Fixing
Install clamps with this product should be installed as follows to maintain the IP performance of the device.
a.
Insert the clamp into the slot of the product.
b.
Screw the unit into the panel cut with a screwdriver.
If the screw is over tightened, it may cause the front deformation, thus resulting the touch sensor
can’t work properly Tighten the screws to a torque of 0.2 N.m.
Chapter 7. Wiring
7.1 Power Wiring
(1) The Power cable should have the following specification.
Power Cable Specification
0.75 ~2.5mm
2
(18~12AWG)
F.G Cable Specification
Over 4mm
2
(11AWG)
Conductor Type
Simple or Standard Wire
Bolt tightening force
≥ 0.2 N.m.
Conductor Length
Temperature rating of the
field installed conductors
65℃ Only
(2) The Power terminal should have the following specification
Caution : The use of the Pin Terminal when installing the power supply and ground terminal is