46
4. Configure Zones Submenu
5.6
See section 3.3.7 Configure Zones Submenu for more detail
Definitions:
Zone – Defines Sensor Input & Relay / Alarm Output
Group – Set of Sensors of same type and output within the same zone.
Average – Activation based upon an average of sensors in a group
Voting – Number of sensors needed to be above trip point to activate output
Quorum – Number of sensors need to vote, 1 = any sensor.
Press Menu to display Hardware Summary
x 4 Configure Zones
Zone 1 Controls
R_ R_ R_ H_ S_
Enter (underlined) number of output for zone
R = Relay (1, 2 and 3), H = Horn (4), S = Strobe (5)
Z o n e 1 C o n t r o l s
R 1 R 2 R 3 H 4 S 5
Figure A-21 Zone Controls
Configure Group 1
Sensor type - enter #
1=CO, 2=NO2, 3=Combustible, 0=None
Z 1 G r o u p 1 N O 2
S e n s o r T y p e : 2
Figure A-22 Zone Group Type
Sensor Number - enter a two digit number for each sensor to be included in the group (e.g., 01, 02, 03…12.) from 01 through 12.
Z 1 G r o u p 1 N O 2
S e n s o r s : 0 2 , 0 4 , 1 1
Figure A-23 Sensor Selection
Rising (activation) Trip point
Z 1 G r o u p 1 N O 2
R i s i n g : 2 . 5 p p m
Figure A-24 Rising Trip Point Entry
The default rising trip points are:
Description
Carbon
Monoxide
Nitrogen
Dioxide
Combustible
Gas
Ammonia
Hydrogen
Sulfide
Refrigerants
Carbon
Dioxide
Oxygen
Type
CO
NO2
EX
NH3
H2S
REF
CO2
O2
Rising Level
35ppm
2.5ppm
10%
25ppm
8ppm
100ppm
1000ppm
20.3%