CONNECTION DIAGRAM
Connect the unit as in the diagram below.
4
7
6
3
2
5
1
0V
24VDC
FG
SLD
DG
DB
DA
10
+IN0
11
–IN0
1
+CJ0
2
–CJ0
+IN1
–IN1
+CJ1
–CJ1
+IN2
–IN2
+CJ2
–CJ2
+IN3
–IN3
+CJ3
–CJ3
INPUT 0
12
13
3
4
INPUT 1
15
16
6
7
INPUT 2
17
18
8
9
INPUT 3
■
Input Connection Example
+INn
–INn
+CJn
–CJn
T/C
+
–
CJC
SENSOR
+INn
–INn
Short
CJC
SENSOR
+CJn
–CJn
•
Unused Input Channels
Close across the unused input terminals as shown below.
(Choose K (CA) thermocouple for unused channels.)
EXTENSION CONNECTOR
In order to improve EMC performance, bond the FG
terminal to ground.
Caution: FG terminal is NOT a protective conductor terminal.
WIRING INSTRUCTIONS
■
SCREW TERMINAL
Torque
: 0.5 N·m
■
SOLDERLESS TERMINAL mm (inch)
Refer to the drawing below for recommended ring tongue
terminal size. Spade tongue type is also applicable. Solder-
less terminal:
Applicable wire size: 0.25 to 1.65 mm2 (AWG 22 to 16)
Recommended manufacturer: Japan Solderless Terminal
MFG. Co., Ltd, Nichifu Co., Ltd
6 (.24) max
3.3 (.13) max
mm (inch)
MASTER CONNECTION
■
MASTER CONNECTION
Tx+/Rx+
Tx–/Rx–
SG
Rx+
Rx–
Host PC
DA
DB
DG
SLD
FG
Remote Unit
DA
DB
DG
SLD
FG
Remote Unit
TERMINATOR
TERMINATOR
Be sure to connect the terminating resistor included in the product package to the unit at both ends of transmission line.
The terminator must be connected across DA and DB.
The Host PC can be located other than at the extreme ends of transmission line.