10
Network Installation
© 2020 MacroAir Technologies Toll Free: 866 668 3247 Fax: 909 890 2313 www.macroairfans.com
Controller 30 Operation Manual 90-30016-00 Rev A-01 Date: 031920
Network Wiring Configurations cont.
Excess Cable at Connection Point
With noise being emitted throughout a typical industrial/commercial environment,
extra cable
should not be coiled up
as the coil itself will create noise/interference in the communication
signal. There should be no more than 2ft [0.6m] of excess cable at each connection point.
If more than 2ft [0.6m] of cable is needed for future relocation of the fan, run the cable up
toward the ceiling and back down in a horseshoe shape.
ALWAYS AVOID SHARP BENDS OF THE CABLE.