R7ML-SV4

EM-7805-A  Rev.4  P. 5 / 10

WIRING INSTRUCTIONS

 

SCREW TERMINAL 

Torque

: 0.5 N·m

 

SOLDERLESS TERMINAL  mm (inch)

Refer to the drawing below for recommended ring tongue 
terminal size.  Spade tongue type is also applicable.  Solder-
less terminal:
Applicable wire size: 0.25 to 1.65 mm

2

 (AWG 22 to 16)

Recommended manufacturer: Japan Solderless Terminal 
MFG. Co., Ltd, Nichifu Co., Ltd

6 (.24) max

3.3 (.13) max

mm (inch)

MEChATROLINK CONNECTION

 MECHATROLINK CONNECTION

SRD+
SRD–

SLD

Master

termi-

nator

termi-

nator

Terminator

  Be sure to connect the terminating resistors to the unit at both ends of transmission line.
  Use the terminating resistor dedicated for MECHATROLINK: Model JEPMC-W6022, Yaskawa Controls Co., Ltd.
 Certain types of Master units may have incorporated terminating resistors.  Consult the instruction manual for the Master.

SRD+
SRD–

SLD

SRD+
SRD–

SLD

Slave

SRD+
SRD–

SLD

SRD+
SRD–

SLD

Slave

SRD+
SRD–

SLD

MECHATROLINK

Cable

MECHATROLINK

Cable

*

*

MEChATROLINK COMMUNICATION

 

MECHATROLINK-I

Baud rate

: 4 Mbps

Transmission distance

: 50 m max.

Distance between stations

: 30 cm min.

Transmission media

: MECHATROLINK cable (Model JEPMC-W6003-x-E, Yaskawa Controls Co., Ltd.)

Max. number of slaves

: 15 (The maximum number of slaves might change depending on the master unit. Refer to the manual 

of the master unit)

Transmission cycle

: 2 msec. (fixed)

Data length

: 17 byte

 

MECHATROLINK-II

Baud rate

: 10 Mbps

Transmission distance

: 50 m max.

Distance between stations

: 50 cm min.

Transmission media

: MECHATROLINK cable (Model JEPMC-W6003-x-E, Yaskawa Controls Co., Ltd.)

Max. number of slaves

: 30 (The maximum number of slaves might change depending on the master unit. Refer to the manual 

of the master unit)

Transmission cycle

: 0.5 msec., 1 msec., 1.5 msec., 2 msec., 4 msec., 8 msec.

Data length

: 17 bytes / 32 bytes selectable (Must choose identical data size for all stations on one network)

056 222 38 18

[email protected]

www.sentronic.com

SENTRONIC

AG

Summary of Contents for R7ML-SV4

Page 1: ...E requirements in regard to the whole system and employ additional protective measures to ensure CE conformity POWER INPUT RATING OPERATIONAL RANGE Locate the power input rating marked on the product...

Page 2: ...SD Green Turns on when the module is transmitting RD Green Turns on when the module is receiving STATION ADDRESS Station Address is selected between 60H and 7FH Intel ligent I O in hexadecimal Certai...

Page 3: ...rate factory default 80 msec Sensor type and range Before starting programming turn on the front SW1 5 6 7 8 For more information about the programming using the R7CON please refer to the R7CON Users...

Page 4: ...ion FG terminal is NOT a protective conductor terminal 1 VH0 10 VL0 11 I0 2 COM0 INPUT 0 3 VH1 12 VL1 13 I1 4 COM1 INPUT 1 6 VH2 15 VL2 16 I2 7 COM2 INPUT 2 8 VH3 17 VL3 18 I3 9 COM3 INPUT 3 Input Con...

Page 5: ...e SRD SRD SLD SRD SRD SLD Slave SRD SRD SLD MECHATROLINK Cable MECHATROLINK Cable MECHATROLINK COMMUNICATION MECHATROLINK I Baud rate 4 Mbps Transmission distance 50 m max Distance between stations 30...

Page 6: ...0 0 11 0 0 12 0 0 13 0 0 14 0 0 15 0 0 16 0 0 17 31 0 0 0 0 Byte 17 through 31 are always 0 in the 32 byte mode These bytes are unavailable for MECHATROLINK I or MECHATROLINK II in the 17 byte mode CD...

Page 7: ...ESPONSE REMARKS 0 CDRW 03H ACK 01H Cyclic Data Read Write CDRW Command Link transmission Acknowledge ACK Positive response to CDRW 1 ID_RD 03H ID_RD 03H Read ID ID_RD Command Read out the device ID 2...

Page 8: ...on cycle 8 0 0 9 0 0 10 0 0 11 0 0 12 0 0 13 0 0 14 0 0 15 0 0 16 0 0 17 31 0 0 0 0 Byte 17 through 31 are always 0 in the 32 byte mode These bytes are unavailable for MECHATROLINK I or MECHATROLINK I...

Page 9: ...id Command Command is not supported Warning 02H Command Not Allowed Command execution conditions are not met Warning 03H Invalid Data Data in the command is not correct Warning 04H Synchronization Err...

Page 10: ...et R7ML EC16x R7ML EC8x Output data are repeated EXT IN HI Extension data high 8 bits R7ML EA16 Bit 8 through 15 data are set R7ML EC16x Output data are repeated R7ML EA8 R7ML EC8x Unused Extension Ou...

Reviews: