Programming on detectors to work with the GBC

 

Settings: 

CM-6/CM-12 

Default 

Change To: 

GD-6/GD-12 

Default 

Change To: 

Power Up Test 

On 

Off 

On 

Off 

Display 

On 

On 

On 

On 

Buzzer 

On 

On 

On 

On 

Alarm Relay Setting 

200 ppm 

200 ppm 

20% LEL 

20% LEL 

Alarm Relay 

Configuration 

Normally Open 

(NO) 

Normally 

Closed (NC) 

Normally 

Open (NO) 

Normally Closed 

(NC)

 

Fan Relay Setting 

35 ppm 

50 ppm 

10% LEL 

10% LEL 

Ran Relay Delay 

3 minutes 

0 minutes 

3 minutes 

0 minutes 

Fan Relay Minimum 

Runtime 

0 minutes 

0 minutes 

0 minutes 

0 minutes 

Fan Relay Latching 

Off 

On 

Off 

On 

Trouble Fan Setting 

Off 

Off 

Off 

Off 

4-20mA 

bAS (basic) 

bAS (basic) 

bAS (basic) 

bAS (basic) 

Calibration due 

dIS (disabled) 

dIS (disabled) 

dIS 

(disabled) 

dIS (disabled) 

 

Power-UP Test Setting – “PUt” 

To select the Power Up Test Configuration, in normal mode, push the Next button to get to “Con” or the 

Configuration menu. Then push the Enter button to enter the Con menu. Then push the Next button to get to the 

second selection “PUt” or Power Up Test setting. Push Enter. If the testis “On” push Next to turn it “OFF” (flashing) 

then push Enter to confirm the change (solid) and push Enter again to return to “PUt” in the Con menu. Push Next 

until “End” is displayed then push Enter to get back to normal operation. 

Alarm Relay Configuration – “Arc”

 

To select the Alarm Relay Configuration, in normal mode, push the Next button to get to “Con” or the Configuration 

menu. Then push the Enter button to enter the Con menu. The sixth selection is the “Arc” or Alarm Relay 

Configuration. Push Next five times to get to “Arc” then Enter. If the relay is “nO” (normally open) push Next to turn 

it to “nC” (flashing) then push Enter to confirm the change (solid) and push Enter again to return to “Arc” in the Con 

menu. Push Next until “End” is displayed then push Enter to get back to normal operation. 

 

Fan Relay Setting – “FrS”

 

To select the Fan Relay setting, in normal mode, push the Next button to get to “Con” or the Configuration menu. 

Then push the Enter button to enter the Con menu. The seventh selection is the “FrS” or Fan Relay setting. Push 

Next six times to get to “FrS” then Enter.  

 

CM-XX:

 If the fan relay is “dIS” (disabled) push Next to change it to 15, 25, 35, 50 or 100 ppm (flashing) 

then push Enter to confirm the change (solid) and push Enter again to return to “FrS” in the Con menu.  

 

GD-XX:

 If the fan relay is “dIS” (disabled) press Next to change it to 3, 4, 5, 6, 7, 8, 9, 10, 11, 12, 13, 14, 

15, 16, 17, 18, 19 or 20% LEL (flashing) then press Enter to confirm the change (solid) and press Enter 

again to return to “FrS” in the Con menu. 

Push Next until “End” is displayed then push Enter to get back to normal operation. 

 

Fan Relay Delay Setting – “Frd” 

To select the Fan Relay Delay setting, in normal mode, push the Next button to get to “Con” or the Configuration 

menu. Then push the Enter button to enter the Con menu. The eighth selection is the “Frd” or Fan Relay Delay. Push 

Next seven times to get to “Frd” then Enter. If the delay is “0” (disabled) push Next to change it to 1, 3, 5, or 10 

minutes (flashing) then push Enter to confirm the change (solid) and push Enter again to return to “Frd” in the Con 

menu. Push Next until “End” is displayed then push Enter to get back to normal operation. 

 

Fan Relay Latching Setting – “FrL” 

To select the Fan Relay Latching Option, in normal mode, push the Next button to get to “Con” or the Configuration 

menu. Then push the Enter button to enter the Con menu. The tenth selection is the “FrL” or Fan Relay Latching 

Option. Push Next nine times to get to “FrL” then Enter. If latching is “OFF” push Next to turn it to “ON” (flashing) 

then push Enter to confirm the change (solid) and push Enter again to return to “FrL” in the Con menu. Push Next 

until “End” is displayed then push Enter to get back to normal operation. 

 

 