Macurco DVP-120C Manual
REV – 1.0
[34-8708-4770-8 ]
49
|
P a g e
•
3
Double tap
Two beeps at five-second intervals
•
4
Triple tap
Three short beeps at ten-second intervals
•
5
Off
Horn will not sound
4.13.8.4
Alarm Strobe Signal
A l a r m S i g n a l s
S t r o b e : 1 C o n t i n .
Figure 4-82 Alarm Signals
This display example shows that the strobe will signal an alarm condition with a continuous signal. The signal
definitions are:
•
1
Continuous
(default)
•
2
Intermittent
One second on at two-second intervals
•
3
Double tap
Two beeps at five-second intervals
•
4
Triple tap
Three short beeps at ten-second intervals
•
5
Off
Strobe will not flash
4.13.8.5
Warning Signal Summary
The warning signals are in response to one or more sensors indicating gas levels at or above the sensors’ configured
warning level.
W a r n i n g S i g n a l s
B u z z
Figure 4-83 Warning Signal
This display example shows that warnings are signaled by the internal Buzzer only.
4.13.8.6
Warning Buzzer Signal
W a r n i n g S i g n a l s
B u z z : 5 O F F
Figure 4-84 Buzzer Warning Signal
This display example shows that the buzzer will not signal a warning condition. The signal definitions are:
•
1
Continuous
•
2
Intermittent
One second on at two-second intervals
•
3
Double tap
Two beeps at five-second intervals
•
4
Triple tap
Three short beeps at ten-second intervals
•
5
Off
Buzzer will not sound (default)
4.13.8.7
Warning Horn Signal
W a r n i n g S i g n a l s