background image

 

 

Macurco™ GBC 

Gas Boiler Controller 

Installation Manual 

 

 

 

Please refer to Product Operation Manual for additional product 

information and features. 

 

1.

 

Safety 

Installation must comply with recognized standards of the appropriate 

authority in the country and concerned locality. 

 

To access the complete manual, go t

www.macurco.com

 or scan the code 

below: 

 
 
 
 

 

 

 

 

 

Macurco Gas Detection 

3601 N. St. Paul Avenue 

Sioux Falls, SD 57104 

Technical Support Contact Information 

Phone: 1-844-325-3050 

Fax: 605-951-9616 

Email

[email protected]

 

Website

www.macurco.com/support/

 

General Contact Information 

Phone: 1-877-367-7891 

Fax: 605-951-9616 

Email

[email protected]

 

Web site

www.macurco.com

 

Rev – 1.2 

Issue Date: 3-3-2022 

Document No: 34-2900-0690-6 

© Aerionics 2022. All rights reserved. 

Macurco is a trademark of Aerionics, Inc. 

 

 

 

   

WARNING 

Each person using this equipment must read and understand the 
information in this User manual before use. Use of this equipment by 

untrained or unqualified persons or use that is not in accordance with this 

user manual, may adversely affect product performance. 
GBC may not function effectively below 32 °F (0 °C) or above 125 °F (51 

°C).  Using the equipment outside of this temperature range may adversely 
affect product. 
Immediately exit any environment that causes an alarm condition on the 
sensor. 
Do not disassemble unit or attempt to repair or modify any component of 
this instrument. This instrument contains no user serviceable parts, and 

substitution of components may adversely affect product performance 

and void product warranty. 
High voltage terminals (120/240 VAC) are located within this detector, 

presenting a hazard to service technicians. Only qualified technicians 
should open the detector case and service the internal circuits. Ensure 

power is de-energized from the detector relays prior to servicing the unit. 

Failure to do so may result in electrical shock. 

 

2.

 

Installation Instructions 

The Macurco GBC enclosure has 6 mounting holes and is shipped with 

mounting screws. Install the mounting screws on the four corners of the 

enclosure. The GBC should be mounted with sufficient space all round for 

access to conduit entry holes on the top and bottom side of the unit.  

Mount the unit in an appropriate space to see and hear the visual and 

audible notification and to easily access the reset button. The enclosure 

comes with one predrilled 3/4” conduit at the bottom center of enclosure 

(conduit fitting connector not included).   

Note:

 If additional entry holes are required, use caution when drilling new 

holes in the enclosure. Protect the internal components to prevent damage 

while drilling.   

 

                       

 

 

3.

 

Main Power Connection

 

Warning

: When making connections, make sure the power is off. 

The GBC offers two power input versions.  GBC-X-24: 24 VAC or VDC and 

GBC-X-120: 120 VAC. Always check the input power type marked on the top 

of the GBC Main PCBA prior to connecting power.   

 

 

There are three terminals for Power: Power, Return, Ground.   The power 

connections to the GBC should be size AWG 18 (minimum) for short runs. 

For longer runs follow recommended power wire gauge guidelines. Match 

the polarity for power connection, for the low voltage models there is a 

bridge rectifier, so it is not polarity sensitive.   

Wire Gauge

 

Maximum Run Length 

(feet) 

(meters) 

18 

500 

152 

16 

800 

244 

14 

1250 

381 

 

Note: 

Only connect the GBC to Class 2 power supply. 

Note: 

It is recommended to use an independent transformer for powering 

the unit(s) due to possible interferences from other devices on the same 

power supply. 

 

4.

 

Sensor Connections

 

There are two sensor connections on the GBC.  These connections provide 

power to the respective units and monitor the normally close circuit that 

controls the GBC.  The GBC can support up to four Macurco 6-Series gas 

detectors (350 mA max) in any combination.  The sensors must be wired in 

series for the normally closed circuit to operate correctly. 

 

Note:

 If not using Sensor Connection 2 with a gas detector a jumper wire or 

zero-ohm resistor is needed between alarm and 24 V.  A zero-ohm resistor 

is factory populated in the Sensor Connection 2, but a jumper wire can be 

used as well.   

 

5.

 

Horn/Strobe Connection

 

The horn/strobe output provides 24 VDC power to a remote horn/strobe 

(250 mA Max).  The horn/strobe will engage during the same time the 

onboard relays are set to engage based on the detector set point. 

 

6.

 

Relay Connections

 

There are four expansion slots that accept the Macurco Expansion Relay 

boards.  Each Expansion Relay board contains two SPDT, 120/240 VAC, 10 A 

Max (resistive) relays.   

Each relay can be wired to be either normally open (NO) or normally closed 

(NC) depending on the application.  

 

 