy sensor addresses 129 thru 144 in order and as needed 

NOTE

: The addresses have been allocated to the exact locations as described 

 they do not change based on  

the 

number of analog input expansion boards installed into any number of RD-24 units. For a full list of  
 

addresses and slot designations, see “Remote Device I/O Chart” below.

 

 

 

 

Summary of Contents for RD-24

Page 1: ...IMPORTANT Keep these user instructions for reference Macurco RD 24 Modbus Remote Driver Installation Operation Manual...

Page 2: ...ion Connection 6 3 2 4 Input Output Connections 7 3 2 5 Expansion Board Connections 8 4 Operations 9 4 1 Power up 9 4 2 Initial Operating Mode 9 4 2 1 RD 24 Settings 9 4 2 2 Programming Mode 9 4 2 3 C...

Page 3: ...analog outputs or analog inputs Using Modbus communication you can control multiple I O based on the application The RD 24 requires 24VDC to operate and can be used to engage or disengage other equipm...

Page 4: ...mmunication Slots 1 4 Baud Rate 4800 9600 19200 default 98400 57600 115200 bps Enclosure NEMA 4X Warranty Two year limited warranty 3 Installation Instructions 3 1 Location Mounting Macurco RD 24 is s...

Page 5: ...button of the connector use flat headed screwdriver insert bare wire into respective wire cavity of the connector and release the white button Ensure that the wire cannot be easily pulled from the co...

Page 6: ...e twisted pair providing a pair for signal A B common COM and shield ground SHD connection NOTE Running the RS 485 cable adjacent to or in the same conduit with high voltage wires is not recommended a...

Page 7: ...7 P a g e 3 2 4 Input Output Connections Figure 3 4 RD 24 Board Diagram Macurco RD 24 Dip Switch EOL Resistor RS 485 COMMS IN OUT POWER IN OUT Expansion Board 2 SHD COM B A SHD COM B A GND GND 24V 24...

Page 8: ...ted 55mA Figure 3 5 Relay Expansion Board 3 2 5 2 Expansion Analog Output Board Expansion Analog Input Board 2 Analog Outputs Both outputs at 4mA Current 32mA Both at 20mA Current 70mA Figure 3 6 Anal...

Page 9: ...D 24 4 2 2 Programming Mode When the RD 24 is powered with address set to 254 it enters programming mode The STATUS LED will be flashing RED and GREEN alternatively every 200 milliseconds to indicate...

Page 10: ...the dip switch address to 255 and power on the RD 24 for at least 3 seconds The LED below the dip switch should blink green rapidly After at least 3 seconds power off the RD 24 Using the dip switch ch...

Page 11: ...lect DELETE RELAY from the RELAYS menu and press ENTER Input the relay number to delete and press ENTER to delete all relays assigned to the zone input 0 and press ENTER The relay s will be deleted fr...

Page 12: ...I O Chart at the end of this manual To assign 4 20mA output to a zone select 4 20MA OUTPUT from the zone configuration menu and press ENTER Then select OUTPUT NUMBER and press ENTER Figure 4 4 Zone 4...

Page 13: ...and NO2 sensor reading is 10 0ppm which corresponds to 12mA then the 4 20mA or Analog output assigned to the zone will output 12mA SCALE In this mode the 4 20mA value for all detectors added to a zon...

Page 14: ...that can be connected to the controller The sensor mapping will be done from top to bottom It grows from sensor 192 all the way to 128 By default DVP 1200 allocates space to connect to 192 digital se...

Page 15: ...ement 6 Figure 3 4 RD 24 Board Diagram 7 Figure 3 5 Relay Expansion Board 8 Figure 3 6 Analog Output Expansion Board 8 Figure 3 7 Analog Input Expansion Board 8 Table 4 1 Baud Rate Configuration 9 Tab...

Page 16: ...00 00 00 00 00 00 00 00 00 85 4D 0x03 2 2 8 Vendor url Returns vendor url in C 01 03 00 15 00 08 55 ASCII C8 www macurco com R 01 03 10 77 77 77 2E 6D 61 63 75 72 63 6F 2E 63 6F 6D 00 A2 D6 0x03 3 0...

Page 17: ...to 3600 seconds state 0 OFF 1 ON Active 0 NO 1 YES x x bit15 bit14 bit13 bit12 bit11 bit10 bit9 bit8 bit7 bit6 bit5 bit4 bit3 bit2 bit1 bit0 Analog Output value when in fail safe condition mA x 100 0...

Page 18: ...elays or two Analog outputs Bit12 defines which output to be controlled 0 output1 1 output 2 bit11 Defines the state of relays 0 OFF and 1 ON bit10 Value to be written to the analog output DAC 0 2000...

Page 19: ...Number _______________________________ Location of Install _________________________ Installed by _________________________________ Remote Device I O Chart Relay connection Connected device Zone Conf...

Page 20: ...4 20mA output 13 4 20mA output 14 4 20mA output 15 4 20mA output 16 4 20mA output 17 4 20mA output 18 4 20mA output 19 4 20mA output 20 4 20mA output 21 4 20mA output 22 4 20mA output 23 4 20mA outpu...

Page 21: ...5 1 191 4 20mA input 16 1 192 4 20mA input 17 2 161 4 20mA input 18 2 162 4 20mA input 19 2 163 4 20mA input 20 2 164 4 20mA input 21 2 165 4 20mA input 22 2 166 4 20mA input 23 2 167 4 20mA input 24...

Page 22: ...47 3 159 4 20mA input 48 3 160 4 20mA input 49 4 129 4 20mA input 50 4 130 4 20mA input 51 4 131 4 20mA input 52 4 132 4 20mA input 53 4 133 4 20mA input 54 4 134 4 20mA input 55 4 135 4 20mA input 5...

Page 23: ...ES OF MERCHANTABILITY AND FITNESS FOR PARTICULAR PURPOSE ARE LIMITED TO A PERIOD OF TWO 2 YEARS FROM THE PURCHASE DATE Macurco shall not be liable for any incidental or consequential damages for breac...

Reviews: