R7M-YV2
P. 2 / 7
EM-7803-D Rev.5
5-2-55, Minamitsumori, Nishinari-ku, Osaka 557-0063 JAPAN
Phone: +81(6)6659-8201 Fax:
+81(6)6659-8510 E-mail: [email protected]
COMPONENT IDENTIFICATION
5
4
3
2 1 0 9
8
7
6
5
4
3
2 1 0 9
8
7
6
5
4
3
2 1 0 9
8
7
6
ERR
RD
RUN
SD
PWR
X10
X1
STATION ADD.
B.RATE
CNFG.
1 2 3 4 5 6 7 8
4
5
6
7
1
2
3
2
3
4
1
5
10
7
8
9
6
(A) Status Indicator LED
(B) Station Address Setting Rotary SW
(C) Baud Rate Setting Rotary SW
(D) Operating Mode Setting DIP SW (SW1)
(E) PC Configurator Jack
(F) CC-Link, Power Supply Terminals
(G) Output Terminals
(A)
(F)
(G)
(B)
(C)
(D)
(E)
■
STATUS INDICATOR LED
ID
COLOR FUNCTION
PWR
Red
Turns on when the internal 5V is supplied
normally.
RUN
Red
Turns on when the data is received nor-
mally.
ERR
Red
Turns on when the received data is abnor-
mal. Blinks when setting is abnormal.
SD
Red
Turns on when the module is transmitting.
RD
Red
Turns on when the module is receiving.
■
NODE ADDRESS
Node Address is selected between 1 and 99 in decimal. The
left switch determines the tenth place digit, while the right
switch does the ones place digit of the address.
5
4
3
2
1
0
9
8
7
6
5
4
3
2
1
0
9
8
7
6
Node Address Setting (x1)
Factory setting : 00
Node Address Setting (x10)
■
BAUD RATE
Baud Rate is selected with the rotary switch.
5
4
3
2
1
0
9
8
7
6
Baud Rate Setting
0 : 38.4 kbps (factory setting)
1 : 19.2 kbps
2 : 9600 bps
3 : 4800 bps
■
EXTENSION MODULE
Combinations with all extension modules are selectable.
■
OPERATING MODE
(*) Factory setting
•
Extension (SW1-1, 1-2)
SW1-1
SW1-2 EXTENSION
OFF
OFF
No extension (*)
ON
OFF
Discrete input, 8 or 16 points
OFF
ON
Discrete output, 8 or 16 points
•
Output at the Loss of Communication (SW1-4)
SW1-4 OUTPUT AT THE LOSS OF COMMUNICATION
OFF
Reset the output (to -15% or approx. -11.5V DC)
ON
Hold the output (*)
(maintains the last data received normally)
•
Output Range (SW1-5, 1-6, 1-7, 1-8)
SW1-5
SW1-6
SW1-7
SW1-8 OUTPUT RANGE
OFF
OFF
OFF
OFF
-10 – +10V DC (*)
ON
OFF
OFF
OFF
-5 – +5V DC
OFF
ON
OFF
OFF
-1 – +1V DC
ON
ON
OFF
OFF
0 – 10V DC
OFF
OFF
ON
OFF
0 – 5V DC
ON
OFF
ON
OFF
1 – 5V DC
OFF
ON
ON
OFF
0 – 1V DC
ON
ON
ON
OFF
-0.5 – +0.5V DC
ON
ON
ON
ON
PC Configurator setting
Note : Be sure to set unused SW1-3 to OFF.
■
POWER SUPPLY, MODBUS TERMINAL ASSIGNMENT
4
DA
5
DG
6
+24V
1
DB
2
SLD
3
FG
7
0V
NO.
ID
FUNCTION, NOTES
1
DB
----
2
SLD
Shield
3
FG
FG
4
DA
----
5
DG
----
6
+24V
Power input (24V DC)
7
0V
Power input (0V)
■
OUTPUT TERMINAL ASSIGNMENT
6
NC
7
VH0
8
VL0
1
NC
2
COM0
3
COM0
9
VH1
4
COM1
10
VL1
5
COM1
NO.
ID
FUNCTION
NO.
ID
FUNCTION
1
NC
No connection
6
NC
No connection
2 COM0 Common 0
7
VH0 Wide span volt. 0
3 COM0 Common 0
8
VL0 Narrow span volt. 0
4 COM1 Common 1
9
VH1 Wide span volt. 1
5 COM1 Common 1
10
VL1 Narrow span volt. 1
■
OUTPUT RANGE
•
Wide span
: -10 – +10V DC, -5 – +5V DC, 0 – 10V DC,
0 – 5V DC, 1 – 5V DC
•
Narrow span
: -1 – +1V DC, 0 – 1V, -0.5 – +0.5V DC