7.
Programming on detectors to work with the GBC
Settings:
CM-6/CM-12
Default
Change To:
GD-6/GD-12
Default
Change To:
Power Up Test
On
Off
On
Off
Display
On
On
On
On
Buzzer
On
On
On
On
Alarm Relay Setting
200 ppm
200 ppm
20% LEL
20% LEL
Alarm Relay
Configuration
Normally Open
(NO)
Normally
Closed (NC)
Normally
Open (NO)
Normally Closed
(NC)
Fan Relay Setting
35 ppm
50 ppm
10% LEL
10% LEL
Ran Relay Delay
3 minutes
0 minutes
3 minutes
0 minutes
Fan Relay Minimum
Runtime
0 minutes
0 minutes
0 minutes
0 minutes
Fan Relay Latching
Off
On
Off
On
Trouble Fan Setting
Off
Off
Off
Off
4-20mA
bAS (basic)
bAS (basic)
bAS (basic)
bAS (basic)
Calibration due
dIS (disabled)
dIS (disabled)
dIS
(disabled)
dIS (disabled)
Power-UP Test Setting – “PUt”
To select the Power Up Test Configuration, in normal mode, push the Next button to get to “Con” or the
Configuration menu. Then push the Enter button to enter the Con menu. Then push the Next button to get to the
second selection “PUt” or Power Up Test setting. Push Enter. If the testis “On” push Next to turn it “OFF” (flashing)
then push Enter to confirm the change (solid) and push Enter again to return to “PUt” in the Con menu. Push Next
until “End” is displayed then push Enter to get back to normal operation.
Alarm Relay Configuration – “Arc”
To select the Alarm Relay Configuration, in normal mode, push the Next button to get to “Con” or the Configuration
menu. Then push the Enter button to enter the Con menu. The sixth selection is the “Arc” or Alarm Relay
Configuration. Push Next five times to get to “Arc” then Enter. If the relay is “nO” (normally open) push Next to turn
it to “nC” (flashing) then push Enter to confirm the change (solid) and push Enter again to return to “Arc” in the Con
menu. Push Next until “End” is displayed then push Enter to get back to normal operation.
Fan Relay Setting – “FrS”
To select the Fan Relay setting, in normal mode, push the Next button to get to “Con” or the Configuration menu.
Then push the Enter button to enter the Con menu. The seventh selection is the “FrS” or Fan Relay setting. Push
Next six times to get to “FrS” then Enter.
•
CM-XX:
If the fan relay is “dIS” (disabled) push Next to change it to 15, 25, 35, 50 or 100 ppm (flashing)
then push Enter to confirm the change (solid) and push Enter again to return to “FrS” in the Con menu.
•
GD-XX:
If the fan relay is “dIS” (disabled) press Next to change it to 3, 4, 5, 6, 7, 8, 9, 10, 11, 12, 13, 14,
15, 16, 17, 18, 19 or 20% LEL (flashing) then press Enter to confirm the change (solid) and press Enter
again to return to “FrS” in the Con menu.
Push Next until “End” is displayed then push Enter to get back to normal operation.
Fan Relay Delay Setting – “Frd”
To select the Fan Relay Delay setting, in normal mode, push the Next button to get to “Con” or the Configuration
menu. Then push the Enter button to enter the Con menu. The eighth selection is the “Frd” or Fan Relay Delay. Push
Next seven times to get to “Frd” then Enter. If the delay is “0” (disabled) push Next to change it to 1, 3, 5, or 10
minutes (flashing) then push Enter to confirm the change (solid) and push Enter again to return to “Frd” in the Con
menu. Push Next until “End” is displayed then push Enter to get back to normal operation.
Fan Relay Latching Setting – “FrL”
To select the Fan Relay Latching Option, in normal mode, push the Next button to get to “Con” or the Configuration
menu. Then push the Enter button to enter the Con menu. The tenth selection is the “FrL” or Fan Relay Latching
Option. Push Next nine times to get to “FrL” then Enter. If latching is “OFF” push Next to turn it to “ON” (flashing)
then push Enter to confirm the change (solid) and push Enter again to return to “FrL” in the Con menu. Push Next
until “End” is displayed then push Enter to get back to normal operation.
Single Sensor Channel Wiring
Dual Sensor Channel Wiring