The settings for Total, Accumulated Total and Flow rate are entirely separate. In this way, different units of
measurement and decimals can be used for each e.g. gallons for total and liters for flow rate.
The K-Factor in 4.1 must be entered in pulses per litre (PPL). Entering the k-factor in pulses per gallon (PPG) will result
in inaccurate readings. Refer to page 8 for detailed instruction on entering the k-factor.
*The k-factor in 4.1 MUST ALWAYS be entered in pulses per LITRE, regardless of units in 1.1, 2.1 and 3.1
The PR unit can only accept a Reed switch input, this sensor has been selected as the most common sensor and
requires very little power with small effect on battery life.
The 2 position terminal block is not polarity conscious so the reed switch wires can be connected in any order.
TERMINAL CONNECTORS
1
Total/ Batch Total
Default value
1.1 Unit
L - m
3
- UKGAL - USGAL - UKbbl –USbbl - OILbbl
L
1.2 Decimals
0 - 1 - 2 - 3
0
2
Accumulated Total
2.1 Unit
L - m
3
- UKGAL - USGAL - UKbbl –USbbl - OILbbl
L
2.2 Decimals
0 - 1 - 2 - 3
0
3 Flow Rate
3.1 Unit
L - m
3
- UKGAL - USGAL - UKbbl –USbbl - OILbbl
L
3.2 Time Period
Second - Minute - Hour
Minutes
3.3 Decimals
0 - 1 - 2 - 3
0
3.4 Calculation
per 1 - 255 pulses
10
3.5 Cut-off
0.1 - 999.9 seconds
30
4
Meter
4.1
*K-Factor
(Pulses per Litre)
0000.000 to 9999.999
’1’ or as per factory
settings
5
Others
5.1 Type
dr
dr
5.2 Software Version
03.xx.xx
03.xx.xx
5.3 Serial No.
xxxxxxx
xxxxxxx
SET-UP FUNCTIONS
Connecting any other type of sensor could cause damage to the unit
For meter mounted displays, these terminals come connected from
factory. No further connections are required by end-user.
For remote displays, Reed switch (from flow meter) to be connected
by the end-user.