INSTALLATION
■
INSTALLATION
1) Set the unit such that its slider is at the bottom.
2) Hook the upper hook at the rear side of the unit onto the
DIN rail.
3) Push the lower part of the unit in the direction of the arrow.
4) Push up the slider so that the unit is fixed.
5) When removing the unit, push down the slider with a tool
such as a flat-blade screwdriver and pull the lower part of
the unit.
Hook
Slider
■
MOUNTING DIRECTION
The unit must be mounted in an upright position as shown below.
Mounting the unit in other orientations may cause the internal temperature to rise, resulting in shorter product life and/or
deteriorated performance.
UP
DOWN
■
MOUNTING INSIDE CONTROL PANEL unit: mm (inch)
- Secure sufficient ventilation space.
- Do not mount the unit right above devices which radiate great heat
such as heaters, transformers, or resistors.
- Provide adequate maintenance space above and below the unit.
Panel ceiling or wiring conduit (clearance of ≤ 50 mm or 2 in.)
Panel bottom or wiring conduit (clearance of ≤ 50 mm or 2 in.)
50 (2)
50 (2)
50 (2)
40 (1.6)