Optoinsulation
Input can be used as pulse counters (see settings chapter).
4.2 Output
Contact mode
SPDT
2000VA
Maximum switching voltage
250Vac~
Max. current
8A
The output has pulse capability (minimum pulse duration is 100ms, maximum around 100 minutes), so, instead to send two
different commands (one to turn on and one to turn off the ouput), is possible to send a duration command, for example to
drive valves or heaters
As application example, to safely turn on an output, send a ON-pulse command for a defined time (for example, for the
maximum allowed interval), and before the expiring time, another ON-pulse command if the output still needs to be ON, or
a simply OFF command if you want to turn it off.
4.2.1 Time schedule
It is possible to program the device with a weekly calendar, based on day of the week and time, to turn ON and OFF the
output at a defined time:
Max. power commutable
NONE