R7ML-SV4

EM-7805-A  Rev.4  P. 1 / 10

DC VOLTAGE/CURRENT INPUT MODULE, 4 points

(MECHATROLINK-

I

 / -

II

)

MODEL

R7ML-SV4

INSTRUCTION MANUAL

BEFORE USE ....

Thank you for choosing M-System.  Before use, please check 
contents of the package you received as outlined below.
If you have any problems or questions with the product, 
please contact M-System’s Sales Office or representatives.

 

PACKAGE INCLUDES:

DC voltage/current input module .......................................(1)

 

MODEL NO.

Confirm Model No. marking on the product to be exactly
what you ordered.

 

INSTRUCTION MANUAL

This manual describes necessary points of caution when
you use this product, including installation, connection and
basic maintenance procedures.

POINTS OF CAUTION

 

CONFORMITY WITH EU DIRECTIVE

• Use MECHATROLINK-II network cable with core (Yasu-

kawa Controls Model JEPMC-W6003-x-E) or equivalent
for the network.

• Ground the FG terminal.

• The actual installation environments such as panel con-

figurations, connected devices and connected wires may

affect the protection level of this unit when it is integrat-

ed in a panel system. The user may have to review the CE

requirements in regard to the whole system and employ

additional protective measures to ensure CE conformity.

 

POWER INPUT RATING & OPERATIONAL RANGE

• Locate the power input rating marked on the product and

confirm its operational range as indicated below:
24V DC rating: 24V ±10%, approx. 70mA

 

GENERAL PRECAUTIONS

• Before you remove the unit or mount it, turn off the power 

supply and input signal for safety.

 

ENVIRONMENT

• Indoor use
• When heavy dust or metal particles are present in the

air, install the unit inside proper housing with sufficient
ventilation.

• Do not install the unit where it is subjected to continuous

vibration.  Do not subject the unit to physical impact.

• Environmental temperature must be within 0 to 55°C (32

to 131°F) with relative humidity within 30 to 90% RH in
order to ensure adequate life span and operation.

 

WIRING

• Do not install cables close to noise sources (relay drive

cable, high frequency line, etc.).

• Do not bind these cables together with those in which

noises are present.  Do not install them in the same duct.

 

AND ....

• The unit is designed to function as soon as power is sup-

plied, however, a warm up for 10 minutes is required for
satisfying complete performance described in the data
sheet.

056 222 38 18

[email protected]

www.sentronic.com

SENTRONIC

AG

Summary of Contents for R7ML-SV4

Page 1: ...E requirements in regard to the whole system and employ additional protective measures to ensure CE conformity POWER INPUT RATING OPERATIONAL RANGE Locate the power input rating marked on the product...

Page 2: ...SD Green Turns on when the module is transmitting RD Green Turns on when the module is receiving STATION ADDRESS Station Address is selected between 60H and 7FH Intel ligent I O in hexadecimal Certai...

Page 3: ...rate factory default 80 msec Sensor type and range Before starting programming turn on the front SW1 5 6 7 8 For more information about the programming using the R7CON please refer to the R7CON Users...

Page 4: ...ion FG terminal is NOT a protective conductor terminal 1 VH0 10 VL0 11 I0 2 COM0 INPUT 0 3 VH1 12 VL1 13 I1 4 COM1 INPUT 1 6 VH2 15 VL2 16 I2 7 COM2 INPUT 2 8 VH3 17 VL3 18 I3 9 COM3 INPUT 3 Input Con...

Page 5: ...e SRD SRD SLD SRD SRD SLD Slave SRD SRD SLD MECHATROLINK Cable MECHATROLINK Cable MECHATROLINK COMMUNICATION MECHATROLINK I Baud rate 4 Mbps Transmission distance 50 m max Distance between stations 30...

Page 6: ...0 0 11 0 0 12 0 0 13 0 0 14 0 0 15 0 0 16 0 0 17 31 0 0 0 0 Byte 17 through 31 are always 0 in the 32 byte mode These bytes are unavailable for MECHATROLINK I or MECHATROLINK II in the 17 byte mode CD...

Page 7: ...ESPONSE REMARKS 0 CDRW 03H ACK 01H Cyclic Data Read Write CDRW Command Link transmission Acknowledge ACK Positive response to CDRW 1 ID_RD 03H ID_RD 03H Read ID ID_RD Command Read out the device ID 2...

Page 8: ...on cycle 8 0 0 9 0 0 10 0 0 11 0 0 12 0 0 13 0 0 14 0 0 15 0 0 16 0 0 17 31 0 0 0 0 Byte 17 through 31 are always 0 in the 32 byte mode These bytes are unavailable for MECHATROLINK I or MECHATROLINK I...

Page 9: ...id Command Command is not supported Warning 02H Command Not Allowed Command execution conditions are not met Warning 03H Invalid Data Data in the command is not correct Warning 04H Synchronization Err...

Page 10: ...et R7ML EC16x R7ML EC8x Output data are repeated EXT IN HI Extension data high 8 bits R7ML EA16 Bit 8 through 15 data are set R7ML EC16x Output data are repeated R7ML EA8 R7ML EC8x Unused Extension Ou...

Reviews: