R7M-YS2

P. 3 / 7

EM-7803-E Rev.5

WIRING INSTRUCTIONS

 

SCREW TERMINAL  

Torque

: 0.5 N·m

 

SOLDERLESS TERMINAL  mm (inch)

Refer to the drawing below for recommended ring tongue 
terminal size.  Spade tongue type is also applicable.  Solder-
less terminals with insulation sleeve do not fit.  
Communication cable: Applicable wire size 0.2 to 0.5 mm2 
(AWG26 - 22)
Recommended manufacturer: Japan Solderless Terminal
MFG.Co.Ltd
Others: 0.25 to 1.65 mm2 (AWG 22 to 16)
Recommended manufacturer: Japan Solderless Terminal
MFG.Co.Ltd, Nichifu Co.,ltd

6 (.24) max

3.3 (.13) max

mm (inch)

EXTERNAL DIMENSIONS

  unit: mm (inch)

2

3

4

1

5

10

7

8

9

6

4

5

6

7

1

2

3

30 (1.18)

[5 (.20)]

3 (.12)

5.5 (.22)

7–M3 SCREW

TERMINALS

for Modbus, POWER

10–M3 SCREW 

TERMINALS

for OUTPUT

DIN RAIL

35mm wide

54 (2.13)

17 (.66)

6 (.24)

50 (1.97)

6 (.24)

18.5 (.73)

115 (4.53)

CONNECTION DIAGRAM

Connect the unit as in the diagram below.

4

7

6

3

2

5

1

0V

24VDC

FG

SLD

DG

DB

DA

7

I0

2

COM0

9

4

OUTPUT 0

I1

COM1

OUTPUT 1

EXTENSION CONNECTOR

In order to improve EMC performance, bond the FG
terminal to ground.
Caution: FG terminal is NOT a protective conductor terminal.

MASTER CONNECTION

 MASTER CONNECTION

Tx+/Rx+
Tx–/Rx–

SG

Rx+
Rx–

Host PC

DA
DB

DG

SLD

FG

Remote Unit

DA
DB

DG

SLD

FG

Remote Unit

TERMINATOR

TERMINATOR

Be sure to connect the terminating resistor included in the product package to the unit at both ends of transmission line.
The terminator must be connected across DA and DB.
The Host PC can be located other than at the extreme ends of transmission line.

056 222 38 18

[email protected]

www.sentronic.com

SENTRONIC

AG

Summary of Contents for R7M-YS2

Page 1: ...ed inside the instrument panel of a metal enclosure The actual installation environments such as panel con figurations connected devices and connected wires may affect the protection level of this uni...

Page 2: ...ress Setting x10 BAUD RATE Baud Rate is selected with the rotary switch 5 4 3 2 1 0 9 8 7 6 Baud Rate Setting 0 38 4 kbps factory setting 1 19 2 kbps 2 9600 bps 3 4800 bps EXTENSION MODULE Combination...

Page 3: ...dbus POWER 10 M3 SCREW TERMINALS for OUTPUT DIN RAIL 35mm wide 54 2 13 17 66 6 24 50 1 97 6 24 18 5 73 115 4 53 CONNECTION DIAGRAM Connect the unit as in the diagram below 4 7 6 3 2 5 1 0V 24VDC FG SL...

Page 4: ...a thick cable to maintain low imped ance at high frequency Use shielded cables for the signals taken out of the control panel Choose a thick and short cable to ground the FG terminal of the R7M module...

Page 5: ...d the panel cover with an earth strap grounding may be strengthened and EMC may be improved Ground the control panel at low impedance using e g braided wires Keep the opening for ventilation as small...

Page 6: ...ons are illustrated in the next page Keep cables as short as possible It prevents noise emissions from the cables and noise overlapping to the cables Attach a ferrite core to reduce noise impact to th...

Page 7: ...us Keep the cable as short as possible To external apparatus Shielded Cable Earth Clamp Remove a part of the shielded cable cover and ground it to the internal panel plate using an earth clamp To conn...

Reviews: