22
3.3.2.3
Load Default Configuration
1 L o a d D e f a u l t
C o n f i g u r a t i o n
Figure 3-20 Load Default Configuration
When the number one (1) digit is pressed, the panel will prompt for the password, even if it has been entered previously. If the
password is entered correctly, the panel will overwrite the existing configuration with the default configuration. This operation is
intended to restore the panel to a known basic condition if it is removed from one installation and installed in another.
The default configuration is:
Password 1234
Sensors
Undefined
Alarm signals
Buzzer = Intermittent, Horn = Intermittent, Strobe = Continuous
Warning signals
Buzzer = Off, Horn = Off, Strobe = Off
Trouble signals
Buzzer = Triple Tap, Horn = Off, Strobe = Off
Relay 1
Normally off, 1 minute turn on delay, 1 minute minimum on time
Relay 2
Normally off, 1 minute turn on delay, 1 minute minimum on time
Relay 3
Normally off, 1 minute turn on delay, 1 minute minimum on time
Horn
Normally off, 1 minute turn on delay, 0 (zero) minimum on time
Strobe
Normally off, 1 minute turn on delay, 0 (zero) minimum on time
Zone1
Controls R1,
Zone2 Controls
R2,
Zone3 Controls
R3
Group 1 in each zone Type 1 CO, Voting mode, Quorum = 1
Group 2 in each zone Type 2 NO2, Voting mode, Quorum = 1
Group 3 in each zone Type 3 EX, Voting mode, Quorum = 1
Group 4 in each zone Type 4 NH3, Voting mode, Quorum = 1
Group 5 in each zone Type 5 H2S, Voting mode, Quorum = 1
Group 6 in each zone Type 6 REF, Voting mode, Quorum = 1
Group 7 in each zone Type 7 CO2, Voting mode, Quorum = 1
Group 8 in each zone Type 8 O2, Voting mode, Quorum = 1
Description
Carbon
Monoxide
Nitrogen
Dioxide
Combustible
Gas
Ammonia
Hydrogen
Sulfide
Refrigerants
Carbon
Dioxide
Oxygen
Type
CO
NO2
EX
NH3
H2S
REF
CO2
O2
Range
200 ppm
20 ppm
50%
100 ppm
50ppm
1000 ppm
5,000ppm
25%
Alarm Level
200ppm
5ppm
20%
75ppm
20ppm
300ppm
3,000ppm
19.5%
Warning Level
100ppm
3ppm
15%
50ppm
14ppm
200ppm
2,000ppm
20.0%
Rising Level
35ppm
2.5ppm
10%
25ppm
8ppm
100ppm
1,000ppm
20.3%
Falling Level
15ppm
1.2ppm
5%
10ppm
3ppm
50ppm
800ppm
20.6%
3.3.2.4
Change Password
C h a n g e P a s s w o r d
* * * *
Figure 3-21 Change Password
When the first digit is entered to change the password the panel will prompt for the existing password to be entered (if it hasn’t already
been entered), see section 3.3.2.5 for more detail. Once the current password has been entered, the panel will prompt for the new
password.